SINGLE LINE DIAGRAM M 2-80mm2 THHN/THWN CU. WIRE 1-22mm² TW (GRD WIRE) IN 54mm RSC PB-1 PB-2 125AT, 2P, 230V GOAT M PB1 PB2 ΤΟ ELECTRIC METER 2-8.0 mm², THHN GROUND FLOOR MAIN PANEL BOARD MAIN BREAKER 125 AT CB, 2 POLE 30 SQ MM 54 MM CU THHN PVC CONDUIT TO MAIN PANEL BOARD 8.0 mm², THHN SECOND FLOOR PANEL BOARD-1 MAIN BREAKER 60 AT CB, 2 POLE 8 SQ MM CU THHN PVC CONDUIT 25 MM LAUNDRY WP KITCHEN WP REFRIGERATOR CD 15 AMP 20 AMP MASTER BEDROOM 20 AMP 20 AMP MARPORT WE TMTWP TO MAIN PANEL BOARD 18.0 mm, THHN THIRD FLOOR PANEL BOARD - 2 MAIN BREAKER 60 AT CB, 2 POLE 8 SQ MM 25 MM CU THHN PVC CONDUIT MASTER TAB WP MASTER TAB 2WP MASTER BEDROома 20 AMP 20 AMP TMB2W.P TAB 3 WP LIVING AREA LOUNGE AREA 15 AMP 15 AMP TV CABLE S KITCHEN LO TABLO BEDROOM 1 20 AMP 20 AMP BEDROOM 2 ACU 20 AMP 20 AMP ACU TV CABLE SET DINING AREA LO FRONTYARD L MASTER BEDROOM CARPORT LO 15 AMP 60 AMP SECOND FLOOR 20 AMP 15 AMP STAIRS LO MASTERAR LLO MASTER TABLO BEDROOM1CO LIVING AREALD THIRD FLOOR 2-80mm² THHN CU. WIRE 1-22mm² TW Cu. WIRE (G) IN 54mm RSC 125AT, 2P, 230V PANEL BOARD! GOAT PANEL BOARD 2 SPARE MASTER BEDROOM 2 BEDROOM CO 20 AMP 15 AMP STAIRS LO MASTERE MASTER TABLO TABLO OUTDOOR CRING AMP SPARE BALCONY 1 LO BEDROOM L 15 AMP AMP SPARE LOUNGE AREA IL BALCONY 1 LO BEDROOM LO LOUNGE AREA 1L 15 AMP 15 AMP LO TOTAL AMPERES = 91.99 A IP (91.99 x 100%)+(25% x 8) -93.99 A FEEDER CURRENT = 93.99 x 125% = 117.49 A FOR OVERCURRENT DEVICE TOTAL AMPERES = 32.6 A IP (32.6 x 100%)+(25% x 8) = 34.6 A FEEDER CURRENT - 34.6 x 125% 43.25 A FOR OVERCURRENT DEVICE HIGHEST CIRCUIT BREAKER RATING = 60 A HIGHEST MOTOR FL CURRENT SUM OF REMAINING CURRENT 8.00 = 8.00 A HIGHEST CIRCUIT BREAKER RATING - 20 A HIGHEST MOTOR FL CURRENT = 8.00 A = 91.99 - SUM OF REMAINING CURRENT = 32.6-8.00 = 24.6 A TOTAL AMPERES = 37.82 A IP = (37.82 x 100% ) + ( 25 % x 8) = 39.82 A FEEDER CURRENT -39.82 x 125% = 49.78 A FOR OVERCURRENT DEVICE HIGHEST CIRCUIT BREAKER RATING HIGHEST MOTOR FL CURRENT SUM OF REMAINING CURRENT 20 A = 8.00 A = 37.82 - 8.00 - 29.82 A = 83.99 A APPLY DEMAND FACTOR = 24.6 x 125% APPLY DEMAND FACTOR = 83.99 = 30.75 A APPLY DEMAND FACTOR 125% = 29.82 x x 125% -37.28 A = 104.99 A 1 PANEL BOARD MANAGEMENT From the lighting and power plans (estimated from the example images): Ground Floor 1. Ceiling Lights: 4 fixtures 。 Assumed Wattage (each): 10 W (LED) 。 Total: 2. Wall Lamps: 3 fixtures 。 Assumed Wattage (each): 15 W (LED) 。 Total: 3. Convenience Outlets: 6 outlets 。 Assumed Wattage (each): 180 W 。 Total: 4. Refrigerator Outlet: 1 outlet 。 Assumed Wattage: 150 W ° Total: 5. Range Outlet: 1 outlet 。 Assumed Wattage: 1000 W 。 Total: Ground Floor Total Load (Watts): ☑ 40+45 + 1080 + 150 + 1000 = 2315 \text{ W} \ Second Floor 1. Ceiling Lights: 5 fixtures 。 Assumed Wattage (each): 10 W 。 Total: 2. Wall Lamps: 2 fixtures 。 Assumed Wattage (each): 15 W ° Total: 3. Convenience Outlets: 4 outlets 。 Assumed Wattage (each): 180 W ° Total: Second Floor Total Load (Watts): ☑ 50+30 720 = 800 \text{ W} } Third Floor 1. Ceiling Lights: 3 fixtures 。 