Textbook Question
Chapter 11, Problem 11.78P
Consider the Rankine cycle of Problem 11.77, whichrejects 2.3 MW to the condenser, which is suppliedwith a cooling water flow rate of 70 kg/s at 15°C.
(a) Calculate UA, a parameter that is indicative of thesize of the condenser required for this operatingcondition.
(b) Consider now the situation where the overall heat transfer coefficient for the condenser, U, is
reduced by 10% because of fouling. Determinethe reduction in the thermal efficiency of thecycle caused by fouling, assuming that the cooling water flow rate and water temperature remainthe same and that the condenser is operated at thesame steam pressure.
Expert Solution & Answer
Want to see the full answer?
Check out a sample textbook solutionStudents have asked these similar questions
The purpose of the regenerative heat exchanger is to essentially recycle the heat rejectedin step (B) as heat absorbed in step (D). Show why this works for the case of a general workingfluid with heat capacity, Cv(T).
A 4-pass-low-pressure surface type feedwater heater is designed to heat
92,730 kg/hr of feedwater from 40°C initial to 80°C final temperature using
steam bleed at 70 kpa abs. containing 2,645 Kj/kg enthalpy. Assume no
subcooling of condensate, determine the effective length of 19 mm O.D x 2
mm thick Muntz metal tubes to be installed, if the water velocity inside the
tubes is 1.22 m/s and U = 3000 W /m²k based on the external surface of the
tubes.
4.
A two pass steam surface condenser is to be designed to condense 10000 kg/hr of steam having an enthalpy of 2240 kj/kg. Condenser pressure is 13.79 kpa. circulating water enters the condenser at 25 C and leaves at 40 C. the outside and inside diameter for a water tube, OD=20 mm, ID = 17 mm and water velocity of 3 m/s. if the overall coefficient of the heat transfer is 14100 kj/hr-m-C of outside tube surface, determine the amount of circulating water in m/hr.
Chapter 11 Solutions
Fundamentals of Heat and Mass Transfer
Ch. 11 - In a fire-tube boiler, hot products of combustion...Ch. 11 - A shell-and-tube heat exchanger is to heat an...Ch. 11 - A steel tube (k=50W/mK) of inner and outer...Ch. 11 - A heat recovery device involves transferring...Ch. 11 - A novel design for a condenser consists of a tube...Ch. 11 - The condenser of a steam power plant...Ch. 11 - Thin-walled aluminum tubes of diameter D = 10mmare...Ch. 11 - A tinned-tube, cross-how heat exchanger is to use...Ch. 11 - Water at a rate of 45,500kg/h is heated from 80...Ch. 11 - A novel heat exchanger concept consists of a...
Ch. 11 - Prob. 11.12PCh. 11 - A process fluid having a specific heat of...Ch. 11 - A shell-and-tube exchanger (two shells, four tube...Ch. 11 - Consider the heat exchanger of Problem 11.14....Ch. 11 - The hot and cold inlet temperatures to a...Ch. 11 - A concentric tube heat exchanger of length L = 2 m...Ch. 11 - A counterflow, concentric tube heat exchanger is...Ch. 11 - Consider a concentric tube heat exchanger with an...Ch. 11 - A shell-and-tube heat exchanger must be designed...Ch. 11 - A concentric tube heat exchanger for cooling...Ch. 11 - A counterflow, concentric tube heat exchanger used...Ch. 11 - An automobile radiator may be viewed as a...Ch. 11 - Hot air for a large-scale drying operation is to...Ch. 11 - In a dairy operation, milk at a flow rate of 250...Ch. 11 - The compartment heater of an automobile...Ch. 11 - A counterflow, twin-tube heat exchanger is made...Ch. 11 - Consider a coupled shell-in-tube heat exchange...Ch. 11 - For health reasons, public spaces require the...Ch. 11 - A shell-and-tube heat exchanger (1 shell pass, 2...Ch. 11 - Saturated water vapor leaves a steam turbine at a...Ch. 11 - The human brain is especially sensitive to...Ch. 11 - Prob. 11.47PCh. 11 - A plate-tin heat exchanger is used to condense a...Ch. 11 - In a supercomputer, signal propagation delays...Ch. 11 - Untapped