Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X 1 = 0.24 Ω (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio η = N 2 / N 1 = 10 . The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, V a ' η ' as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.
Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X 1 = 0.24 Ω (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio η = N 2 / N 1 = 10 . The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, V a ' η ' as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.
Solution Summary: The author calculates the power factor of a three-phase transformer bank, which is supplying 100MW at 0.8 pf lagging to the bus having voltage 230kV.
Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by
X
1
=
0.24
Ω
(on the low-voltage side), negligible resistance and magnetizing current, and turns ratio
η
=
N
2
/
N
1
=
10
. The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV.
(a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus,
V
a
'
η
'
as the reference Account for the phase shift, and assume positive-sequence operation.
(b) Find the phase shift between the primary and secondary voltages.
Chat gpt responses and ai responses are reported immediately as im here paying my own money for expert solutions other than that please solve this question step by step handwritten solution thanks for understanding
A 4-cell reuse cellular system is being rolled out into an operation area and you are the engineer taking charge of this project. The subscriber density for the operation area is 600 people per km2. The average traffic load generated per subscriber is 0.2 Er. You are required to deploy 8 clusters of cells in the operation area and provide a Grade of Service of 0.5% to the subscribers using the blocked calls cleared model. You found out that the total number of trunk channels available to the system is 140. Assuming that fixed channel assignment is used, compute:
a) The traffic load that can be offered to the operation area.
b) The size of the operation area (in km2) that can be supported by the system.
c) The proposed cell area and radius, based on the operation area determined in part (b).
Having successfully implemented the first system above, you are now tasked to implement another system. The requirement is that, this second system must have a cluster size of 7 and provides a…
NO AI PLEASE
Chapter 3 Solutions
Power System Analysis and Design (MindTap Course List)
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.