b) The single line diagram of a power system is shown in Figure Q2.1 including generator and transformer winding connection and earthing details. The parameters for this system have been calculated on a common 100 MVA base and are given in Table Q2.1. All resistances and shunt susceptances are neglected. This system experiences a single line to ground fault at a point F on line L1. The point F is at a distance d from Bus 4 along the line L1. The total length 1 of the line L1 is 50 km. Note that the location of d is not drawn to scale in Figure Q2.1. The fault current at the fault point F is measured to be 6.106 kA. G1 G2 1 2 IN T1 3 ΔΕ T2 T3 Figure Q2.1 4 L1 (l-d) 5
b) The single line diagram of a power system is shown in Figure Q2.1 including generator and transformer winding connection and earthing details. The parameters for this system have been calculated on a common 100 MVA base and are given in Table Q2.1. All resistances and shunt susceptances are neglected. This system experiences a single line to ground fault at a point F on line L1. The point F is at a distance d from Bus 4 along the line L1. The total length 1 of the line L1 is 50 km. Note that the location of d is not drawn to scale in Figure Q2.1. The fault current at the fault point F is measured to be 6.106 kA. G1 G2 1 2 IN T1 3 ΔΕ T2 T3 Figure Q2.1 4 L1 (l-d) 5
Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
Related questions
Concept explainers
Three-Phase Transformers
Three-segment transformers are a type of transformer used to transform voltages of electrical systems into three ranges. Two type transformers are shell-type transformer and core type transformer. In brief, it could be described because of the exquisite kinds of configurations.
Transformer
Ever since electricity has been created, people have started using it in its entirety. We see many types of Transformers in the neighborhoods. Some are smaller in size and some are very large. They are used according to their requirements. Many of us have seen the electrical transformer but they do not know what work they are engaged in.
Question
![b) The single line diagram of a power system is shown in Figure Q2.1 including
generator and transformer winding connection and earthing details. The parameters
for this system have been calculated on a common 100 MVA base and are given in
Table Q2.1. All resistances and shunt susceptances are neglected. This system
experiences a single line to ground fault at a point F on line L1. The point F is at a
distance d from Bus 4 along the line LI. The total length of the line L1 is 50 km.
Note that the location of d is not drawn to scale in Figure Q2.1. The fault current at
the fault point F is measured to be 6.106 kA.
G1
G1
G2
i)
G2
T1
T2
T3
L1
11)
2
Rated voltage
(kV)
20
20
20/33
20/33
33/11
11
T1
ΔΕ
T2
T3
Figure Q2.1
Table Q2.1
Zero sequence
reactance Xo (p.u.)
0.20
0.15
0.12
0.20
0.20
1.20
Positive sequence
reactance X₁ (p.u.)
0.30
0.25
0.12
0.20
0.20
0.50
UNIVERSITY OF
LIVERPOOL
L1
(l-d)
5
Negative sequence
reactance X₂ (p.u.)
0.35
0.30
0.12
0.20
0.20
0.50
Determine the zero, positive, and negative sequence Thevenin equivalent
impedances as seen at the fault point F. These should be evaluated in per unit
and shown as a function of d.
Use the sequence impedances calculated in part (i) to determine the distance d
of the fault (in km) from Bus 4.](/v2/_next/image?url=https%3A%2F%2Fcontent.bartleby.com%2Fqna-images%2Fquestion%2Fa9b1d17a-e20e-4c57-82c6-db5a2ea019fe%2F641eb54b-ab1b-424a-a9a7-6b7ead5d819b%2Fhude49k_processed.png&w=3840&q=75)
Transcribed Image Text:b) The single line diagram of a power system is shown in Figure Q2.1 including
generator and transformer winding connection and earthing details. The parameters
for this system have been calculated on a common 100 MVA base and are given in
Table Q2.1. All resistances and shunt susceptances are neglected. This system
experiences a single line to ground fault at a point F on line L1. The point F is at a
distance d from Bus 4 along the line LI. The total length of the line L1 is 50 km.
Note that the location of d is not drawn to scale in Figure Q2.1. The fault current at
the fault point F is measured to be 6.106 kA.
G1
G1
G2
i)
G2
T1
T2
T3
L1
11)
2
Rated voltage
(kV)
20
20
20/33
20/33
33/11
11
T1
ΔΕ
T2
T3
Figure Q2.1
Table Q2.1
Zero sequence
reactance Xo (p.u.)
0.20
0.15
0.12
0.20
0.20
1.20
Positive sequence
reactance X₁ (p.u.)
0.30
0.25
0.12
0.20
0.20
0.50
UNIVERSITY OF
LIVERPOOL
L1
(l-d)
5
Negative sequence
reactance X₂ (p.u.)
0.35
0.30
0.12
0.20
0.20
0.50
Determine the zero, positive, and negative sequence Thevenin equivalent
impedances as seen at the fault point F. These should be evaluated in per unit
and shown as a function of d.
Use the sequence impedances calculated in part (i) to determine the distance d
of the fault (in km) from Bus 4.
Expert Solution
![](/static/compass_v2/shared-icons/check-mark.png)
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 6 steps with 16 images
![Blurred answer](/static/compass_v2/solution-images/blurred-answer.jpg)
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
![Introductory Circuit Analysis (13th Edition)](https://www.bartleby.com/isbn_cover_images/9780133923605/9780133923605_smallCoverImage.gif)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
![Delmar's Standard Textbook Of Electricity](https://www.bartleby.com/isbn_cover_images/9781337900348/9781337900348_smallCoverImage.jpg)
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
![Programmable Logic Controllers](https://www.bartleby.com/isbn_cover_images/9780073373843/9780073373843_smallCoverImage.gif)
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
![Introductory Circuit Analysis (13th Edition)](https://www.bartleby.com/isbn_cover_images/9780133923605/9780133923605_smallCoverImage.gif)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
![Delmar's Standard Textbook Of Electricity](https://www.bartleby.com/isbn_cover_images/9781337900348/9781337900348_smallCoverImage.jpg)
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
![Programmable Logic Controllers](https://www.bartleby.com/isbn_cover_images/9780073373843/9780073373843_smallCoverImage.gif)
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
![Fundamentals of Electric Circuits](https://www.bartleby.com/isbn_cover_images/9780078028229/9780078028229_smallCoverImage.gif)
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
![Electric Circuits. (11th Edition)](https://www.bartleby.com/isbn_cover_images/9780134746968/9780134746968_smallCoverImage.gif)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
![Engineering Electromagnetics](https://www.bartleby.com/isbn_cover_images/9780078028151/9780078028151_smallCoverImage.gif)
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,