Assumed Wattage (each): 10 W 。 Total: 2. Wall Lamp: 1 fixture 。 Assumed Wattage: 15 W 。 Total: 3. Convenience Outlets: 2 outlets 。 Assumed Wattage (each): 180 W 。 Total: 4. Waterproof Outlet (e.g., balcony/ garden): 1 outlet 。 Assumed Wattage: 100 W 。 Total: Third Floor Total Load (Watts): ☑ 30+15+ 360 + 100 = 505 \text{ W} 2. Convert Wattage to Amperage Using the formula: . • = Current in amperes = Power in watts = Voltage (assume 220 V) Per Floor Current 1. Ground Floor Current 1. Second Floor Current 1. Third Floor Current 1. Total Connected Current (Amperes) 1. Demand Factor Residential circuits often use a demand factor of around 80% to account for the fact that not all loads run simultaneously at full capacity. 4. Breaker Sizing per Floor When grouping circuits, ensure that each breaker is loaded to no more than 80% of its rating to avoid nuisance tripping. Ground Floor • Load: 10.52 A • A 15A breaker is suitable. At 80% loading, a 15A breaker can handle about 12A. Since 10.52A < 12A, it's within the safe limit. Second Floor • Load: 3.64 A • This is a relatively small load. A 10A breaker or 15A breaker would be sufficient. Typically, you might combine small circuits or leave them on a separate breaker if code or design preferences require separation. Third Floor • Load: 2.30 A • Similarly small load. A 10A breaker would be sufficient. 5. Main Breaker and Feeder Sizing 1. Main Breaker 。 Calculated demand load is ~13.17A. 。 A 20A main breaker is a practical choice, giving a safe margin above 13.17A and leaving room for minor future expansions. 2. Feeder Cable 。 Must safely carry the main breaker rating (20A). • Common practice: ► 2.5 mm² copper for up to 20A over moderate distances. ▸ 4.0 mm² copper if the distance is long or if local codes require a larger gauge for voltage drop or future-proofing. 6. Example Panel Board Schedule Below is a simplified example of how you might arrange the panel board: Circui Descr Break Estim Rema t No. iption er 1 Grou nd Floor ated rks Size Load (A) 15A 10.52 Keep withi n Light 80% of S/ Outle ts 15A 2 Seco 10A 3.64 Could nd comb Floor Light ine with S/ Third Outle Floor ts if desir ed 3 Third Floor 10A 2.30 Low load Light S/ Outle ts Main Break er 20A 13.17 Cover (dem S and) total dema nd load Note: In many real projects, you might have separate circuits for heavy loads. (e.g., dedicated range circuit, air conditioning units, etc.), or more granular lighting/outlet circuits to comply with local electrical codes. 7. Key Points and Explanation 1. Why Apply a Demand Factor? In residential design, it's rare that all lights and appliances operate simultaneously at peak. Thus, a demand factor (often 70-80% for typical residences) is applied to avoid oversizing. 2. Why Keep Each Breaker at 80% Loading? Circuit breakers are designed to handle their full rated current, but continuous loads (running over 3 hours) must not exceed 80% of the breaker rating per most electrical codes (e.g., NEC in the US). This ensures safety and reliability. 