One particular zone served by a multizone air handler has a design cooling load of 1750 Btu/hr (0.5 kW with a SHF of 0.8. The coil has air entering at 84 F (29 C) db and 70 F (21 C) wb with air leaving at 50 F (10 C) db and 90% relative humidity (RH). Zone conditions are 75 F (24 C) db and 50% RH. (a) What amount of air must be supplied to the space? (b) At what condition is the air supplied to the space? (c) How much air flows over the coil and how much air bypasses the coil for this one zone? Assume sea-level pressure.
Want to see the full answer?
Check out a sample textbook solutionChapter 3 Solutions
Heating Ventilating and Air Conditioning: Analysis and Design
Additional Engineering Textbook Solutions
Automotive Technology: Principles, Diagnosis, And Service (6th Edition) (halderman Automotive Series)
Fundamentals Of Thermodynamics
Statics and Mechanics of Materials (5th Edition)
INTERNATIONAL EDITION---Engineering Mechanics: Statics, 14th edition (SI unit)
Fundamentals of Heat and Mass Transfer
Thinking Like an Engineer: An Active Learning Approach (4th Edition)
- Gaisano Mall uses an atmospheric cooling tower to provide cooling for the jacket water of a four-stroke 309 KW diesel generator. The cooling tower efficiency is 53% at a temperature of approach of 11 deg. C. if ambient air has a relative humidity of 60% and dry bulb temperature of 31 deg. C, determine the cooling water supplied to the diesel engine in liters/hour.arrow_forwardAir enters a coil in the air-handling unit (AHU) at dry-bulb temperature (Id) of 40 oC, and wet- bulb temperature (Tw) of 26 oC. The air leaves the coil at dry-bulb temperature (Td) of 12 oC, and relative humidity of 80%. This process is: Note: You need to use the psychrometric chart. O Cooling and humidification, and the air looses 50 kJ/kg of energy. O Heating and humidification and the air gains 110 kl/kg of energy. O Evaporative cooling and the air neither looses nor gains energy. O Cooling and dehumidification and the air looses 50 kl/kg of energy.arrow_forwardAn air-conditioning system to be installed in a factory with sensible and latent cooling loads of 175 KW and 65 KW, respectively. Assume that the relative humidity of supply air is 90%. The inside state is at 21 °C DB and 70% RH. What is the approximate required dry-bulb temperature in °C of the supply state of air? Select one: O a. 17 b. 16 O c. 18 O d. 14.5 Oe. 14 Larrow_forward
- Q.2 An evaporative cooler is used to cool a space which has a sensible heat load of 15 kW and a latent heat load of 4.8 kW. The dry air mass flow rate of the supply air is 1.4 kg/s. The air leaves the cooler with a db-temperature of 18°C and a relative humidity of 100%. The outdoor air db-temperature is 35°C. The pressure is constant at 101.3 kPa. Determine (1) the db-temperature and relative humidity of the (ii) the outdoor relative humidity, and (iii) the mass flow rate of water. space,arrow_forwardUsing a psychometric diagram, describe the heating and humidification process from the following data. Initially the air was at dry bulb temperature (DBT) 35 ° C and RH 35%. air preheated to DBT 85 ° C. The heated air is then flowed through a humidifier to increase the RH to 25%. for this process, count, a. change in absolute humidity of air from initial to final conditions = ..... (kg water / kg air) b. change in air enthalpy from initial to final conditions = ..... (kj / kg air)arrow_forwardาา 3.15.) In air conditioning unit, 71,000 cfm at 80'F dry bulb 60% th and standard atmospheric pressure, enter the unit. The air leaves the wait at 57°F dry bulb and 90% relative humidity. Calculate the following a.) Cooling capacity of the air conditioning unit, in Btu/h 6.) rate of water removal from the unit. (.) sensible heat load on the conditioner, in Btu/h di) latent heat load on the conditioning in Blu/h e.) The dew point of the air leaving the conditioner.arrow_forward
