Heating Ventilating and Air Conditioning: Analysis and Design
Heating Ventilating and Air Conditioning: Analysis and Design
6th Edition
ISBN: 9780471470151
Author: Faye C. McQuiston, Jeffrey D. Spitler, Jerald D. Parker
Publisher: Wiley, John & Sons, Incorporated
bartleby

Videos

Textbook Question
Book Icon
Chapter 3, Problem 3.15P

Air enters a cooling coil at the rate of 5000 cfm (2.4 m3/s) at 80 F (27 C) db, 68 F (20 C) wb and sea-level pressure. The air leaves the coil at 55 F (13 C) db, 54 F (12 C) wb. (a) Determine the SHF and the apparatus dew point. (b) Compute the total and sensible heat transfer rates from the air.

Blurred answer
Students have asked these similar questions
0.2 A condenser condenses 2700kg steam per hour while air leaks into It at 2.2kg/hr. The condensate and air suction spout temperatures are 32.9°C. The barometer and vacuum gauge readings are 765mmHg and 690mmHg respectively. The condenser uses 125.55M9 of cooling water per hour to condense steam with a dryness fraction of 0.86 and the air pump has a volumetric efficiency of 82.5%. Take R = 0.287kJ/kgK for air and calculate: %3D 6.2.1 the temperature rise of the cooling water (10.85°C); 6.2.2 the air pump capacity in m2/min (0.78m3³/min).
Moist air enters an air-conditioning system as shown in the figure below at T1 = 28°C, 01 = 80% and a volumetric flow rate of (AV)1 = 0.47 m3/s. At the exit of the dehumidifying section, the air is saturated, @, = 100%, and the condensate leaves this section at the same temperature as the moist air. At the exit of the heating section the moist air is at T3 = 24°C, 03 = 50%. The system operates at steady state, the pressure is 1 bar at all locations, and kinetic and potential energy effects are negligible. Dehumidifying Section Heating Section 2 = 100% T3 = 24°C Ø3 = 50% T1= 28°C $1. (AV)ı Initial dew point- O = 100% Condensate - saturated at T2 T2 T3 ww
1. A variable-air-volume cooling system delivers air to a controlled space maintained at 24 C db and 17 C wb. Under design conditions, the total cooling load is 60 kW with a sensible heat factor of 0.60, and the supply air temperature is 16 C db. At minimum load, about 7.5 kW with SHF of 0.80, the air quantity may be reduced no more than 75% by volume of the full load design value. Calculate the minimum volume of air to be supplied to the space at minimum load, cu.m/min.

Chapter 3 Solutions

Heating Ventilating and Air Conditioning: Analysis and Design

Ch. 3 - The environmental conditions in a room are to be...Ch. 3 - Air enters a cooling coil at the rate of 5000 cfm...Ch. 3 - Air flowing in a duct has dry and wet bulb...Ch. 3 - Air is humidified with the dry bulb temperature...Ch. 3 - Air at 38 C db and 20 C wb is humidified...Ch. 3 - Two thousand cfm (1.0 m3/s) of air at an initial...Ch. 3 - Air at 40 F (5 C) db and 35 F (2 C) wb is mixed...Ch. 3 - Rework Problem 3-25, using Chart 1a, with the...Ch. 3 - The design cooling load for a zone in a building...Ch. 3 - Assume that the air in Problem 3-22 is supplied to...Ch. 3 - The sensible heat loss from a space is 500,000...Ch. 3 - Air enters a refrigeration coil at 90 Fdb and 75...Ch. 3 - A building has a total heating load of 200,000...Ch. 3 - Reconsider Problem 3-36 for an elevation of 5000...Ch. 3 - The system of Problem 3-34 has a supply air fan...Ch. 3 - An evaporative cooling system is to be used to...Ch. 3 - A cooling system is being designed for use at high...Ch. 3 - Consider a space heating system designed as shown...Ch. 3 - A variable-air-volume VAV cooling system is a type...Ch. 3 - Rework Problem 3-43 for an elevation of 5000 feet...Ch. 3 - The design condition for a space is 77 F (25 C) db...Ch. 3 - Rework Problem 3-45 for an elevation of 5000 feet...Ch. 3 - It is necessary to cool and dehumidify air from 80...Ch. 3 - Conditions in one zone of a dual-duct conditioning...Ch. 3 - Rework Problem 3-48 for an elevation of 5000 ft...Ch. 3 - A water coil in Problem 3-48 cools return air to...Ch. 3 - A multizone air handler provides air to several...Ch. 3 - Under normal operating conditions a zone has a...Ch. 3 - An interior zone of a large building is designed...Ch. 3 - Outdoor air is mixed with room return air to...Ch. 3 - Consider an enclosed swimming pool. The pool area...Ch. 3 - One particular zone served by a multizone air...Ch. 3 - A research building requires 100 percent outdoor...Ch. 3 - A space requires cooling in the amount of 120,000...
Knowledge Booster
Background pattern image
Mechanical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Elements Of Electromagnetics
Mechanical Engineering
ISBN:9780190698614
Author:Sadiku, Matthew N. O.
Publisher:Oxford University Press
Text book image
Mechanics of Materials (10th Edition)
Mechanical Engineering
ISBN:9780134319650
Author:Russell C. Hibbeler
Publisher:PEARSON
Text book image
Thermodynamics: An Engineering Approach
Mechanical Engineering
ISBN:9781259822674
Author:Yunus A. Cengel Dr., Michael A. Boles
Publisher:McGraw-Hill Education
Text book image
Control Systems Engineering
Mechanical Engineering
ISBN:9781118170519
Author:Norman S. Nise
Publisher:WILEY
Text book image
Mechanics of Materials (MindTap Course List)
Mechanical Engineering
ISBN:9781337093347
Author:Barry J. Goodno, James M. Gere
Publisher:Cengage Learning
Text book image
Engineering Mechanics: Statics
Mechanical Engineering
ISBN:9781118807330
Author:James L. Meriam, L. G. Kraige, J. N. Bolton
Publisher:WILEY
The Refrigeration Cycle Explained - The Four Major Components; Author: HVAC Know It All;https://www.youtube.com/watch?v=zfciSvOZDUY;License: Standard YouTube License, CC-BY