3. Breaker Sizing vs. Wire Sizing 。 Breaker rating protects the circuit wire from overheating. 。 Wire gauge is chosen to match or exceed the breaker rating. 。 If you have long wire runs, you may upsize to reduce voltage drop. 4. Local Code Requirements Always cross-check with your local electrical code (NEC, IEC, PEC, etc.) for exact rules on circuit loading, branch circuit grouping, wire sizing, grounding, GFCI/AFCI requirements, and breaker selection. Final Summary 1. Total Estimated Load: ~3620 W (16.46 A at 220V). 2. After 80% Demand Factor: ~13.17 A. 3. Recommended Main Breaker: 20A. 4. Branch Circuits: • Ground Floor: 15A breaker (~10.5A load) • Second Floor: 10A breaker (~3.6A load) o Third Floor: 10A breaker (~2.3A load)
SINGLE LINE DIAGRAM M 2-80mm2 THHN/THWN CU. WIRE 1-22mm² TW (GRD WIRE) IN 54mm RSC PB-1 PB-2 125AT, 2P, 230V GOAT M PB1 PB2 ΤΟ ELECTRIC METER 2-8.0 mm², THHN GROUND FLOOR MAIN PANEL BOARD MAIN BREAKER 125 AT CB, 2 POLE 30 SQ MM 54 MM CU THHN PVC CONDUIT TO MAIN PANEL BOARD 8.0 mm², THHN SECOND FLOOR PANEL BOARD-1 MAIN BREAKER 60 AT CB, 2 POLE 8 SQ MM CU THHN PVC CONDUIT 25 MM LAUNDRY WP KITCHEN WP REFRIGERATOR CD 15 AMP 20 AMP MASTER BEDROOM 20 AMP 20 AMP MARPORT WE TMTWP TO MAIN PANEL BOARD 18.0 mm, THHN THIRD FLOOR PANEL BOARD - 2 MAIN BREAKER 60 AT CB, 2 POLE 8 SQ MM 25 MM CU THHN PVC CONDUIT MASTER TAB WP MASTER TAB 2WP MASTER BEDROома 20 AMP 20 AMP TMB2W.P TAB 3 WP LIVING AREA LOUNGE AREA 15 AMP 15 AMP TV CABLE S KITCHEN LO TABLO BEDROOM 1 20 AMP 20 AMP BEDROOM 2 ACU 20 AMP 20 AMP ACU TV CABLE SET DINING AREA LO FRONTYARD L MASTER BEDROOM CARPORT LO 15 AMP 60 AMP SECOND FLOOR 20 AMP 15 AMP STAIRS LO MASTERAR LLO MASTER TABLO BEDROOM1CO LIVING AREALD THIRD FLOOR 2-80mm² THHN CU. WIRE 1-22mm² TW Cu. WIRE (G) IN 54mm RSC 125AT, 2P, 230V PANEL BOARD! GOAT PANEL BOARD 2 SPARE MASTER BEDROOM 2 BEDROOM CO 20 AMP 15 AMP STAIRS LO MASTERE MASTER TABLO TABLO OUTDOOR CRING AMP SPARE BALCONY 1 LO BEDROOM L 15 AMP AMP SPARE LOUNGE AREA IL BALCONY 1 LO BEDROOM LO LOUNGE AREA 1L 15 AMP 15 AMP LO TOTAL AMPERES = 91.99 A IP (91.99 x 100%)+(25% x 8) -93.99 A FEEDER CURRENT = 93.99 x 125% = 117.49 A FOR OVERCURRENT DEVICE TOTAL AMPERES = 32.6 A IP (32.6 x 100%)+(25% x 8) = 34.6 A FEEDER CURRENT - 34.6 x 125% 43.25 A FOR OVERCURRENT DEVICE HIGHEST CIRCUIT BREAKER RATING = 60 A HIGHEST MOTOR FL CURRENT SUM OF REMAINING CURRENT 8.00 = 8.00 A HIGHEST CIRCUIT BREAKER RATING - 20 A HIGHEST MOTOR FL CURRENT = 8.00 A = 91.99 - SUM OF REMAINING CURRENT = 32.6-8.00 = 24.6 A TOTAL AMPERES = 37.82 A IP = (37.82 x 100% ) + ( 25 % x 8) = 39.82 A FEEDER CURRENT -39.82 x 125% = 49.78 A FOR OVERCURRENT DEVICE HIGHEST CIRCUIT BREAKER RATING HIGHEST MOTOR FL CURRENT SUM OF REMAINING CURRENT 20 A = 8.00 A = 37.82 - 8.00 - 29.82 A = 83.99 A APPLY DEMAND FACTOR = 24.6 x 125% APPLY DEMAND FACTOR = 83.99 = 30.75 A APPLY DEMAND FACTOR 125% = 29.82 x x 125% -37.28 A = 104.99 A 1 PANEL BOARD MANAGEMENT From the lighting and power plans (estimated from the example images): Ground Floor 1. Ceiling Lights: 4 fixtures 。 