Under normal operating conditions a zone has a total cooling load of 120,000 Btu/hr (35 kW) with a SHF of 0.8. The space is to be maintained at 74 F (23 C) db and 50% relative humidity (RH). However, there are periods when the latent load is high and the SHF is estimated to be as low as 0.6. Assume that air enters the cooling coil at 8 F (29 C) db and 71 F (22 C) wb and the coil apparatus dew point is 48 F (9 C). (a) Devise a system and the associated psychrometric processes to cover the necessary range of operation. b) Define the various air states and show the processes on Chart ia. (c) Compute air-flow rate, coil load, minimum zone load, and any reheat that may be required. Assume constant air flow and standard sea-level pressure.
Want to see the full answer?
Check out a sample textbook solutionChapter 3 Solutions
Heating Ventilating and Air Conditioning: Analysis and Design
Additional Engineering Textbook Solutions
Engineering Mechanics: Dynamics (14th Edition)
DeGarmo's Materials and Processes in Manufacturing
Engineering Mechanics: Statics & Dynamics (14th Edition)
Automotive Technology: Principles, Diagnosis, And Service (6th Edition) (halderman Automotive Series)
Introduction To Finite Element Analysis And Design
Engineering Mechanics: Statics
- A space is to be maintained at 75 F db and 40% relative humidity. The total heat gain to the space is 62,000 Btu/hr with a SHF of 0.8. The outdoor air requirement is 500 cfm. The outdoor air has a temperature of 90 F and 50% relative humidity. Assume that the supply air has a temperature of 50 F db. Determine the following: a. Quantity of supplied air b. Capacity of the cooling coil c. Rate of moisture removal from the dehumidification elementarrow_forwardP=19 Moist air goes into air-conditioning unit at a degree-30 C and 70% relative humidity, and it is cooled to 20-degree C and 20% relative humidity at a constant pressure of 1.01325 bar. The mass flow rate of dry air is mda=63 kg/s The unit applies refrigerant R-134a as the cooling fluid that enters inside the tubes of the cooling coil at 3.6 bar with a quality of 0.2 and leaves as a saturated vapor at the same pressure of 3.6 bar. Use the psychometric chart to determine: a) Mass flow rate of condensed water in kg/s b) The heat transfer rate from the air to the cooling coil in kW (Use the psychometric chart) c) The mass flow rate of R-134a that is needed in kg/sarrow_forwardThermo Fluid help needed air conditionerarrow_forward
- ASHRAE standard 62.2 states that the minimum acceptable rate of airflow into and out of a room is 15cfm (cubic feet per minute). If air is supplied at 68°F with a relative humidity of 45%, how many gallons of water (minimum) must be added to a portable room humidifier before you go to sleep if you would like to maintain the room at 65% humidity for 7 hours?arrow_forwardPick the right combination of True Statements. 1. As the by-pass factor (BPF) of the cooling coil increases, temperature difference between air at the outlet of the coil and coil ADP decreases. 2. As the by-pass factor (BPF) of the cooling coil increases, temperature difference between air at the outlet of the coil and coil ADP increases. 3. During cooling and humidification process, the enthalpy of air may increase, decrease or remain constant depending upon the temperature of the wet surface. 4. During sensible cooling of air, dry bulb temperature decreases but wet bulb temperature remains constant 5. The sensible heat factor for a sensible heating process is 1.0arrow_forwardUsing a psychrometric diagram, describe the heating and humidification process from the following data. Initially the air was at a dry bulb temperature (DBT) of 40 ° C and RH60%. The air is heated to DBT 90 ° C. The heated air is then flowed through a humidifier to increase the RH to 25%. For this process, calculate, a. Change in absolute humidity of air from initial to final conditions = kg water / kg air). b. The change in air enthalpy from initial to final conditions. = (kj / kg air)arrow_forward
- For summer air conditioner application of a room; The sensible heat gain of the room is 13kW, the latent heat gain is 3kW, and the design conditions are determined as 21°C relative humidity 55%. Outdoor air conditions are at 42 °C 35% relative humidity, and the relative humidity of the air passing through the cooling coil at the exit from the coil will be 95%. Since the amount of air blown into the environment is 5000m^3/h, the return air is 700 m^3/h: a- Show the event in the psychometric diagram according to the data of the air conditioning application. b-Find the dry bulb temperature of the air at the outlet of the cooling coil. c-Calculate the amount of air that is bypassed and not by-passed from the coil B Mahalarrow_forwardI need the answer as soon as possiblearrow_forwardIn an air sample with a dry-bulb temperature of 28°C and a wet-bulb temperature of 22°C what is the (relative humidity)?arrow_forward
- Is it possible that during sensible heating process the condition of air reaches a relative humidity of 0% ?arrow_forwardwhat is the relationship and formula of relative humidity and temperature?arrow_forwardUsing a psychometric diagram, describe the heating and humidification process from the following data. Initially the air was at dry bulb temperature (DBT) 35 ° C and RH 35%. air preheated to DBT 85 ° C. The heated air is then flowed through a humidifier to increase the RH to 25%. for this process, count, a. change in absolute humidity of air from initial to final conditions = ..... (kg water / kg air) b. change in air enthalpy from initial to final conditions = ..... (kj / kg air)arrow_forward
- Elements Of ElectromagneticsMechanical EngineeringISBN:9780190698614Author:Sadiku, Matthew N. O.Publisher:Oxford University PressMechanics of Materials (10th Edition)Mechanical EngineeringISBN:9780134319650Author:Russell C. HibbelerPublisher:PEARSONThermodynamics: An Engineering ApproachMechanical EngineeringISBN:9781259822674Author:Yunus A. Cengel Dr., Michael A. BolesPublisher:McGraw-Hill Education
- Control Systems EngineeringMechanical EngineeringISBN:9781118170519Author:Norman S. NisePublisher:WILEYMechanics of Materials (MindTap Course List)Mechanical EngineeringISBN:9781337093347Author:Barry J. Goodno, James M. GerePublisher:Cengage LearningEngineering Mechanics: StaticsMechanical EngineeringISBN:9781118807330Author:James L. Meriam, L. G. Kraige, J. N. BoltonPublisher:WILEY