geothermal sites in the United States...Ch. 11 - A shell-and-tube heat exchanger consists of 135...Ch. 11 - An ocean thermal energy conversion system is...Ch. 11 - Prob. 11.55PCh. 11 - Prob. 11.56PCh. 11 - The chief engineer at a university that is...Ch. 11 - A shell-and-tube heat exchanger with one shell...Ch. 11 - Prob. 11.59PCh. 11 - Prob. 11.60PCh. 11 - Prob. 11.61PCh. 11 - Prob. 11.62PCh. 11 - A recuperator is a heat exchanger that heats air...Ch. 11 - Prob. 11.64PCh. 11 - Prob. 11.65PCh. 11 - A cross-flow heat exchanger consists of a bundle...Ch. 11 - Exhaust gas from a furnace is used to preheat the...Ch. 11 - Prob. 11.68PCh. 11 - A liquefied natural gas (LNG) regasification...Ch. 11 - Prob. 11.70PCh. 11 - A shell-and-tube heat exchanger consisting of...Ch. 11 - Prob. 11.73PCh. 11 - The power needed to overcome wind and friction...Ch. 11 - Prob. 11.75PCh. 11 - Consider a Rankine cycle with saturated steam...Ch. 11 - Consider the Rankine cycle of Problem 11.77,...Ch. 11 - Prob. 11.79PCh. 11 - Prob. 11.80PCh. 11 - Hot exhaust gases are used in a...Ch. 11 - Prob. 11.84PCh. 11 - Prob. 11.90PCh. 11 - Prob. 11S.1PCh. 11 - Prob. 11S.2PCh. 11 - Prob. 11S.3PCh. 11 - Solve Problem 11.15 using the LMTD method.Ch. 11 - Prob. 11S.5PCh. 11 - Prob. 11S.6PCh. 11 - Prob. 11S.8PCh. 11 - Prob. 11S.10PCh. 11 - Prob. 11S.11PCh. 11 - A cooling coil consists of a bank of aluminum...Ch. 11 - Prob. 11S.17P
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.Similar questions
- A two-pass steam surface condenser is to be designed to condense10,000 kg/hr of steam having an enthalpy of 2,240 kJ/kg. Condenserpressure is 13.79 kPa. Circulating water enters the condenser at 25 OCand leaves at 40 OC. The outside and inside diameter for a water tube;OD=20 mm , ID = 17 mm and water velocity of 3 m/s. If the overallcoefficient of heat transfer is 14,100 kJ/hr-m2-OC of outside tubesurface, determine the amount of circulating water in m3/hr.arrow_forwardWater from a natural river source at 22°C and a flow rate of 25,000 kg/s is used as the heat sink for a condenser unit at a large manufacturing company. The condenser consist of 20,000 tubes and is used to condense steam to liquid at 50°C. construction and 20mm nominal diameter. The condenser is a one The tubes are of thin wall shell, two-tube-passes heat exchanger. convective heat transfer coefficient of 11,500 W/m².K on the tube outer surface and the water flowing in the tubes is required to remove heat at a rate of 2 x 10° W. Environmental laws require that the effluent from the condensing unit to the river source should be less than 35°C. Using both the e-NTU and LMTD methods, calculate the outlet temperature of the cooling water and the required tube length per pass. The specification is a Use T =27°C; and for flow through the tubes use, Nu, = 0.023 Re Pr°4arrow_forwardQ#03: a) Calculate the log-mean-temperature difference and value of overall heat transfer coefficient from the data provided in observation table#01. The data is collected by testing shell-and-tube heat exchanger having parallel/co-current flow arrangement on multi-heat exchanger unit. Note: The contact area for shell-and-tube heat exchanger is 0.3297 m?. Take G-4.183 KJ/kg°C and p=998.2 kg/m³. Сool cool water in Hot water Hot water in Hot water out water U Q. Hot Water (LPM) Q: Cool Water tank temp. temp. temp. T3 out S# LMTD temp. T4 temp. Ts (LPM) ("C) (°C) (°C) (*C) (°C) 1 3 50 50 38 17 27 T-bl u01arrow_forward