Assumed Wattage (each): 10 W (LED) 。 Total: 2. Wall Lamps: 3 fixtures 。 Assumed Wattage (each): 15 W (LED) 。 Total: 3. Convenience Outlets: 6 outlets 。 Assumed Wattage (each): 180 W 。 Total: 4. Refrigerator Outlet: 1 outlet 。 Assumed Wattage: 150 W ° Total: 5. Range Outlet: 1 outlet 。 Assumed Wattage: 1000 W 。 Total: Ground Floor Total Load (Watts): ☑ 40+45 + 1080 + 150 + 1000 = 2315 \text{ W} \ Second Floor 1. Ceiling Lights: 5 fixtures 。 Assumed Wattage (each): 10 W 。 Total: 2. Wall Lamps: 2 fixtures 。 Assumed Wattage (each): 15 W ° Total: 3. Convenience Outlets: 4 outlets 。 Assumed Wattage (each): 180 W ° Total: Second Floor Total Load (Watts): ☑ 50+30 720 = 800 \text{ W} } Third Floor 1. Ceiling Lights: 3 fixtures 。 Assumed Wattage (each): 10 W 。 Total: 2. Wall Lamp: 1 fixture 。 Assumed Wattage: 15 W 。 Total: 3. Convenience Outlets: 2 outlets 。 Assumed Wattage (each): 180 W 。 Total: 4. Waterproof Outlet (e.g., balcony/ garden): 1 outlet 。 Assumed Wattage: 100 W 。 Total: Third Floor Total Load (Watts): ☑ 30+15+ 360 + 100 = 505 \text{ W} 2. Convert Wattage to Amperage Using the formula: . • = Current in amperes = Power in watts = Voltage (assume 220 V) Per Floor Current 1. Ground Floor Current 1. Second Floor Current 1. Third Floor Current 1. Total Connected Current (Amperes) 1. Demand Factor Residential circuits often use a demand factor of around 80% to account for the fact that not all loads run simultaneously at full capacity. 4. Breaker Sizing per Floor When grouping circuits, ensure that each breaker is loaded to no more than 80% of its rating to avoid nuisance tripping. Ground Floor • Load: 10.52 A • A 15A breaker is suitable. At 80% loading, a 15A breaker can handle about 12A. Since 10.52A < 12A, it's within the safe limit. Second Floor • Load: 3.64 A • This is a relatively small load. A 10A breaker or 15A breaker would be sufficient. Typically, you might combine small circuits or leave them on a separate breaker if code or design preferences require separation. Third Floor • Load: 2.30 A • Similarly small load. A 10A breaker would be sufficient. 5. Main Breaker and Feeder Sizing 1. Main Breaker 。 Calculated demand load is ~13.17A. 。 A 20A main breaker is a practical choice, giving a safe margin above 13.17A and leaving room for minor future expansions. 2. Feeder Cable 。 Must safely carry the main breaker rating (20A). • Common practice: ► 2.5 mm² copper for up to 20A over moderate distances. ▸ 4.0 mm² copper if the distance is long or if local codes require a larger gauge for voltage drop or future-proofing. 6. Example Panel Board Schedule Below is a simplified example of how you might arrange the panel board: Circui Descr Break Estim Rema t No. iption er 1 Grou nd Floor ated rks Size Load (A) 15A 10.52 Keep withi n Light 80% of S/ Outle ts 15A 2 Seco 10A 3.64 Could nd comb Floor Light ine with S/ Third Outle Floor ts if desir ed 3 Third Floor 10A 2.30 Low load Light S/ Outle ts Main Break er 20A 13.17 Cover (dem S and) total dema nd load Note: In many real projects, you might have separate circuits for heavy loads. (e.g., dedicated range circuit, air conditioning units, etc.), or more granular lighting/outlet circuits to comply with local electrical codes. 