Consider an enclosed swimming pool. The pool area has a sensible heat loss of 424,000 Btu/hr (124 kW) and a latent heat gain of 530,000 Btufhr (155 kW) on a design day when the outdoor air is at 35 F (2 C) and 20 percent relative humidity (RH). The space is to be maintained at 75 F (24 C) and 50 percent RH. Outdoor air is to be heated to 60 F (16 C), mixed with recirculated air from the conditioned space and the mixed air heated to supply conditions. (a) At what rate, in cfm, is the air supplied to the space if the supply air temperature is 95 F (35 C)? (b) At what rate, in cfm, is outdoor air and recirculated air flowing? (c) What is the heat transfer rate for the preheat process? (d) What is the heat transfer rate for the mixed air heating process?
Want to see the full answer?
Check out a sample textbook solutionChapter 3 Solutions
Heating Ventilating and Air Conditioning: Analysis and Design
Additional Engineering Textbook Solutions
Thinking Like an Engineer: An Active Learning Approach (3rd Edition)
Engineering Mechanics: Statics
Applied Fluid Mechanics (7th Edition)
Engineering Mechanics: Statics & Dynamics (14th Edition)
Introduction to Heat Transfer
- A summer air conditioning system (schematic shown below) consisting of a cooling coil and a reheat coil, supplies air to a space maintained at 26°C db-temperature and 19°C wb-temperature. The sensible and latent heat loads on the space are both 18 kW and 18 kW, respectively. The conditions of the air leaving the cooling coil are 10°C db-temperature and 90% relative humidity. The pressure is constant at 101.325 kPa. About 30% of the return air is replaced with outdoor air at 30°C db-temperature and 80% RH. Determine: The db-temperature of supply air in % The dry-air mass flow rate of supply air in kg/sarrow_forwardroom contains air at 30 degrees * C and a total pressure of 96.0 kPa with a relative humidity of 75 percen ermine (a) the partial pressure of dry air and (b) the specific humidity.arrow_forwardAn air conditioning system, shown schematically below, supplies air at the rate of 4 kg/s to a space maintained at a db-temperature of 27°C and relative humidity of 50%. The sensible and latent heat loads on the space are 46 kW and 20 kW respectively. Outdoor air at 35°C db-temperature and 24°C wb-temperature is introduced at the rate of 1.1 kg/s. The relative humidity of the air leaving the cooling coil is 90%. The pressure is constant at 101.3 kPa. Determine:the supply air temperature in °Cthe supply air relative humidity in %the mass flow rate of the air that bypasses the cooling coil in kg/sthe refrigeration capacity of the cooling coil in kWarrow_forward
- 2. An air-conditioning system is to take in outdoor air at 10 C and 30 percent relative humidity at a steady rate of 45 m3/min and to condition it to 25 C and 60 percent relative humidity. The outdoor air is first heated to 22 C in the heating section and then humidified by the injection of hot steam in the humidifying section. Assuming the entire process takes place at a pressure of 100 kPa, determine (a) the rate of heat supply in the heating section and (b) the mass flow rate of the steam required in the humidifying section. 22 C 25 C Heating Hum hiner 7,10°C. 7-25 C = 30%arrow_forwardThe temperature of the air in a dryer is maintained constant by the use of steam coils within the dryer. The product enters the dryer at the rate of one metric ton per hour. The initial moisture content is 3 kg moisture per kg of dry solid and will be dried to moisture content of 0.10 kg moisture per kg of dry solid. Air enters the dryer with a humidity ratio of 0.016 kg moisture per kg of dry air and leaves with a relative humidity of 100% while the temperature remains constant at 60°C. If the total pressure of the air is 101.325 kPaa, determine the vapor pressure at heater inlet in psia.arrow_forwardThe temperature of the air in a dryer is maintained constant by the use of steam coils within the dryer. The product enters the dryer at the rate of one metric ton per hour. The initial moisture content is 3 kg moisture per kg of dry solid and will be dried to moisture content of 0.10 kg moisture per kg of dry solid. Air enters the dryer with a humidity ratio of 0.016 kg moisture per kg of dry air and leaves with a relative humidity of 100% while the temperature remains constant at 60°C. If the total pressure of the air is 101.325 kPaa, determine the specific enthalpy at dryer outlet in kJ/kg.arrow_forward
