Textbook Question
Chapter 2, Problem 2.45P
Two balanced Y-connected loads, one drawing 10 kW at 0.8 power factor lagging and the other IS kW at 0.9 power factor leading, are connected in parallel and supplied by a balanced three-phase Y-connected, 480-V source. (a) Determine the source current. (b) If the load neutrals are connected to the source neutral by a zero-ohm neutral wire through an ammeter, what will the ammeter read?
Expert Solution & Answer
Trending nowThis is a popular solution!
Students have asked these similar questions
(b) A symmetrical three-wire three-phase supply as shown in Figure Q2(b) is connected to a
balanced three-phase load. The value of impedance, Z is identified to be 100-j75 Q.
(i)
Find IaB, IBC and ICa
(ii)
Determine Iaa, IbB and Ic
(iii)
Determine Iba, Isb and Ix
(iv)
Draw the phasor diagram of all currents in Q(b)(i) and Q(b)(ii)
Three load units A, B and C are connected in parallel and take currents that are respectively 12, 10 and 15 amperes. Assuming IA to be the reference phasor, IB leads IA by 30°, and IC lags IA by 65°, calculate the total current and the angle it makes with the reference.
If you have 3-phase power and you need to step down (or up) in 3-phase voltage, how many single-phase transformers are needed? Explain.
Chapter 2 Solutions
Power System Analysis and Design (MindTap Course List)
Ch. 2 - The rms value of v(t)=Vmaxcos(t+) is given by a....Ch. 2 - If the rms phasor of a voltage is given by V=12060...Ch. 2 - If a phasor representation of a current is given...Ch. 2 - Prob. 2.4MCQCh. 2 - Prob. 2.5MCQCh. 2 - Prob. 2.6MCQCh. 2 - Prob. 2.7MCQCh. 2 - Prob. 2.8MCQCh. 2 - Prob. 2.9MCQCh. 2 - The average value of a double-frequency sinusoid,...
Ch. 2 - The power factor for an inductive circuit (R-L...Ch. 2 - The power factor for a capacitive circuit (R-C...Ch. 2 - Prob. 2.13MCQCh. 2 - The instantaneous power absorbed by the load in a...Ch. 2 - Prob. 2.15MCQCh. 2 - With generator conyention, where the current...Ch. 2 - Consider the load convention that is used for the...Ch. 2 - Prob. 2.18MCQCh. 2 - The admittance of the impedance j12 is given by...Ch. 2 - Consider Figure 2.9 of the text, Let the nodal...Ch. 2 - The three-phase source line-to-neutral voltages...Ch. 2 - In a balanced three-phase Y-connected system with...Ch. 2 - In a balanced system, the phasor sum of the...Ch. 2 - Consider a three-phase Y-connected source feeding...Ch. 2 - For a balanced- load supplied by a balanced...Ch. 2 - A balanced -load can be converted to an...Ch. 2 - When working with balanced three-phase circuits,...Ch. 2 - The total instantaneous power delivered by a...Ch. 2 - The total instantaneous power absorbed by a...Ch. 2 - Under balanced operating conditions, consider the...Ch. 2 - One advantage of balanced three-phase systems over...Ch. 2 - While the instantaneous electric power delivered...Ch. 2 - Given the complex numbers A1=630 and A2=4+j5, (a)...Ch. 2 - Convert the following instantaneous currents to...Ch. 2 - The instantaneous voltage across a circuit element...Ch. 2 - For the single-phase circuit shown in Figure...Ch. 2 - A 60Hz, single-phase source with V=27730 volts is...Ch. 2 - (a) Transform v(t)=75cos(377t15) to phasor form....Ch. 2 - Let a 100V sinusoidal source be connected to a...Ch. 2 - Consider the circuit shown in Figure 2.23 in time...Ch. 2 - For the circuit shown in Figure 2.24, compute the...Ch. 2 - For the circuit element of Problem 2.3, calculate...Ch. 2 - Prob. 2.11PCh. 2 - The voltage v(t)=359.3cos(t)volts is applied to a...Ch. 2 - Prob. 2.13PCh. 2 - A single-phase source is applied to a...Ch. 2 - Let a voltage source v(t)=4cos(t+60) be connected...Ch. 2 - A single-phase, 120V(rms),60Hz source supplies...Ch. 2 - Consider a load impedance of Z=jwL connected to a...Ch. 2 - Let a series RLC network be connected to a source...Ch. 2 - Consider a single-phase load with an applied...Ch. 2 - A circuit consists of two impedances, Z1=2030 and...Ch. 2 - An industrial plant consisting primarily of...Ch. 2 - The real power delivered by a source to two...Ch. 2 - A single-phase source has a terminal voltage...Ch. 2 - A source supplies power to the following three...Ch. 2 - Consider the series RLC circuit of Problem 2.7 and...Ch. 2 - A small manufacturing plant is located 2 km down a...Ch. 2 - An industrial load consisting of a bank of...Ch. 2 - Three loads are connected in parallel across a...Ch. 2 - Prob. 2.29PCh. 2 - Figure 2.26 shows three loads connected in...Ch. 2 - Consider two interconnected voltage sources...Ch. 2 - Prob. 2.35PCh. 2 - Prob. 2.36PCh. 2 - Prob. 2.37PCh. 2 - Prob. 2.38PCh. 2 - Prob. 2.39PCh. 2 - A balanced three-phase 240-V source supplies a...Ch. 2 - Prob. 2.41PCh. 2 - A balanced -connected impedance load with (12+j9)...Ch. 2 - A three-phase line, which has an impedance of...Ch. 2 - Two balanced three-phase loads that are connected...Ch. 2 - Two balanced Y-connected loads, one drawing 10 kW...Ch. 2 - Three identical impedances Z=3030 are connected in...Ch. 2 - Two three-phase generators supply a three-phase...Ch. 2 - Prob. 2.48PCh. 2 - Figure 2.33 gives the general -Y transformation....Ch. 2 - Consider the balanced three-phase system shown in...Ch. 2 - A three-phase line with an impedance of...Ch. 2 - A balanced three-phase load is connected to a...Ch. 2 - What is a microgrid?Ch. 2 - What are the benefits of microgrids?Ch. 2 - Prob. CCSQCh. 2 - Prob. DCSQ
