Consider a three-phase generator rated 3 00 MVA , 23 kV , supplying a system load of 240 MA and 0.9 power factor lagging at 230 kV through a 33 0 MVA , 23 Δ / 23 0 Y-kV step-up transformer with a leakage reactance of 0.11 per unit. (a) Neglecting the exciting current and choosing base values at the load of 100 MVL and 230 kV. Find the phasor currents I A , I B , and I C supplied to the load in per unit. (b) By choosing the load terminal voltage I A as reference, specify the proper base for the generator circuit and determine the generator voltage V as well as the phasor currents I A , I B , and I C , from the generator. ( Note: Take into account the phase shift of the transformer.) (C) Find the generator terminal voltage in kV and the real power supplied by the generator in MW. (d) By omitting the transformer phase shift altogether, check to see whether you get the same magnitude of generator terminal voltage and real power delivered by the generator.
Consider a three-phase generator rated 3 00 MVA , 23 kV , supplying a system load of 240 MA and 0.9 power factor lagging at 230 kV through a 33 0 MVA , 23 Δ / 23 0 Y-kV step-up transformer with a leakage reactance of 0.11 per unit. (a) Neglecting the exciting current and choosing base values at the load of 100 MVL and 230 kV. Find the phasor currents I A , I B , and I C supplied to the load in per unit. (b) By choosing the load terminal voltage I A as reference, specify the proper base for the generator circuit and determine the generator voltage V as well as the phasor currents I A , I B , and I C , from the generator. ( Note: Take into account the phase shift of the transformer.) (C) Find the generator terminal voltage in kV and the real power supplied by the generator in MW. (d) By omitting the transformer phase shift altogether, check to see whether you get the same magnitude of generator terminal voltage and real power delivered by the generator.
Consider a three-phase generator rated
3
00
MVA
,
23 kV
, supplying a system load of 240 MA and 0.9 power factor lagging at 230 kV through a
33
0
MVA
,
23
Δ
/
23
0
Y-kV
step-up transformer with a leakage reactance of 0.11 per unit. (a) Neglecting the exciting current and choosing base values at the load of 100 MVL and 230 kV. Find the phasor currents
I
A
,
I
B
,
and
I
C
supplied to the load in per unit. (b) By choosing the load terminal voltage
I
A
as reference, specify the proper base for the generator circuit and determine the generator voltage V as well as the phasor currents
I
A
,
I
B
,
and
I
C
,
from the generator. (Note: Take into account the phase shift of the transformer.) (C) Find the generator terminal voltage in kV and the real power supplied by the generator in MW. (d) By omitting the transformer phase shift altogether, check to see whether you get the same magnitude of generator terminal voltage and real power delivered by the generator.
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
How does a Transformer work - Working Principle electrical engineering; Author: The Engineering Mindset;https://www.youtube.com/watch?v=UchitHGF4n8;License: Standard Youtube License