P1-Equipment ratings for the three-bus power system shown below are as follows (all per unit values listed were determined utilizing the equipment's Voltage and MVA ratings): Generator G1: Generator G2: 550 MVA, 13.8 kV, X" = 0.18 per unit (pos, neg, zero) 750 MVA, 18 kV, X" = 0.20 per unit (pos, neg, zero) Transformer T1: 500 MVA, 13.8 A/500 YkV X = 0.12 per unit Transformer T2: Each 500 kV line: 750 MVA, 18 A/500 Y kV, X = 0.10 per unit X1 = 385 Ohms A three-phase bolted short circuit occurs at bus 2, where the prefault voltage is 525 kV. Prefault load current is neglected. a) Identify per unit impedance of the G1, G2, T1, T2, and the 500 kV line based upon the proper voltage base and 1000 MVA b) Draw the positive, negative, and zero-sequence reactance diagram in per unit on a 1000- MVA. c) Determine the Thevenin reactance in per-unit at the fault for the positive, negative, and zero sequences. d) Determine the subtransient fault current in per unit and in kA rms, and e) contributions to the fault current from generator G1 and G2 T1 1 G1 7500 38 ΔΥ j50 12 YA 22 G2

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter9: Unsymmetrical Faults
Section: Chapter Questions
Problem 9.5P
icon
Related questions
Question

DO NOT WANT AI SOLUTIONS. Thank you

P1-Equipment ratings for the three-bus power system shown below are as follows (all per unit values
listed were determined utilizing the equipment's Voltage and MVA ratings):
Generator G1:
Generator G2:
550 MVA, 13.8 kV, X" = 0.18 per unit (pos, neg, zero)
750 MVA, 18 kV, X" = 0.20 per unit (pos, neg, zero)
Transformer T1:
500 MVA, 13.8 A/500 YkV X = 0.12 per unit
Transformer T2:
Each 500 kV line:
750 MVA, 18 A/500 Y kV, X = 0.10 per unit
X1 = 385 Ohms
A three-phase bolted short circuit occurs at bus 2, where the prefault voltage is 525 kV. Prefault
load current is neglected.
a) Identify per unit impedance of the G1, G2, T1, T2, and the 500 kV line based upon the
proper voltage base and 1000 MVA
b) Draw the positive, negative, and zero-sequence reactance diagram in per unit on a 1000-
MVA.
c) Determine the Thevenin reactance in per-unit at the fault for the positive, negative, and
zero sequences.
d) Determine the subtransient fault current in per unit and in kA rms, and
e) contributions to the fault current from generator G1 and G2
T1 1
G1
7500
38
ΔΥ
j50
12
YA
22
G2
Transcribed Image Text:P1-Equipment ratings for the three-bus power system shown below are as follows (all per unit values listed were determined utilizing the equipment's Voltage and MVA ratings): Generator G1: Generator G2: 550 MVA, 13.8 kV, X" = 0.18 per unit (pos, neg, zero) 750 MVA, 18 kV, X" = 0.20 per unit (pos, neg, zero) Transformer T1: 500 MVA, 13.8 A/500 YkV X = 0.12 per unit Transformer T2: Each 500 kV line: 750 MVA, 18 A/500 Y kV, X = 0.10 per unit X1 = 385 Ohms A three-phase bolted short circuit occurs at bus 2, where the prefault voltage is 525 kV. Prefault load current is neglected. a) Identify per unit impedance of the G1, G2, T1, T2, and the 500 kV line based upon the proper voltage base and 1000 MVA b) Draw the positive, negative, and zero-sequence reactance diagram in per unit on a 1000- MVA. c) Determine the Thevenin reactance in per-unit at the fault for the positive, negative, and zero sequences. d) Determine the subtransient fault current in per unit and in kA rms, and e) contributions to the fault current from generator G1 and G2 T1 1 G1 7500 38 ΔΥ j50 12 YA 22 G2
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning