3. The per unit values of positive, negative and zero sequence reactances of a network at fault are 0.08, 0.07 and 0.05 respectively. Determine the fault current if fault is line-to-line-to-ground. [j 16 p.u.]

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter7: Symmetrical Faults
Section: Chapter Questions
Problem 7.2MCQ: Even though the fault current is not symmetrical and not strictly periodic, the rms asymmetrical...
icon
Related questions
Question
3. The per unit values of positive, negative and zero sequence reactances of a network at fault are 0.08, 0.07
and 0.05 respectively. Determine the fault current if fault is line-to-line-to-ground.
[j 16 p.u.]
Transcribed Image Text:3. The per unit values of positive, negative and zero sequence reactances of a network at fault are 0.08, 0.07 and 0.05 respectively. Determine the fault current if fault is line-to-line-to-ground. [j 16 p.u.]