Concept explainers
(a) Find both wattmeter readings in Fig. 12.39 if VA = 100∠0 ° V rms, VB = 50∠90° V rms, ZA = 10 − j10 Ω, ZB = 8 + j6 Ω, and ZC = 30 + j10 Ω. (b) Is the sum of these readings equal to the total power taken by the three loads? Verify your answer with an appropriate simulation.
■ FIGURE 12.39
a.
Find the wattmeter readings in the circuit of Figure 12.39.
Answer to Problem 39E
The reading of wattmeter
Explanation of Solution
Given data:
The load impedance are
Calculation:
The given figure with mesh currents is shown in Figure 1.
Apply Kirchhoff’s voltage law to the loop with current
Apply Kirchhoff’s voltage law to the loop with current
Apply Kirchhoff’s voltage law to the loop with current
Rearrange equation (1).
Substitute equation (4) in (3).
Simplify the equation as follows.
Substitute equation (5) in (4).
Substitute equation (6) in (2).
Simplify the equation as follows.
Substitute
Substitute
Calculate the power delivered by phase A as follows.
Calculate the power delivered by phase B as follows.
Conclusion:
Thus, the reading of wattmeter
b.
Verify that the sum of the wattmeter reading is equal to the total power taken by the three loads using LTspice.
Explanation of Solution
Formula used:
Write the expression for inductive reactance.
Here,
Write the expression for capacitive reactance.
Here,
Calculation:
Let us assume that the angular frequency
Substitute
Substitute
Substitute
LTspice Simulation:
Draw the given figure in LTspice as shown in Figure 2. V1 zero and V2 zero connected in the circuit to find the current flows through it.
Set the values of voltages VA by right clicking on the voltage component, select none in “Functions” and enter the Small signal AC analysis parameters: AC amplitude as 100 for V1 as shown in Figure 3 for VA.
Now save the circuit, and open the “Edit Simulation command” choose AC analysis and select the sweep type as Decade, Number of points per decade 1, Start frequency and Stop frequency as 0.159155 Hz.
Now, run the simulation for the designed circuit. The output for the AC analysis will displays as shown in Figure 5.
From above simulation results, the current flows through the load resistance are given below.
Calculate the power delivered to load
Calculate the power delivered to load
Calculate the power delivered to load
The total power delivered to the load is
The sum of the wattmeter reading is
Conclusion:
Thus, it is verified that sum of the wattmeter reading is equal to the total power taken by the three loads using LTspice.
Want to see more full solutions like this?
Chapter 12 Solutions
Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf
- 5. The figure below shows two star connected loads with three phase power. The voltage source is 120Z0°. The loads are Z₁ = 10 + j4 № and Z₂ = 2 +j3 №. The cables are negligible. Calculate: a) the line and phase current. b) the real power from the source. c) the reactive power of the circuit. Is V N Z₁ Z₁ Z₁ Z₂ Z₂ N N Z₂arrow_forwardPlease answer quickly "In series-connected ac circuit, the total voltage across the circuit is always equal to the sum of the magnitude (only) of the individual voltage across each element." True False The power factor is equal to cosine of the phase difference. True False A leading power factor means that the circuit is predominantly capacitive in nature. True False "Since most loads are resistive in nature (e.g. motors), improvement of power factor is done by connecting capacitor banks or a synchronous condenser " True Falsearrow_forwardс Example: Delta-connected load consists of 10-Ohm resistance in series with 20-mH inductance. Source is Y-connected, abc sequence, 120-V rms, 60Hz. Determine laa, Ibb, Icc, lab, Ibc and ICA if: Van = 120/30°(V)rms Vcn a Van Vbn b IaA IbB I cc B IAB N IBC Z A ICA Carrow_forward
- A generator is rated 100 MW, 13.8kV and 90% power factor. The effectiveresistance is 1.5 times the ohmic resistance. The ohmic resistance isobtained by connecting two terminals to a DC source. The current andvoltage are 87.6 A and 6 V respectively. What is the DC resistance perphase? What is the effective resistance per phase? Whole Solutionarrow_forwardSolve both a) and b) with all the steps and correct detailsarrow_forwardProblem 2 For the system shown in Figure 12.5: a) Find Is. b) Find the average power delivered to each element. c) Find the reactive power associated with each element. d) Find PT, QT, and ST. e) Find the power factor seen by the source E. R₁ ww 392 + E = 50 V/60° R3 ww 492 R₂ 12 Ω Χ 16Ω Xc 802 Figure 12.5arrow_forward
- 3) This MCQ QUESTION FROM BASIC POWER ELECTRICAL ENGINEERING course. just write for me the the correct answer.arrow_forward2.1 Two power stations, A and B, are synchronized at 66 kV. They are inter-connected by a transmission line with an inductive reactance of 6.7-Ω and resistance of 3.5-Ω per phase. The voltage of power station A is advanced with an angle of 10.5 degrees with respect to the voltage of power station B. The loading of power station B has a real power of 200 MW. The respective loads of the two power stations are as follows: Power station A: 165 MVA at a power factor of 0.819 lagging. Power station B: The reactive power consumed by the load is 155 Mvar. *Round off to two decimal places in every question. Determine the following: 12.The interconnector current (kA)and it's angle 13.The reactive power received by power station A (MVar). 14.The active power received by power station B (MW).arrow_forward2.1 Two power stations, A and B, are synchronized at 66 kV. They are inter-connected by a transmission line with an inductive reactance of 6.7-Ω and resistance of 3.5-Ω per phase. The voltage of power station A is advanced with an angle of 10.5 degrees with respect to the voltage of power station B. The loading of power station B has a real power of 200 MW. The respective loads of the two power stations are as follows: Power station A: 165 MVA at a power factor of 0.819 lagging. Power station B: The reactive power consumed by the load is 155 Mvar. *Round off to two decimal places to every question 15.The active power loss within the interconnector (MW). 16.The reactive power loss within the interconnector (MVar). 17.The final loading of power station A (MVA) and it's anglearrow_forward
- Introductory Circuit Analysis (13th Edition)Electrical EngineeringISBN:9780133923605Author:Robert L. BoylestadPublisher:PEARSONDelmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage LearningProgrammable Logic ControllersElectrical EngineeringISBN:9780073373843Author:Frank D. PetruzellaPublisher:McGraw-Hill Education
- Fundamentals of Electric CircuitsElectrical EngineeringISBN:9780078028229Author:Charles K Alexander, Matthew SadikuPublisher:McGraw-Hill EducationElectric Circuits. (11th Edition)Electrical EngineeringISBN:9780134746968Author:James W. Nilsson, Susan RiedelPublisher:PEARSONEngineering ElectromagneticsElectrical EngineeringISBN:9780078028151Author:Hayt, William H. (william Hart), Jr, BUCK, John A.Publisher:Mcgraw-hill Education,