- Air conditioning systemarrow_forwardA space to be conditioned has a sensible heat load of 80 kw and a latent heat load of 20 kw and is to be maintained at 20°C and 50% relative humidity. Outside air is at 35°C and 60% RH. The conditioned air will enter the space at 15°C. If 40% of the supply air is fresh and the rest is recirculated, the refrigeration capacity of the system is nearest to what value? 430 kw 455 kw 428 kw Ⓒ333 kwarrow_forwardWhat happens when relative humidity (RH) = 100%? a)if the air is continued to be cooled, at what temperature will the saturation point be reached? b)What happens if the air is continued to be cooled below the DBT you just found? (psychrometric chart image)arrow_forward
- Pick the right combination of True Statements. 1. As the by-pass factor (BPF) of the cooling coil increases, temperature difference between air at the outlet of the coil and coil ADP decreases. 2. As the by-pass factor (BPF) of the cooling coil increases, temperature difference between air at the outlet of the coil and coil ADP increases. 3. During cooling and humidification process, the enthalpy of air may increase, decrease or remain constant depending upon the temperature of the wet surface. 4. During sensible cooling of air, dry bulb temperature decreases but wet bulb temperature remains constant 5. The sensible heat factor for a sensible heating process is 1.0arrow_forwardThe design condition for a space is 77oF db and 50% relative humidity with 55oF db supply air at 90% relative humidity. A 50-ton, constant-volume space air- conditioning system uses face and bypass and water temperature control. Outdoor air is supplied at 95oF db, 60% relative humidity with a ratio of 1 lbm to 5 lbm re-circulated air. A part-load condition exists where the total space load is decreased by 50% and the SHF is increased to 90%. The outdoor air condition changes to 85oF db and 70% relative humidity. Assume sea-level conditions. a) At full – load conditions:a. Show all the processes on a psychrometric chart.b. Determine the temperature must the air be supplied to the space at fullload conditions.c. Determine the apparatus dew point temperature at full load conditions. b)At part – load conditions:a. Show all the processes on a psychrometric chart.b. Determine the temperature must the air be supplied to the space at partload conditions.c. Determine the apparatus dew point…arrow_forwardThe following data were obtained from space cooling load survey of an Air-Conditioning (AC) system of a Conference Hall: Sensible Heat Load Latent heat Load 10.5 tons 2.0 tons Design inside condition is set at 22 C dry bulb temperature and 60 percent relative humidity. Cold air is supplied to the Hall at 14 °C. The AC system is designed with mass ratio of 4:1 total supplied cooled air to required minimum outdoor ventilation air. Outdoor air is 30 °C dry bulb and 70 % relative humidity. Determine: a) Recommend an AC system suitable to the set-up above. b) What is the air-cooling apparatus SHF? c) What is the probable Apparatus Dewpoint (ADP)? d) What is the probable cooling coil Bypass Factor (BPF) of the cooling apparatus? e) Fan capacity needed that supplies air to the hall in liters/hour f) Refrigeration capacity of the Air-Cooling Apparatus in tonsarrow_forward
- Elements Of ElectromagneticsMechanical EngineeringISBN:9780190698614Author:Sadiku, Matthew N. O.Publisher:Oxford University PressMechanics of Materials (10th Edition)Mechanical EngineeringISBN:9780134319650Author:Russell C. HibbelerPublisher:PEARSONThermodynamics: An Engineering ApproachMechanical EngineeringISBN:9781259822674Author:Yunus A. Cengel Dr., Michael A. BolesPublisher:McGraw-Hill Education
- Control Systems EngineeringMechanical EngineeringISBN:9781118170519Author:Norman S. NisePublisher:WILEYMechanics of Materials (MindTap Course List)Mechanical EngineeringISBN:9781337093347Author:Barry J. Goodno, James M. GerePublisher:Cengage LearningEngineering Mechanics: StaticsMechanical EngineeringISBN:9781118807330Author:James L. Meriam, L. G. Kraige, J. N. BoltonPublisher:WILEY