Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN: 9781305632134
Author: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher: Cengage Learning
expand_more
expand_more
format_list_bulleted
Concept explainers
Question
Chapter 2, Problem 2.48P
To determine
(a)
The power triangle of each load and the combine load.
To determine
(b)
The power factor of the combined load and state whether lagging or leading.
To determine
(c)
The magnitude of the line current from the source.
To determine
(d)
The capacitive reactance is needed in each leg to make the source power factor unity.
To determine
(e)
The magnitude of the current in each capacitor and the line current from the source.
Expert Solution & Answer
Trending nowThis is a popular solution!
Students have asked these similar questions
Connect three single-phase transformers in Y-Y, with subtractive polarity, so that the line-to-line voltages on the primary are 30 degrees delayed to their respective line-to-line voltages on the secondary. It should show each step that is needed to make this connection (example: the phasor diagram) and should show the final connection of the three transformers including the polarity markings. Assume phase A on the primary is terminal "H1".
2- Draw and explain the phasor diagram for two transformers in parallel.
In the system shown in Figure 1, the transformers are connected star-star with both star points grounded and the generators are connected in
star with thier star points grounded. The system base is 15 MVA. The transformers all have reactances of 0.04 p.u. on this 15 MVA base. The
reactances of all other elements are given in Table 1 (in 2) and the voltage levels are given in Table 2.
p.u.
G1
p.u.
T1
jö
Per-Unit
Convert all values to p.u. on a 15 MVA base.
Xa=
p.u.
Xc₂=
XL =
V BABE
G1
2
X
9
T3
Figure 1: A section of the distribution system
T1
L
Table 1: Sequence reactances (2)
3
G1 L G2
0.3 0.59 0.01
4
L
9/10 10
Fault Voltage
What is the voltage at bus 3 (in Volts) after the fault has occurred?
Vp=
V
T2
5
T2
34
10/4
Table 2: Voltage bases (kV)
G2
4
T3
10/9
|
G2
Fault Current
A three-phase fault with a fault reactance of 0.01 p.u. occurs at bus 3. Calculate the fault current flowing at the fault point in KA.
Ip=-j
KA
So
Chapter 2 Solutions
Power System Analysis and Design (MindTap Course List)
Ch. 2 - The rms value of v(t)=Vmaxcos(t+) is given by a....Ch. 2 - If the rms phasor of a voltage is given by V=12060...Ch. 2 - If a phasor representation of a current is given...Ch. 2 - Prob. 2.4MCQCh. 2 - Prob. 2.5MCQCh. 2 - Prob. 2.6MCQCh. 2 - Prob. 2.7MCQCh. 2 - Prob. 2.8MCQCh. 2 - Prob. 2.9MCQCh. 2 - The average value of a double-frequency sinusoid,...
Ch. 2 - The power factor for an inductive circuit (R-L...Ch. 2 - The power factor for a capacitive circuit (R-C...Ch. 2 - Prob. 2.13MCQCh. 2 - The instantaneous power absorbed by the load in a...Ch. 2 - Prob. 2.15MCQCh. 2 - With generator conyention, where the current...Ch. 2 - Consider the load convention that is used for the...Ch. 2 - Prob. 2.18MCQCh. 2 - The admittance of the impedance j12 is given by...Ch. 2 - Consider Figure 2.9 of the text, Let the nodal...Ch. 2 - The three-phase source line-to-neutral voltages...Ch. 2 - In a balanced three-phase Y-connected system with...Ch. 2 - In a balanced system, the phasor sum of the...Ch. 2 - Consider a three-phase Y-connected source feeding...Ch. 2 - For a balanced- load supplied by a balanced...Ch. 2 - A balanced -load can be converted to an...Ch. 2 - When working with balanced three-phase circuits,...Ch. 2 - The total instantaneous power delivered by a...Ch. 2 - The total instantaneous power absorbed by a...Ch. 2 - Under balanced operating conditions, consider the...Ch. 2 - One advantage of balanced three-phase systems over...Ch. 2 - While the instantaneous electric