Heating Ventilating and Air Conditioning: Analysis and Design
Heating Ventilating and Air Conditioning: Analysis and Design
6th Edition
ISBN: 9780471470151
Author: Faye C. McQuiston, Jeffrey D. Spitler, Jerald D. Parker
Publisher: Wiley, John & Sons, Incorporated
bartleby

Videos

Textbook Question
Book Icon
Chapter 3, Problem 3.38P

The system of Problem 3-34 has a supply air fan located just downstream of the cooling coil. The total power input to the fan is 4.0 hp. It is also estimated that heat gain to the supply duct system is 1000 Btu/hr. Rework Problem 3-34 using Chart la, taking the fan and duct heat gain into account. Make a sketch of the processes.

Blurred answer
Students have asked these similar questions
16-4 A refrigerant 22 system has a capacity of 180 kW at an evaporating temperature of -30°°C when the condensing pressure is 1500 kPa. (a) Compute the power requirement for a system with a single compressor. (b)Compute the total power required by the two compressors in the system shown in Fig. 16-17 where there is no intercooling but there is flash-gas removal at600 kPa. Ans. 60.7 kW Condenser 1500 kPa 5 600 kPa 3 Flash-gas compressor Evaporator 180 kW -30°C Figure 16-17 Flash-gas removal system in Prob. 16-4. 2 Evaporator compressor
* It required to design a ducting system to condition the building shown in figure (1). The uantity of outdoor is (20%) of supply air. Using information in table, find 1- The sensible and latent load for cooling coil. 2- The quantity and condition of supply air to each place. 3- By using equal pressure drop method, design the rectangular ducting system with maximum height side (600mm). 4- Illustrate the all process on psychometric chart. Outdoor 45 °C db & 30% RH Out let type Celling conditioning indoor conditioning 24 °C db & 50% RH diffuser Number of diffuser 2 for each place 15 kpa 10 kpa 15 kpa By pass factor Apparatus dew point 9°C Ap losses diffuser Ap losses filter Ap losses coil 0.15 R/w 1.5 бm бm бm Room (1) Room (2) RSH=6KW Room (3) 4m RSH=8KW RSH=8KW RLH=2KW RLH=1KW RLH=2KW 2m AHU Mechanical Room (4) RSH=20KW 4m Room RLH=3KW 4m 14m
6. A Thomas meter is located in an air duct of 2 sq ft cross-sectional area. The air weighs 0.083 lb per cu ft, and its specific heat is 0.24. Assume a controlled temperature differential of 5° and heater potential of 110 volts. Plot the velocity as abscissa and amperage as ordinate for veloc- ity 0 to 300 ft per min. Assume constant amperage of 3, and plot tem- perature difference against velocity. Discuss the curves from the stand- point of accuracy of the system. J: よ itet legeted oulindriool oir tube

Chapter 3 Solutions

Heating Ventilating and Air Conditioning: Analysis and Design

Ch. 3 - The environmental conditions in a room are to be...Ch. 3 - Air enters a cooling coil at the rate of 5000 cfm...Ch. 3 - Air flowing in a duct has dry and wet bulb...Ch. 3 - Air is humidified with the dry bulb temperature...Ch. 3 - Air at 38 C db and 20 C wb is humidified...Ch. 3 - Two thousand cfm (1.0 m3/s) of air at an initial...Ch. 3 - Air at 40 F (5 C) db and 35 F (2 C) wb is mixed...Ch. 3 - Rework Problem 3-25, using Chart 1a, with the...Ch. 3 - The design cooling load for a zone in a building...Ch. 3 - Assume that the air in Problem 3-22 is supplied to...Ch. 3 - The sensible heat loss from a space is 500,000...Ch. 3 - Air enters a refrigeration coil at 90 Fdb and 75...Ch. 3 - A building has a total heating load of 200,000...Ch. 3 - Reconsider Problem 3-36 for an elevation of 5000...Ch. 3 - The system of Problem 3-34 has a supply air fan...Ch. 3 - An evaporative cooling system is to be used to...Ch. 3 - A cooling system is being designed for use at high...Ch. 3 - Consider a space heating system designed as shown...Ch. 3 - A variable-air-volume VAV cooling system is a type...Ch. 3 - Rework Problem 3-43 for an elevation of 5000 feet...Ch. 3 - The design condition for a space is 77 F (25 C) db...Ch. 3 - Rework Problem 3-45 for an elevation of 5000 feet...Ch. 3 - It is necessary to cool and dehumidify air from 80...Ch. 3 - Conditions in one zone of a dual-duct conditioning...Ch. 3 - Rework Problem 3-48 for an elevation of 5000 ft...Ch. 3 - A water coil in Problem 3-48 cools return air to...Ch. 3 - A multizone air handler provides air to several...Ch. 3 - Under normal operating conditions a zone has a...Ch. 3 - An interior zone of a large building is designed...Ch. 3 - Outdoor air is mixed with room return air to...Ch. 3 - Consider an enclosed swimming pool. The pool area...Ch. 3 - One particular zone served by a multizone air...Ch. 3 - A research building requires 100 percent outdoor...Ch. 3 - A space requires cooling in the amount of 120,000...

Additional Engineering Textbook Solutions

Find more solutions based on key concepts
Knowledge Booster
Background pattern image
Mechanical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Refrigeration and Air Conditioning Technology (Mi...
Mechanical Engineering
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:Cengage Learning
Text book image
Principles of Heat Transfer (Activate Learning wi...
Mechanical Engineering
ISBN:9781305387102
Author:Kreith, Frank; Manglik, Raj M.
Publisher:Cengage Learning
The Refrigeration Cycle Explained - The Four Major Components; Author: HVAC Know It All;https://www.youtube.com/watch?v=zfciSvOZDUY;License: Standard YouTube License, CC-BY