7. Key Points and Explanation 1. Why Apply a Demand Factor? In residential design, it's rare that all lights and appliances operate simultaneously at peak. Thus, a demand factor (often 70-80% for typical residences) is applied to avoid oversizing. 2. Why Keep Each Breaker at 80% Loading? Circuit breakers are designed to handle their full rated current, but continuous loads (running over 3 hours) must not exceed 80% of the breaker rating per most electrical codes (e.g., NEC in the US). This ensures safety and reliability. 3. Breaker Sizing vs. Wire Sizing 。 Breaker rating protects the circuit wire from overheating. 。 Wire gauge is chosen to match or exceed the breaker rating. 。 If you have long wire runs, you may upsize to reduce voltage drop. 4. Local Code Requirements Always cross-check with your local electrical code (NEC, IEC, PEC, etc.) for exact rules on circuit loading, branch circuit grouping, wire sizing, grounding, GFCI/AFCI requirements, and breaker selection. Final Summary 1. Total Estimated Load: ~3620 W (16.46 A at 220V). 2. After 80% Demand Factor: ~13.17 A. 3. Recommended Main Breaker: 20A. 4. Branch Circuits: • Ground Floor: 15A breaker (~10.5A load) • Second Floor: 10A breaker (~3.6A load) o Third Floor: 10A breaker (~2.3A load)
Chapter33: Residential Utility-interactive Photovoltaic Systems
Section: Chapter Questions
Problem 6R: To size conductors and overcurrent devices for source circuits, you must multiply the module string...
Related questions
Question
Can you draw the computed panel board (2nd attached pic) like the panel board management (1st attached pic)?
ps. not graded, i just want to know what it looks like when it draw.

Transcribed Image Text:SINGLE LINE DIAGRAM
M
2-80mm2 THHN/THWN CU. WIRE
1-22mm² TW (GRD WIRE)
IN 54mm RSC
PB-1
PB-2
125AT, 2P, 230V
GOAT
M
PB1
PB2
ΤΟ
ELECTRIC
METER
2-8.0 mm², THHN
GROUND FLOOR
MAIN PANEL
BOARD
MAIN BREAKER
125 AT CB, 2 POLE
30 SQ MM
54 MM
CU THHN
PVC CONDUIT
TO
MAIN PANEL
BOARD
8.0 mm², THHN
SECOND FLOOR
PANEL BOARD-1
MAIN BREAKER
60 AT CB, 2 POLE
8 SQ MM CU THHN
PVC CONDUIT
25 MM
LAUNDRY WP
KITCHEN WP
REFRIGERATOR
CD
15 AMP 20 AMP
MASTER BEDROOM
20 AMP 20 AMP
MARPORT WE
TMTWP
TO
MAIN PANEL
BOARD
18.0 mm, THHN
THIRD FLOOR
PANEL BOARD - 2
MAIN BREAKER
60 AT CB, 2 POLE
8 SQ MM
25 MM
CU THHN
PVC CONDUIT
MASTER TAB WP
MASTER TAB 2WP
MASTER BEDROома
20 AMP 20 AMP
TMB2W.P
TAB 3 WP
LIVING AREA
LOUNGE AREA
15 AMP 15 AMP
TV CABLE S
KITCHEN LO
TABLO
BEDROOM 1
20 AMP 20 AMP
BEDROOM 2
ACU
20 AMP 20 AMP
ACU
TV CABLE SET
DINING AREA LO
FRONTYARD L
MASTER BEDROOM
CARPORT LO
15 AMP 60 AMP
SECOND FLOOR
20 AMP 15 AMP
STAIRS LO
MASTERAR LLO
MASTER TABLO
BEDROOM1CO
LIVING AREALD
THIRD FLOOR
2-80mm² THHN CU. WIRE
1-22mm² TW Cu. WIRE (G)
IN 54mm RSC
125AT, 2P, 230V
PANEL BOARD!