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- 6. 150 kVA, 2800-240 V, 50 Hz transformer. Regis = 0.0082N , Xeq.Ls = 0.0223N RfcHs=2200N Step down transformer delivers 135 kW to a load at 0.9 lagging power factor at rated voltage. Determine the Following: a) Terminal voltage (LV side). b) Terminal voltage (HV side). c) High side current. d) Input impedance. e) Voltage regulation. f) Efficiency. g) Voltage regulation for 0.9 leading pf. h) Draw the phasor diagram of secondary circuit at 0.9 lagging pf. i) Draw the phasor diagram of secondary circuit at 0.9 leading pf. XmHs=12002arrow_forwardPlease answer correct with reasonarrow_forwardconductor radius is 0.75cmarrow_forward
- Two 7970-V:230-V single-phase transformers with impedance with respect to their secondaries of 1.5 + j3 and 2 + j4.5 ohms are connected in parallel to a 7900-V source. Their secondaries are supplying a common load of 30 + j40 ohms. A. What is the magnitude of the voltage across the load in volts? (2 decimal places) B. What is the magnitude of the total current supplied by the 7900-V source in amperes? (3 decimal places) C. What is the efficiency of the parallel transformers combined in percent? ( 1 decimal place)arrow_forwardThree single phase transformers each having a 240 V primary and two 250 V secondaries, as shown in the figure below, is to be connected to a 400 V, 3–phase supply to give a six phase output. A d e В f Show how this is done and find the voltage between adjacent phases of the 6-phase output.arrow_forwardConsider Two same size series connected PV modules,each with the specification as Po=100W, Voc= 24.5V and Isc=5A.then choose the correct Statement Refer to this PV Panel. a.The output power from this panel is 100W , the Voltage is 24.5V and the current is 10A b.The output power from this panel is 200W , the Voltage is 24.5V and the current is 10A c.The output power from this panel is 200W , the Voltage is 49V and the current is 5A d.The output power from this panel is 200W , the Voltage is 49V and the current is 10AClear my choicearrow_forward
- Problem 5 Consider a three winding transformer with the following particulars: = Z₁ Z2 Z3 =0.02 + j0.08 £, V₂ = 400 V, 12 = 60/30° A, and I3 = 50/-40° A. Assume that V₂ is the reference phasor, calculate: The intermediate voltage Vo. a. b. The primary current I₁ and the primary voltage V₁. c. The tertiary voltage V3 referred to the primary side. d. The apparent powers and the power factors at the primary, secondary and tertiary terminals. e. The transformer efficiency.arrow_forwardi can't figure out the configuration of this xfmr.arrow_forwardA source of AC emf E₁ = 100/00 volts with an impedance of Z₁ = 20/0° ohms is connected in parallel with another AC source of E₂ = 100/53.1º volts with an impedance Z₂ = 20/0° ohms. The two AC source are use to supply a load impedance of Z₁ = 20/-900 ohms. Calculate the value of the load current IL. O a. 10 amperes O b. 12 amperes O C. 4 amperes O d. 8 amperesarrow_forward
- In the system shown in Figure 1, the transformers are connected star-star with both star points grounded and the generators are connected in star with thier star points grounded. The system base is 15 MVA. The transformers all have reactances of 0.04 p.u. on this 15 MVA base. The reactances of all other elements are given in Table 1 (in 2) and the voltage levels are given in Table 2. p.u. G1 p.u. T1 jö Per-Unit Convert all values to p.u. on a 15 MVA base. Xa= p.u. Xc₂= XL = V BABE G1 2 X 9 T3 Figure 1: A section of the distribution system T1 L Table 1: Sequence reactances (2) 3 G1 L G2 0.3 0.59 0.01 4 L 9/10 10 Fault Voltage What is the voltage at bus 3 (in Volts) after the fault has occurred? Vp= V T2 5 T2 34 10/4 Table 2: Voltage bases (kV) G2 4 T3 10/9 | G2 Fault Current A three-phase fault with a fault reactance of 0.01 p.u. occurs at bus 3. Calculate the fault current flowing at the fault point in KA. Ip=-j KA Soarrow_forwardTwo transformers of different apparent power ratings connected in parallel can supply a. a maximum load equal to twice the larger rating. b. a maximum load equal to one-half of the sum of both ratings. C. a maximum load equal to twice the smaller rating. d. a maximum load equal to the sum of both ratings.arrow_forwardWhat will be the value of the twiddle factor: W42arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
Electrical Measuring Instruments - Testing Equipment Electrical - Types of Electrical Meters; Author: Learning Engineering;https://www.youtube.com/watch?v=gkeJzRrwe5k;License: Standard YouTube License, CC-BY
01 - Instantaneous Power in AC Circuit Analysis (Electrical Engineering); Author: Math and Science;https://www.youtube.com/watch?v=If25y4Nhvw4;License: Standard YouTube License, CC-BY