A multizone air handler provides air to several zones. One interior zone contains computer equipment with only a sensible load. The coil in the unit cools air from 85 F (29 C) db and 70 F (21 C) wb to 53 F (12 C) db and 90% relative humidity (RH). (a) If the zone is to be maintained at 75 F (24 C) and 50% RH, what proportion of the supply air to the zone bypasses the coil? The amount of air supplied to the zone is 2,500 cfm (1.18 m3/s). (b) What is the cooling load for the zone? Assume standard sea-level pressure.
Want to see the full answer?
Check out a sample textbook solutionChapter 3 Solutions
Heating Ventilating and Air Conditioning: Analysis and Design
Additional Engineering Textbook Solutions
Thinking Like an Engineer: An Active Learning Approach (4th Edition)
Engineering Mechanics: Statics
Statics and Mechanics of Materials (5th Edition)
Introduction To Finite Element Analysis And Design
INTERNATIONAL EDITION---Engineering Mechanics: Statics, 14th edition (SI unit)
Introduction to Heat Transfer
- Give correct solution onlyarrow_forwardAn air-conditioning system to be installed in a factory with sensible and latent cooling loads of 175 KW and 65 KW, respectively. Assume that the relative humidity of supply air is 90%. The inside state is at 21 °C DB and 70% RH. What is the approximate required dry-bulb temperature in °C of the supply state of air? Select one: O a. 17 b. 16 O c. 18 O d. 14.5 Oe. 14 Larrow_forwardA summer air-conditioning shown below is required to maintain a certain room at specified conditions. The layout of the system is indicated on the next page and the specifications are listed below.System specifications:Required room temperature: 23⁰C, 50% Relative humidityAtmospheric pressure: 101 kPaOutside air conditions: 30⁰C, 80% Relative humidity Sensible heat gain: 5 kWLatent heat gain: 4 kWTemperature rise across fan: 1.5⁰CTemperature of air leaving cooler: 12⁰CTemperature of air entering room: 18⁰CApparatus dew point of cooler: 7⁰Carrow_forward
- please solve in 4o mins i will give you positive feedbackarrow_forwardOn a hot summer day, the temperature is 35 ° C, barometric pressure 103 kPa and relative humidity 90%. One The air conditioner draws the outside air and cools it to 20 ° C and raises the air to 12500 L / h. Calculate the condensation rate of the moisture (kg / h) and the flow rate of the air drawn from the outside.arrow_forwardneed help. air conditioningarrow_forward
- Pick the right combination of True Statements. 1. As the by-pass factor (BPF) of the cooling coil increases, temperature difference between air at the outlet of the coil and coil ADP decreases. 2. As the by-pass factor (BPF) of the cooling coil increases, temperature difference between air at the outlet of the coil and coil ADP increases. 3. During cooling and humidification process, the enthalpy of air may increase, decrease or remain constant depending upon the temperature of the wet surface. 4. During sensible cooling of air, dry bulb temperature decreases but wet bulb temperature remains constant 5. The sensible heat factor for a sensible heating process is 1.0arrow_forwardPls. Answer thank you!Atmospheric air from the inside of an automobile enters the evaporator section of the air conditioner at 1 atm, 27 C and 50 percent relative humidity. The air returns to the automobile at 10 C and 90 percent relative humidity. The passenger compartment has a volume of 2 m3 and 5 air changes per minute are required to maintain the inside of the automobile at the desired comfort level. Sketch the psychrometric diagram for the atmospheric air flowing through the air conditioning process. Determine the dew point and wet bulb temperatures at the inlet to the evaporator section, in 8 C. the required heat transfer rate from the atmospheric air to the evaporator fluid, in kW. the rate of condensation of water vapor in the evaporator section, in kg/min.arrow_forwardThe following data refer to summer air conditioning of a building: Outside design conditions 43 °C DBT, 27 °C WBT Inside design condition 25 °C DBT, 50% RH Room sensible heat gain 84000 kJ/h Room latent heat gain 21000 kJ/h BPF of cooling coil 0.2 The return air from the room is mixed with the outside air before entry to cooling coil in the ratio of 4:1 by mass. Determine: (a) Apparatus dew point of the cooling coil (b) Entry and exit conditions of air for cooling coil (c) Fresh air mass flow rate and (d) Refrigeration load on the cooling coil.arrow_forward
- ASHRAE standard 62.2 states that the minimum acceptable rate of airflow into and out of a room is 15cfm (cubic feet per minute). If air is supplied at 68°F with a relative humidity of 45%, how many gallons of water (minimum) must be added to a portable room humidifier before you go to sleep if you would like to maintain the room at 65% humidity for 7 hours?arrow_forwardNo card B a m OO ON 94)| 1:50 mlms.hu.edu.jo/mod/qu 3 A 476 m rigid tank contains saturated Refrigerant-134a mixture at 700 kPa with 27% quality. A valve at the bottom of the tank is now opened, and only liquid is withdrawn from the tank. Heat is transferred to the refrigerant such that the pressure inside the tank remains constant. The valve is closed when no liquid is left in the tank and vapor starts to come out. What is the amount of R-134a that exited from the tank "kg"? R-134a Sat. vapor P = 700 kPa Sat. Liquid Select one: A. 42.72 B. 49.05 C. 45.49 D. 35.99 E. 39.55arrow_forwardIn air-conditioning, how are two or more streams of air mixed? typwrittenarrow_forward
- Refrigeration and Air Conditioning Technology (Mi...Mechanical EngineeringISBN:9781305578296Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill JohnsonPublisher:Cengage Learning