A research building requires 100 percent outdoor ventilation air 24 hours a day. This causes a high latent cooling load relative to the sensible load. The peak cooling load is 100,000 Btu/hr (29.3 kW) with a SHF of 0.5. A coil configuration available has an apparatus dew point temperature of 45 F (7 C) and can cool outdoor air from 85 F (29 C) db, 70 F (21 C) wb, to 51 F (11 C) wb. The space is to be maintained at 73 F (24 C) db and 50% relative humidity (RH). Assume constant air flow and standard sea-level pressure. (a) Layout processes on Chart ia for a system to accommodate the given requirements. (b) That quantity of air must be supplied to handle the peak load? (c) Determine other unknown quantities such as coil load, reheat, etc.
Want to see the full answer?
Check out a sample textbook solutionChapter 3 Solutions
Heating Ventilating and Air Conditioning: Analysis and Design
Additional Engineering Textbook Solutions
Engineering Mechanics: Statics
Thinking Like an Engineer: An Active Learning Approach (4th Edition)
Introduction to Heat Transfer
Fundamentals of Heat and Mass Transfer
Thinking Like an Engineer: An Active Learning Approach (3rd Edition)
Automotive Technology: Principles, Diagnosis, And Service (6th Edition) (halderman Automotive Series)
- A- Specify is the following conditions are comfort or not: 1- DBT 22 C° and WBT = 16 Cº 2- DBT=24 C° and RH= 80 % B- Compare between the following: 1- Cooling load and the heat gain. 2- Overall heat transfer coefficient and convection heat transfer coefficient.arrow_forwardHow to solve theoretical efficiency of the cooling tower regarding air and water entering the system? Please provide examples. Subject : Heat transferarrow_forwardThe following data refer to summer air conditioning of a building: Outside design conditions 43 °C DBT, 27 °C WBT Inside design condition 25 °C DBT, 50% RH Room sensible heat gain 84000 kJ/h Room latent heat gain 21000 kJ/h BPF of cooling coil 0.2 The return air from the room is mixed with the outside air before entry to cooling coil in the ratio of 4:1 by mass. Determine: (a) Apparatus dew point of the cooling coil (b) Entry and exit conditions of air for cooling coil (c) Fresh air mass flow rate and (d) Refrigeration load on the cooling coil.arrow_forward
- A meeting hall is maintained at 25°C, 18Cwb. The space has a cooling load of 40 kw of which 32 kw is sensible cooling load. The temperature of the supply air to the space must not be lower than 18°C. Determine A. Sensible heat ratio B. Amount of air supply to the space (kg/s) C. Conditions of supply air D. Capacity of supply fan (CFM)arrow_forwardA laboratory space to be maintained at 24oC DB and 50% RH experiences a sensible-cooling load of 42 kW and a latent load of 18 kW. Because the latent load is heavy, the air-conditioning system is equipped for reheating the air leaving the cooling coil. The cooling coil has been selected to provide outlet air at 9 oC and 95% RH. What is (a) the air rate and (b) the temperature of supply air? Air pressure is 101.325 kPaarrow_forwardb.) A variable-air-volume cooling system delivers air to a controlled space maintained at 24 C db and 17 C wb. Under design conditions, the total cooling load is 60 kW with a sensible heat factor of 0.60, and the supply air temperature is 16 C db. At minimum load, about 7.5 kW with SHF of 0.80, the air quantity may be reduced no more than 75% by volume of the full load design value. Determine the supply air conditions for minimum load (state dry bulb temperature and wet bulb temperature, both in degree C).arrow_forward
- 3. For an air-conditioning system, the outdoor .. and indoor design dry bulb temperatures are 45°C and 25°C respectively. The space to be air-conditioned is 20m x 30m-x 5 m and infiltration is estimated to be one air are 1.2 (kg of dry air)/m³ and 1.02 kJ/(kg of dry air) °C, then the sensible heat load due to infiltration is, nearlyarrow_forwardI need to solve question 1arrow_forwardA summer air-conditioning shown below is required to maintain a certain room at specified conditions. The layout of the system is indicated on the next page and the specifications are listed below.System specifications:Required room temperature: 23⁰C, 50% Relative humidityAtmospheric pressure: 101 kPaOutside air conditions: 30⁰C, 80% Relative humidity Sensible heat gain: 5 kWLatent heat gain: 4 kWTemperature rise across fan: 1.5⁰CTemperature of air leaving cooler: 12⁰CTemperature of air entering room: 18⁰CApparatus dew point of cooler: 7⁰Carrow_forward
- Question 4 A VRF cooling unit, having a cooling capacity of 25 kW, have the following COPS: COP100% = 369, COP75% = 5.72, COP50% = 6.65, COP25% = 8.16. Assume that the cooling unit has 13 hours of usage daily, having standby power of 200 W and energy tariffs of 41 cents per kWh. Using NEA's recommended AEC estimation, determine the annual energy cost up to 2 decimal points. Do not include "S" in your answer. Selected Answer: O 5,643.75 Correct Answer 5,584.12 0.01%arrow_forwardRefrigerationarrow_forwardThe mass flow rate of the refrigerant in a Single Stage Vapor Compression (SSVC) refrigeration system is 0.015 kg/s and the evaporating and condensing temperatures shall be -20°C and 50°C, respectively. Determine the cooling capacity in tons.arrow_forward
- Refrigeration and Air Conditioning Technology (Mi...Mechanical EngineeringISBN:9781305578296Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill JohnsonPublisher:Cengage LearningPrinciples of Heat Transfer (Activate Learning wi...Mechanical EngineeringISBN:9781305387102Author:Kreith, Frank; Manglik, Raj M.Publisher:Cengage Learning