- In an air-conditioning unit 3.5 m3/s of air at 32 C dry-bulb temperature, 50 percentrelative humidity, and standard atmospheric pressure enters the unit. The leavingcondition of the air is 18 C dry-bulb temperature and 90 percent relative humdity.Using properties from the psychrometric chart, (a) calculate the refrigeratingcapacity in kilowatts and (b) determine the rate of water removal from the airarrow_forwardFresh atmospheric air mixed with recycled air is heated to 349K and admitted to a drier at 101.3 KPa at a rate of 100 m3/min. The relative humidity of the air entering the drier is 7.5%. Atmospheric air is at 302K and has a relative humidity of 30%. The air leaves the drier at 306K and 90% relative humidity, a portion of which is recycled and the other portion discarded. The vapour pressures of water are 4KPa at 302K, 5KPa at 306K and 40KPa at 349K. Calculate the following:a) The ratio of wet recycle stream to wet fresh stream.b) The mass of dry air to be fed to the drier to remove one kilogram of water in the drier.c) The rate at which water is removed in kg/min.arrow_forwardThe dry bulb and wet bulb temperature of an enclosed room was 27 deg C and 23 deg C, respectively. Determine the following: Dew point temperature (in deg F) Enthalpy (BTU/lb) Specific volume (m^3/kg) Relative Humidity Humidity Ratio (lb air/ lb dg)arrow_forward
- An auditorium seating 1800 people in three consecutive sitting for 6 hours, is to be maintained at 25°C dry bulb and 20°C wet bulb temperatures with outdoor air at 35°C dry bulb and 60% relative humidity. Conditioned air enters the auditorium at 15°C. Ventilation requirement is 8 m³/hr per person. Solar and other heat loads amount to 108,000 KJ/hr. The sensible and latent heat loads from the occupants is 275 KJ/hr per person and 150 KJ/hr per person, respectively. The ventilation load is nearest to what value? 266.64 kw 29.63 kw 115 kw 44.12 kwarrow_forwardAt sea level conditions, 2000 cfm of outside air is entering a mixing box at 50°F drybulb and 42°F wet bulb and mixes with 9000 cfm of return air which is at 80°F drybulb and 70°F wet bulb. Determine the thermodynamic state of the mixed air andreport the following for the mixed air: 1)Dry bulb temperature,2) Wet bulb temperature,3) Dew point temperature,4) Relative humidity,5) Humidity ratio,6) Specific enthalpy,7) Specific volume,8) Density,9) Mass flow rate. Show the process on a psychrometric chart.arrow_forwardCan you make a schematic diagram for this problem? 600 lps of air at 30°C dry-bulb and 22°C wet-bulb temperatures is heated to a temperature of 45°C and enters the dryer. The air leaves the dryer adiabatically and its relative humidity is 70%. Determine: (a.) The water evaporated kg/hr; (b.) The volume air leaving the dryer in cu.m/min; and (c.) kJ requirement of the dryer per kg of water evaporated.arrow_forward
- Elements Of ElectromagneticsMechanical EngineeringISBN:9780190698614Author:Sadiku, Matthew N. O.Publisher:Oxford University PressMechanics of Materials (10th Edition)Mechanical EngineeringISBN:9780134319650Author:Russell C. HibbelerPublisher:PEARSONThermodynamics: An Engineering ApproachMechanical EngineeringISBN:9781259822674Author:Yunus A. Cengel Dr., Michael A. BolesPublisher:McGraw-Hill Education
- Control Systems EngineeringMechanical EngineeringISBN:9781118170519Author:Norman S. NisePublisher:WILEYMechanics of Materials (MindTap Course List)Mechanical EngineeringISBN:9781337093347Author:Barry J. Goodno, James M. GerePublisher:Cengage LearningEngineering Mechanics: StaticsMechanical EngineeringISBN:9781118807330Author:James L. Meriam, L. G. Kraige, J. N. BoltonPublisher:WILEY