- a) Calculate the log-mean-temperature difference and value of overall heat transfer coefficient from the data provided in observation table#01. The data is collected by testing shell-and-tube heat exchanger having parallel/co-current flow arrangement on multi-heat exchanger unit. Note: The contact area for shell-and-tube heat exchanger is 0.3297 m?. Take C,=4.183KJ/kg°C and p=998.2 kg/m?. Сool cool Hot water Hot water in Hot water out water Q: Cool water in U Q. Hot Water (LPM) tank temp. temp. T: temp. T3 out S# Water LMTD temp. T4 (°C) T1 temp. Ts (LPM) ("C) (°C) (°C) (°C) 1 3 2 50 50 38 17 27arrow_forward21, from a temperature of water is beine heated 85.1°F to a Aaturated temperatue of 211.4 °F at pressure of 0.101325 mpausing a 2-4 shell and tube heat exchanger. The inlet water mass flow rate =600 kg /min. The heat transfer oil being used is assumed to be stable mineral oil enters at 320 °F, highly refined and with average heat mass flow rate = 148 2 kg /min 0.4498 btu I 16°F capacity Overall heat transfer coefficient 113.3973 btu toztty fina: heeded surface areaarrow_forwardPlease help me, I want to answer this question without quoting or plagiarism, I hope the solution is to be written in MS Word, not written by hand. (b)arrow_forward
- in a 10-m long center-current flow tubular heat exchanger, a liquid food, flowing in the inner pipe (inside diameter 5 cm), is heated from 4 to 60 C for pasteurization. In the outer tube (diameter 10 cm), hot water enters at 95 C and exits at 80 C. A) If the mass flow rate of the hot water is 5 kg/s, what is the flow rate of the pasteurized product? The specific heat of the water is 4.2 kJ/(kg C), specific heat of product is 3.8 kJ/(kg C) B) what is the log mean temperature difference C) What is the overall heat transfer coefficient for the heat exchanger based on the outside surface?arrow_forwardThe cooling load of a cold store is 24kW, the evaporator temperature is -10 ° C, the condenser temperature is 40 ° C. R134a is used as the refrigerant. Calculate the mass flow rate, the power consumed by the compressor, the cooling effect coefficient and coefficient according to all these data. (compressor characteristics Heating effect hik (compressor internal efficiency) = 0.75, hmk (mechanical efficiency) = 0.80, hec (electric efficiency) = 0.97 and hkk (belt pulley efficiency) = 0.95) motorarrow_forwardhelpparrow_forward
- Calculate the logarithmic mean temperature difference for a condenser if the temperature difference between condensing steam and water inlet is 650oC and that steam inlet and water is 120oC.arrow_forwardA straight-condensing 10,500 kW turbine has a guaranteed steam rate of 6 kg/kW.hr when exhausting at 5.0 kPa. Exhaust steam enters the condenser at 90% quality, and it is estimated that fouling will decrease the overall coefficient by 30% during operation. Cooling water is available at 20 ℃, and for design purposes, 1 ½ in OD 17 BWG Brass tubes (thickness = 0.070 in, k=65 BTU/hrftF°.) are specified with 12 C° rise in cooling water, which circulates at 6 ft/s. Inside and outside film coefficients are hi=970 and ho=1478 BTU/hrft2F°. Design a condenser for this turbine, considering tube and boundary resistance as flat surfaces and neglecting any crossflow factor. Determine: a) Effective overall coefficient of heat transfer b) Volume flow rate of cooling waterarrow_forwardAn ice plant of 200 tons refrigeration capacity makes use of the shelland tube superheat remover. The temperature of discharge is 112 OCand vapor is cooled to 52 OC. Water enters at 24 OC and is heatedduring the counterflow with the vapor to 70 OC. The compressoroperates at 1352.2 kPaa condenser pressure and 247.14 kPaaevaporating pressure. The overall coefficient of heat transfer is 390kJ/hr-m2-C. Calculate the LMTD.arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Principles of Heat Transfer (Activate Learning wi...Mechanical EngineeringISBN:9781305387102Author:Kreith, Frank; Manglik, Raj M.Publisher:Cengage Learning
Principles of Heat Transfer (Activate Learning wi...
Mechanical Engineering
ISBN:9781305387102
Author:Kreith, Frank; Manglik, Raj M.
Publisher:Cengage Learning
The Refrigeration Cycle Explained - The Four Major Components; Author: HVAC Know It All;https://www.youtube.com/watch?v=zfciSvOZDUY;License: Standard YouTube License, CC-BY