GOAT
PANEL BOARD 2
SPARE
MASTER BEDROOM 2
BEDROOM CO
20 AMP 15 AMP
STAIRS LO
MASTERE
MASTER TABLO
TABLO
OUTDOOR CRING
AMP
SPARE
BALCONY 1 LO
BEDROOM L
15 AMP
AMP
SPARE
LOUNGE AREA IL
BALCONY 1 LO
BEDROOM LO
LOUNGE AREA 1L
15 AMP 15 AMP
LO
TOTAL AMPERES = 91.99 A
IP (91.99 x 100%)+(25% x 8) -93.99 A
FEEDER CURRENT = 93.99 x 125% = 117.49 A
FOR OVERCURRENT DEVICE
TOTAL AMPERES = 32.6 A
IP (32.6 x 100%)+(25% x 8) = 34.6 A
FEEDER CURRENT - 34.6 x 125% 43.25 A
FOR OVERCURRENT DEVICE
HIGHEST CIRCUIT BREAKER RATING = 60 A
HIGHEST MOTOR FL CURRENT
SUM OF REMAINING CURRENT
8.00
= 8.00 A
HIGHEST CIRCUIT BREAKER RATING - 20 A
HIGHEST MOTOR FL CURRENT
= 8.00 A
= 91.99 -
SUM OF REMAINING CURRENT
= 32.6-8.00
= 24.6 A
TOTAL AMPERES = 37.82 A
IP = (37.82 x 100% ) + ( 25 % x 8) = 39.82 A
FEEDER CURRENT -39.82 x 125% = 49.78 A
FOR OVERCURRENT DEVICE
HIGHEST CIRCUIT BREAKER RATING
HIGHEST MOTOR FL CURRENT
SUM OF REMAINING CURRENT
20 A
= 8.00 A
= 37.82 - 8.00
- 29.82 A
= 83.99 A
APPLY DEMAND FACTOR
= 24.6 x 125%
APPLY DEMAND FACTOR
= 83.99
= 30.75 A
APPLY DEMAND FACTOR
125%
= 29.82 x
x 125%
-37.28 A
= 104.99 A
1
PANEL BOARD MANAGEMENT

Transcribed Image Text:From the lighting and power plans
(estimated from the example images):
Ground Floor
1. Ceiling Lights: 4 fixtures
。 Assumed Wattage (each): 10 W
(LED)
。 Total:
2. Wall Lamps: 3 fixtures
。 Assumed Wattage (each): 15 W
(LED)
。 Total:
3. Convenience Outlets: 6 outlets
。 Assumed Wattage (each): 180 W
。 Total:
4. Refrigerator Outlet: 1 outlet
。 Assumed Wattage: 150 W
° Total:
5. Range Outlet: 1 outlet
。 Assumed Wattage: 1000 W
。 Total:
Ground Floor Total Load (Watts):
☑
40+45 + 1080 + 150 + 1000 = 2315
\text{ W} \
Second Floor
1. Ceiling Lights: 5 fixtures
。 Assumed Wattage (each): 10 W
。 Total:
2. Wall Lamps: 2 fixtures
。 Assumed Wattage (each): 15 W
° Total:
3. Convenience Outlets: 4 outlets
。 Assumed Wattage (each): 180 W
° Total:
Second Floor Total Load (Watts):
☑
50+30 720 = 800 \text{ W} }
Third Floor
1. Ceiling Lights: 3 fixtures
。 Assumed Wattage (each): 10 W
。 Total:
2. Wall Lamp: 1 fixture
。 Assumed Wattage: 15 W
。 Total:
3. Convenience Outlets: 2 outlets
。 Assumed Wattage (each): 180 W
。 Total:
4. Waterproof Outlet (e.g., balcony/
garden): 1 outlet
。 Assumed Wattage: 100 W
。 Total:
Third Floor Total Load (Watts):
☑
30+15+ 360 + 100 = 505 \text{ W}
2. Convert Wattage to
Amperage
Using the formula:
.
