Consider a temperature control loop composed of a voltage-controlled power source (gain coefficient of 2 kW/V), a furnace, a compensator (which acts as a controller), and an electrical thermometer to obtain a measurement of the room temperature. This system can be represented by the following block diagram, with all units shown: Controller Heater R'(s) Volts 8(s + 1.6) 2 kW/V S+ 0.2 Volts kW Furnace 500 (s + 0.1)(s +25) Thermometer T'(s) T'm(s) 0.01 V/°C Volts °C Note that our system's setpoint is in volts rather than °C. a) Determine the closed-loop transfer function for measured temperature setpoint changes, Tm(s) R'(s)' b) Create Bode plots of this system using controller gains of Kc = {1, 10, 100}. c) If the compensator is replaced by a PID-controller, determine the initial controller parameters for this system under PID control using the Ziegler-Nichols initial tuning method. d) Model both the original system and the system under PID control obtained in Part (c) in Simulink. Simulating a step change of 0.01 V in R'(s), obtain time-domain plots for both models showing the actual temperature, T', and the measured temperature, T responses. e) Lastly, we will simulate some unwanted cooling effects to our system. Modify your simulation from part d) to apply a -100 kW step disturbance to the input of the furnace, while R'(s) = 0. Compare each model's ability to reject disturbances.

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question

Please describe how to do each step in detail. thanks

Consider a temperature control loop composed of a voltage-controlled power source (gain
coefficient of 2 kW/V), a furnace, a compensator (which acts as a controller), and an electrical
thermometer to obtain a measurement of the room temperature. This system can be represented
by the following block diagram, with all units shown:
Controller
Heater
R'(s)
Volts
8(s + 1.6)
2 kW/V
S+ 0.2
Volts
kW
Furnace
500
(s + 0.1)(s +25)
Thermometer
T'(s)
T'm(s)
0.01 V/°C
Volts
°C
Note that our system's setpoint is in volts rather than °C.
a) Determine the closed-loop transfer function for measured temperature setpoint changes,
Tm(s)
R'(s)'
b) Create Bode plots of this system using controller gains of Kc = {1, 10, 100}.
c) If the compensator is replaced by a PID-controller, determine the initial controller
parameters for this system under PID control using the Ziegler-Nichols initial tuning
method.
d) Model both the original system and the system under PID control obtained in Part (c) in
Simulink. Simulating a step change of 0.01 V in R'(s), obtain time-domain plots for both
models showing the actual temperature, T', and the measured temperature, T
responses.
e) Lastly, we will simulate some unwanted cooling effects to our system. Modify your
simulation from part d) to apply a -100 kW step disturbance to the input of the furnace,
while R'(s) = 0. Compare each model's ability to reject disturbances.
Transcribed Image Text:Consider a temperature control loop composed of a voltage-controlled power source (gain coefficient of 2 kW/V), a furnace, a compensator (which acts as a controller), and an electrical thermometer to obtain a measurement of the room temperature. This system can be represented by the following block diagram, with all units shown: Controller Heater R'(s) Volts 8(s + 1.6) 2 kW/V S+ 0.2 Volts kW Furnace 500 (s + 0.1)(s +25) Thermometer T'(s) T'm(s) 0.01 V/°C Volts °C Note that our system's setpoint is in volts rather than °C. a) Determine the closed-loop transfer function for measured temperature setpoint changes, Tm(s) R'(s)' b) Create Bode plots of this system using controller gains of Kc = {1, 10, 100}. c) If the compensator is replaced by a PID-controller, determine the initial controller parameters for this system under PID control using the Ziegler-Nichols initial tuning method. d) Model both the original system and the system under PID control obtained in Part (c) in Simulink. Simulating a step change of 0.01 V in R'(s), obtain time-domain plots for both models showing the actual temperature, T', and the measured temperature, T responses. e) Lastly, we will simulate some unwanted cooling effects to our system. Modify your simulation from part d) to apply a -100 kW step disturbance to the input of the furnace, while R'(s) = 0. Compare each model's ability to reject disturbances.
Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,