power delivered...Ch. 2 - Given the complex numbers A1=630 and A2=4+j5, (a)...Ch. 2 - Convert the following instantaneous currents to...Ch. 2 - The instantaneous voltage across a circuit element...Ch. 2 - For the single-phase circuit shown in Figure...Ch. 2 - A 60Hz, single-phase source with V=27730 volts is...Ch. 2 - (a) Transform v(t)=75cos(377t15) to phasor form....Ch. 2 - Let a 100V sinusoidal source be connected to a...Ch. 2 - Consider the circuit shown in Figure 2.23 in time...Ch. 2 - For the circuit shown in Figure 2.24, compute the...Ch. 2 - For the circuit element of Problem 2.3, calculate...Ch. 2 - Prob. 2.11PCh. 2 - The voltage v(t)=359.3cos(t)volts is applied to a...Ch. 2 - Prob. 2.13PCh. 2 - A single-phase source is applied to a...Ch. 2 - Let a voltage source v(t)=4cos(t+60) be connected...Ch. 2 - A single-phase, 120V(rms),60Hz source supplies...Ch. 2 - Consider a load impedance of Z=jwL connected to a...Ch. 2 - Let a series RLC network be connected to a source...Ch. 2 - Consider a single-phase load with an applied...Ch. 2 - A circuit consists of two impedances, Z1=2030 and...Ch. 2 - An industrial plant consisting primarily of...Ch. 2 - The real power delivered by a source to two...Ch. 2 - A single-phase source has a terminal voltage...Ch. 2 - A source supplies power to the following three...Ch. 2 - Consider the series RLC circuit of Problem 2.7 and...Ch. 2 - A small manufacturing plant is located 2 km down a...Ch. 2 - An industrial load consisting of a bank of...Ch. 2 - Three loads are connected in parallel across a...Ch. 2 - Prob. 2.29PCh. 2 - Figure 2.26 shows three loads connected in...Ch. 2 - Consider two interconnected voltage sources...Ch. 2 - Prob. 2.35PCh. 2 - Prob. 2.36PCh. 2 - Prob. 2.37PCh. 2 - Prob. 2.38PCh. 2 - Prob. 2.39PCh. 2 - A balanced three-phase 240-V source supplies a...Ch. 2 - Prob. 2.41PCh. 2 - A balanced -connected impedance load with (12+j9)...Ch. 2 - A three-phase line, which has an impedance of...Ch. 2 - Two balanced three-phase loads that are connected...Ch. 2 - Two balanced Y-connected loads, one drawing 10 kW...Ch. 2 - Three identical impedances Z=3030 are connected in...Ch. 2 - Two three-phase generators supply a three-phase...Ch. 2 - Prob. 2.48PCh. 2 - Figure 2.33 gives the general -Y transformation....Ch. 2 - Consider the balanced three-phase system shown in...Ch. 2 - A three-phase line with an impedance of...Ch. 2 - A balanced three-phase load is connected to a...Ch. 2 - What is a microgrid?Ch. 2 - What are the benefits of microgrids?Ch. 2 - Prob. CCSQCh. 2 - Prob. DCSQ
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- 1. How do you measure three phase line currents by using two current transformers? Draw the connection scheme.arrow_forwardThree zones of a single-phase circuit are identified in the figure with a generator voltage specification of 240 V. The zones are connected by the transformers T1 and T2, whose ratings are shown below.Using base values of 30 kVA and 240 volts in zone 1, draw the pu circuit and determine the pu impedance and pu source voltage. Then calculate the load current in pu and in amperes.*Round the final answer to four decimal places, polar form, and label it with the correct units.arrow_forwardThe p.u. impedance value of an alternator corresponding to base values of 13.2 kV and 30 MVA is 0.2 p.u. Then the p.u. impedance value of an alternator for the new base values of 13.8 kV and 50 MVA is......arrow_forward