•
= Current in amperes
= Power in watts
= Voltage (assume 220 V)
Per Floor Current
1. Ground Floor Current
1. Second Floor Current
1. Third Floor Current
1. Total Connected Current (Amperes)
1. Demand Factor
Residential circuits often use a
demand factor of around 80% to
account for the fact that not all
loads run simultaneously at full
capacity.
4. Breaker Sizing per Floor
When grouping circuits, ensure that
each breaker is loaded to no more than
80% of its rating to avoid nuisance
tripping.
Ground Floor
• Load: 10.52 A
• A 15A breaker is suitable. At 80%
loading, a 15A breaker can handle
about 12A. Since 10.52A < 12A, it's
within the safe limit.
Second Floor
• Load: 3.64 A
• This is a relatively small load. A 10A
breaker or 15A breaker would be
sufficient. Typically, you might
combine small circuits or leave them
on a separate breaker if code or
design preferences require
separation.
Third Floor
• Load: 2.30 A
•
Similarly small load. A 10A breaker
would be sufficient.
5. Main Breaker and Feeder
Sizing
1. Main Breaker
。 Calculated demand load is
~13.17A.
。 A 20A main breaker is a practical
choice, giving a safe margin
above 13.17A and leaving room
for minor future expansions.
2. Feeder Cable
。 Must safely carry the main
breaker rating (20A).
• Common practice:
► 2.5 mm² copper for up to 20A
over moderate distances.
▸ 4.0 mm² copper if the distance
is long or if local codes require
a larger gauge for voltage drop
or future-proofing.
6. Example Panel Board
Schedule
Below is a simplified example of how
you might arrange the panel board:
Circui Descr Break Estim Rema
t No. iption er
1
Grou
nd
Floor
ated rks
Size Load
(A)
15A 10.52 Keep
withi
n
Light
80%
of
S/
Outle
ts
15A
2
Seco 10A
3.64
Could
nd
comb
Floor
Light
ine
with
S/
Third
Outle
Floor
ts
if
desir
ed
3
Third
Floor
10A 2.30
Low
load
Light
S/
Outle
ts
Main
Break
er
20A
13.17 Cover
(dem S
and)
total
dema
nd
load
Note: In many real projects, you might
have separate circuits for heavy loads.
(e.g., dedicated range circuit, air
conditioning units, etc.), or more
granular lighting/outlet circuits to
comply with local electrical codes.
7. Key Points and Explanation
1. Why Apply a Demand Factor?
In residential design, it's rare that all
lights and appliances operate
simultaneously at peak. Thus, a
demand factor (often 70-80% for
typical residences) is applied to
avoid oversizing.
2. Why Keep Each Breaker at 80%
Loading?
Circuit breakers are designed to
handle their full rated current, but
continuous loads (running over 3
hours) must not exceed 80% of the
breaker rating per most electrical
codes (e.g., NEC in the US). This
ensures safety and reliability.
3. Breaker Sizing vs. Wire Sizing
。 Breaker rating protects the circuit
wire from overheating.
。 Wire gauge is chosen to match or
exceed the breaker rating.
。 If you have long wire runs, you
may upsize to reduce voltage
drop.
4. Local Code Requirements
Always cross-check with your local
electrical code (NEC, IEC, PEC, etc.)
for exact rules on circuit loading,
branch circuit grouping, wire sizing,
grounding, GFCI/AFCI requirements,
and breaker selection.
Final Summary
1. Total Estimated Load: ~3620 W
(16.46 A at 220V).
2. After 80% Demand Factor: ~13.17 A.
3. Recommended Main Breaker: 20A.
4. Branch Circuits:
• Ground Floor: 15A breaker
(~10.5A load)
• Second Floor: 10A breaker (~3.6A
load)
o Third Floor: 10A breaker (~2.3A
load)
Expert Solution

This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 2 steps with 3 images

Recommended textbooks for you

EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:
9781337516549
Author:
Simmons
Publisher:
CENGAGE LEARNING - CONSIGNMENT

Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning

Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning

EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:
9781337516549
Author:
Simmons
Publisher:
CENGAGE LEARNING - CONSIGNMENT

Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning

Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning

Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning