Samples of coarse aggregate from a stockpile are brought to the laboratory for determination of specific gravities. The following weights are found:
Mass of moist aggregate sample as brought to the laboratory: 5,298 g
Mass of oven dried aggregate: 5,216 g
Mass of aggregates submerged in water: 3,295 g
Mass of SSD (Saturated Surface Dry) Aggregate: 5,227 g
Find
a. The aggregate bulk dry specific gravity
b. The aggregate apparent specific gravity
c. The moisture content of stockpile aggregate (report as a percent)
d. Absorption (report as percent)
Trending nowThis is a popular solution!
Learn your wayIncludes step-by-step video
Chapter 5 Solutions
Materials for Civil and Construction Engineers (4th Edition)
Additional Engineering Textbook Solutions
Foundation Design: Principles and Practices (3rd Edition)
Modern Database Management (12th Edition)
Starting out with Visual C# (4th Edition)
Modern Database Management
Absolute Java (6th Edition)
Starting Out with Java: From Control Structures through Objects (6th Edition)
- Coarse aggregate is placed in a rigid bucket and rodded with a tamping rod to determine its unit weight. The following data are obtained: Volume of bucket = 0.3 cuft Weight of empty bucket is 19.8 lb Weight of bucket filled with dry rodded coarse aggregate = 57.6 lb If the bulk dry specific gravity of the aggregate is 2.63 and unit weight of water = to 62.4lb/ft^3, calculate the percent voids in the aggregate (one decimal only). Input magnitude only.arrow_forwardThe mass of aggregate B has been reduced and weighed to conduct an aggregate test shown in Table 2. (a) Calculate the: (i) dry bulk specific gravity (ii) SSD bulk specific gravity,arrow_forwardis 5.10 only as specified by the instructor. Samples of coarse aggregate from a stockpile are brought to the laboratory for determination of specific gravities. The following weights are found: Mass of moist aggregate sample as brought to the laboratory: 5,298 g Mass of oven dried aggregate: 5,216 g dadeab terhib Mass of aggregates submerged in water: 3,295 g Mass of SSD (Saturated Surface Dry) Aggregate: 5,227 g 112 Find a. The aggregate bulk dry specific gravity b. The aggregate apparent specific gravity c. The moisture content of stockpile aggregate (report as a percent) d. Absorption (report as percent)arrow_forward
- Laboratory specific gravity and absorption tests are run on two coarse aggregate sizes, which have to be blended. The results are as follows:Aggregate A: Bulk specific gravity = 2.814; Absorption = 0.4% Aggregate B: Bulk specific gravity = 2.441; Absorption = 5.2% a. What is the specific gravity of a mixture of 50% aggregate A and 50% aggregate B by weight? b. What is the absorption of the mixture?arrow_forwardThe following are the results in the test for specific gravity of fine aggregates:Mass of Oven-dried specimen in air = 502gMass of Pycnometer filled with water, to calibration mark = 640gMass of Saturated Surface Dry Specimen = 510gMass of Pycnometer filled with specimen and water to calibration mark = 950gCalculate the absorption, apparent specific gravity, bulk specific gravity in SSD condition, and bulk specific gravity in OD conditionarrow_forwardThe mass of fine aggregate B has been reduced and weighed to conduct an aggregate test shown in Table 2. (e) Calculate the dry bulk specific gravity, SSD bulk specific gravity, apparent specific gravity, and the aggregate absorption.arrow_forward
- 2.638, 2.514, 2.437 O 2.651, 2.472, 2.364arrow_forwardhelp find a, and barrow_forwardThoroughly mix the aggregate sample and reduce it to an amount suitable for testing, using a sample splitter or by quartering. The minimum sample size should be as follows: Minimum Mass, kg Fine aggregate with at least 95% passing 2.36-mm sieve 0.1 Fine aggregate with at least 85% passing 4.75-mm sieve 0.5 Coarse aggregate with a nominal maximum size of 9.5 mm 1 Coarse aggregate of a nominal maximum size of 12.5 mm 2 Coarse aggregate of a nominal maximum size of 19.0 mm Coarse aggregate of a nominal maximum size of 25.0 mm 10 Coarse aggregate of a nominal maximum size of 37.5 mm 15arrow_forward
- Students in the materials lab performed the specific gravity and absorption test (ASTM C127) on coarse aggregate and they obtained following data: a. Dry weight = 3862.1 g b. SSD weight = 3923.4 g c. Submerged weight = 2452.1 g 1. Calculate the specific gravity values (dry bulk, SSD, and apparent) and the absorption of the coarse aggregate. (Answer in 3 decimal places)arrow_forwardplease quickly thanks !arrow_forwardThe mass of aggregate B has been reduced and weighed to conduct an aggregate test shown in Table 2. (e) Calculate the: (iii)apparent specific gravity, and the (iv) aggregate absorption.arrow_forward
- Structural Analysis (10th Edition)Civil EngineeringISBN:9780134610672Author:Russell C. HibbelerPublisher:PEARSONPrinciples of Foundation Engineering (MindTap Cou...Civil EngineeringISBN:9781337705028Author:Braja M. Das, Nagaratnam SivakuganPublisher:Cengage Learning
- Fundamentals of Structural AnalysisCivil EngineeringISBN:9780073398006Author:Kenneth M. Leet Emeritus, Chia-Ming Uang, Joel LanningPublisher:McGraw-Hill EducationTraffic and Highway EngineeringCivil EngineeringISBN:9781305156241Author:Garber, Nicholas J.Publisher:Cengage Learning