- Two 7970-V:230-V single-phase transformers with impedance with respect to their secondaries of 1.5 + j3 and 2 + j4.5 ohms are connected in parallel to a 7900-V source. Their secondaries are supplying a common load of 30 + j40 ohms. A. What is the magnitude of the voltage across the load in volts? (2 decimal places) B. What is the magnitude of the total current supplied by the 7900-V source in amperes? (3 decimal places) C. What is the efficiency of the parallel transformers combined in percent? ( 1 decimal place)arrow_forwardIn the system shown in Figure 1, the transformers are connected star-star with both star points grounded and the generator is connected in star with its star points grounded. The per unit impedances of each element on a 40 MVA base are given in Table 1 and the voltage levels are given in Table 2. Z [p.u.] 0 2 tööt Generator 0.01 +j0.08 p.u. L Figure 1: A section of the distribution system Transformer T1 Line V BASE [KV] 0.04 + j 0.03 + j 0.15000000000000002 0.06000000000000000 Generator Table 1: Sequence impedances (p.u. on 40 MVA base) 3 T2 181. Line 3 10 Table 2: Voltage bases (kV) Load 1 Transformer T2 Load Current A load current of 11.316 kA is flowing with a lagging power factor of 90 %. Convert this to a current vector in per-unit. IL = 0.04 + j 0.06000000000000000arrow_forwardConsider the three single-phase two-winding transformers shown in Figure 3.37. The high-voltage windings are connected in Y. (a) For the low-voltage side, connect the windings in , place the polarity marks, and label the terminals a, b, and c in accordance with the American standard. (b) Relabel the terminals a, b, and c such that VAN is 90 out of phase with Va for positive sequence.arrow_forward
- Consider a single-phase electric system shown in Figure 3.33. Transformers are rated as follows: XY15MVA,13.8/138kV, leakage reactance 10 YZ15MVA,138/69kV, leakage reactance 8 With the base in circuit Y chosen as 15MVA,138kV determine the per-unit impedance of the 500 resistive load in circuit Z, referred to circuits Z, Y, and X. Neglecting magnetizing currents, transformer resistances, and line impedances, draw the impedance diagram in per unit.arrow_forwardIn developing per-unit equivalent circuits for three-phase transformers. under balanced three-phase operation. (i) A common Sbase is selected for both the H and X terminals. (ii) The ratio of the voltage bases Vbase/VbaseX is selected to be equal to the ratio of the rated line-to-line voltages VratedHLL/VratedXLL. (a) Only one of the above is true. (b) Neither is true. (C) Both statements are true.arrow_forwardThree single-phase two-winding transformers, each rated 3kVA,220/110volts,60Hz, with a 0.10 per-unit leakage reactance, are connected as a three-phase extended autotransformer bank, as shown in Figure 3.36(c). The low-voltage winding has a 110 volt rating. (a) Draw the positive-sequence phasor diagram and show that the high-voltage winding has a 479.5 volt rating. (b) A three-phase load connected to the low-voltage terminals absorbs 6 kW at 110 volts and at 0.8 power factor lagging. Draw the per-unit impedance diagram and calculate the voltage and current at the high-voltage terminals. Assume positive-sequence operation.arrow_forward
- Determine the positive- and negative-sequence phase shifts for the three- phase transformers shown in Figure 3.36.arrow_forwarde = 0 Q1: What does happen if we change two currents? a. Q2: What does happen if we have a three-phase four poles machine? Q3: What does happen if we have a two-phase two poles machine? e = 0 Q4: What does happen if we apply a capacitance in phase b and then use same voltage for both phase. Dr. Ali Ki. pw --arrow_forwardIn a Three-phase alternator, a given field current produces an armature current of 250 A on short-circuit and a generated e.m.f. of 1500 V on open-circuit. Calculate the terminal p.d. when a load of 250 A at 6.6 kV and 0.8 p.f. lagging is switched off. Calculate also the regulation of the alternator at the given load. Subject: Electrical engineeringarrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Power System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning