Refrigerant-134a enters the condenser of a residential heat pump at 800 kPa and 35°C at a rate of 0.018 kg/s and leaves at 800 kPa as a saturated liquid. If the compressor consumes 1.2 kW of power, determine (a) the COP of the heat pump and (b) the rate of heat absorption from the outside air.
FIGURE P6–57
(a)
The COP of the heat pump.
Answer to Problem 57P
The COP of the heat pump is
Explanation of Solution
Write the expression for the energy balance equation.
Here, the total energy entering the system is
Simplify Equation (II) and write energy balance relation of refrigrent-134a.
Here, the rate of work to be done into the system is
Substitute
Write the expression for the rate of coefficient performance of a heat pump.
Here the rate of required input of the heat pump is
Conclusion:
Convert the unit of pressure from kPa to MPa.
Refer to Table A-13, “Superheated refrigerant-134a”, obtain the below properties at the superheated pressure and temperature of 800 kPa (0.80 MPa) and 35 C using interpolation method of two variables.
Write the formula of interpolation method of two variables.
Here, the variables denote by x and y are superheated temperature and specific enthalpy.
Show the temperature at 31.31 C and 40 C as in Table (1).
Temperature, C | Specific enthaply, |
Saturated liquid, | |
31.31 C | 267.34 |
35 C | ? |
40 C | 276.46 |
Calculate superheated pressure and temperature of 800 kPa (0.80 MPa) and 35 C for liquid phase using interpolation method.
Substitute 31.31 C for
From above calculation the initial enthalpy of condenser is
Refer to Table A-12, “Saturated pressure table” obtain properties at the superheated pressure and quality of final state of 800 kPa and 0.
Write the expression of final specific enthalpy of a two-phase system for condenser.
Here, the specific enthalpy of condenser is
Substitute
Substitute
Substitute
Thus, the COP of the heat pump is
(b)
The rate of heat absorbed from the outside air.
Answer to Problem 57P
The rate of heat absorbed from the outside air is
Explanation of Solution
Write the expression for the rate of conversation of energy principle for refrigerant 134a.
Here, the rate of heat rejected in the condenser is
Conclusion:
Substitute
Thus, the rate of heat absorbed from the outside air is
Want to see more full solutions like this?
Chapter 6 Solutions
THERMODYNAMICS (LL)-W/ACCESS >CUSTOM<
- A refrigeration system uses a water-cooled condenser for rejecting the waste heat. The system absorbs heat from a space at 25°F at a rate of 21,000 Btu/h. Water enters the condenser at 65°F at a rate of 1.45 lbm/s. The COP of the system is estimated to be 1.9. Determine the maximum possible COP of the system. The specific heat of water is 1.0 Btu/bm·°F.arrow_forwardRefrigerant- 134a enters the condenser of a residential heat pump at 200 kPa and 35°C at a rate of 0.161 kg/s and leaves at 200 kPa as saturated liquid. If the compressor consumes 2.5 kW of power, determine (a) the COP of the heat pump and (b) the rate of heat absorption from outside air COP = 10.657 & QL = 10 998 kW COP = 6346 & QL = 15.758 KW COP = 12.658 & QL = 12.667 kW COP = 15.773 & QL = 36.931 kWarrow_forwardRefrigerant-134a enters the condenser of a residential heat pump at 1400 kPa and 65°C at a rate of 0.062 kgis and leaves at 1400 kPa as saturated liquid. If the compressor consumes 1.6 KW of power, determine (a) the COP of the heat pump and (b) the rate of heat absorption from outside air COP 3.651V& QL 4 465 kW COP 6.356 & QL 8.570 kW COP = 5432 & QL 9.653 kW COP 1.346& QL= 2.784 kWarrow_forward
- Refrigerant 134 A enters in a condenser of a heat pump at 180 kPa and -4 0C and exits with a quality of 0.8 and the same pressure of 180 kPa. The mass flow rate of the refrigerant is 65 kg/h, and the heat pump compressor consumes 45 kJ/min of power. Determine the coefficient of performance of the heat pump. Type your answer in the first box.arrow_forwardAn air conditioner with refrigerant-134a as the refrigerant is used to keep a large space at 20°C by rejecting the waste heat to the outside air at 37 °C. The room is gaining heat through the walls and the windows at a rate of 125 kJ/min while the heat generated by the computer, TV, and lights amounts to 0.7 kW. Unknown amount of heat is also generated by the people in the room. The condenser and evaporator pressures are 1200 and 500 kPa, respectively. The refrigerant is saturated liguid at the condenser exit and saturated vapor at the compressor inlet. If the refrigerant enters the compressor at a rate of 65 L/min and the isentropic efficiency of the compressor is 70%, determine (a) the temperature of the refrigerant at the compressor exit, (b) the rate of heat generated by the people in the room, (c) the COP of the air conditioner, and (d) the minimum volume flow rate of the refrigerant at the compressor inlet for the same compressor inlet and exit conditions.arrow_forwardRefrigerant-134a enters the condenser of a residential heat pump at 800 kPa and 358C at a rate of 0.018 kg/s and leaves at 800 kPa as a saturated liquid. If the compressor consumes 1.2 kW of power, determine (a) the COP of the heat pump and (b) the rate of heat absorption from the outside airarrow_forward
- Steam with quality 0.85 enters the condenser of a power plant at 20 kPa with a mass flow rate 10 kg/s. It is cooled by water from a nearby river by circulating through the tubes inside the condenser. If the steam leaves the condenser as saturated liquid at 20 kPa and the temperature rise of the cooling water is 15°C, (a) determine the minimum mass flow rate of the cooling water required, (b) determine the heat transfer rate from the steam to the cooling water. Hint: Average specific heats at room temperature can be used for the cooling water from river. E Waterarrow_forwardA cooling coil removes a total heat load of 41 kW from a conditioned air. The refrigerating unit uses a 10.8-kW compressor. The ambient air around the cooling tower is at 26.15°C and 40% RH. The inlet temperature of the cooling water to the heat exchanger, which allows heat transfer between the refrigerant and the cooling water, is 20°C. If the mass flow rate of the cooling water is 1 kg/s, determine: The exit temperature of the water as it leaves the heat exchanger in C. The efficiency of the cooling tower in %.arrow_forwardA steam power plant has a high pressure of 2.5 MPa after release from the pump and it maintains 40°C in the condenser. The quality of the stream exiting the turbine is 80%. Solve for the work produced by the turbine and the pump, the heat transfer in the boiler, and heat removed by the condenser. (Answer in kJ/kg)arrow_forward
- The drinking water needs of a production facility with 20 employees are to be met by a bubbler-type water fountain. The refrigerated water fountain is to cool water from 22°C to 8°C and supply cold water at a rate of 0.4 L per hour per person. Heat is transferred to the reservoir from the surroundings at 25°C at a rate of 45 W. If the COP of the refrigeration system is 2.925, determine the size of the compressor, in W, that will be suitable for the refrigeration system of this water cooler. The density and specific heat of water at room temperature are p= 1.0 kg/L and c = 4.18 kJ/kg.°C. (Round the final answer to three decimal places.) Water inlet 22°C 0.4 L/h-person 25°C 8°C Water reservoir Refrigeration Water fountain system The size of the compressor is W.arrow_forwardRefrigerant-134a at a rate of 0.08 kg/s enters the compressor of a refrigerator as superheated vapor at 0.18 MPa and 0 ℃ and leaves at 0.9 MPa and 80 ℃. The refrigerant is cooled in the condenser to 31.3 ℃ and 0.8 MPa and it is throttled to 0.18 MPa. Disregarding any heat transfer and pressure drops in the connecting lines between the components, a) Show the cycle on a T-S diagram b) Determine the rate of heat removal from the refrigerated space and the power input to the compressor c) Determine the adiabatic efficiency of the compressor d) Determine the coefficient of performance of the refrigerator.arrow_forwardA refrigerator using R-134a as the refrigerant is used to keep a space at - 10°C by rejecting heat to ambient air at 22 °C. R-134a enters the compressor at 140 kPa as a saturated vapor and leaves at 800 kPa and 70 °C. The refrigerant leaves the condenser as a saturated liquid. The rate of cooling provided by the system is 2600 W. Determine (a) the mass flow rate of R-134a, (b) the COP, (c) the exergy destruction in each component of the cycle, (d) the second-law efficiency of the cycle, and (e) the total exergy destruction in the cycle.arrow_forward
- Elements Of ElectromagneticsMechanical EngineeringISBN:9780190698614Author:Sadiku, Matthew N. O.Publisher:Oxford University PressMechanics of Materials (10th Edition)Mechanical EngineeringISBN:9780134319650Author:Russell C. HibbelerPublisher:PEARSONThermodynamics: An Engineering ApproachMechanical EngineeringISBN:9781259822674Author:Yunus A. Cengel Dr., Michael A. BolesPublisher:McGraw-Hill Education
- Control Systems EngineeringMechanical EngineeringISBN:9781118170519Author:Norman S. NisePublisher:WILEYMechanics of Materials (MindTap Course List)Mechanical EngineeringISBN:9781337093347Author:Barry J. Goodno, James M. GerePublisher:Cengage LearningEngineering Mechanics: StaticsMechanical EngineeringISBN:9781118807330Author:James L. Meriam, L. G. Kraige, J. N. BoltonPublisher:WILEY