Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X 1 = 0.24 Ω (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio η = N 2 / N 1 = 10 . The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, V a ' η ' as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.
Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X 1 = 0.24 Ω (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio η = N 2 / N 1 = 10 . The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, V a ' η ' as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.
Solution Summary: The author calculates the power factor of a three-phase transformer bank, which is supplying 100MW at 0.8 pf lagging to the bus having voltage 230kV.
Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by
X
1
=
0.24
Ω
(on the low-voltage side), negligible resistance and magnetizing current, and turns ratio
η
=
N
2
/
N
1
=
10
. The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV.
(a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus,
V
a
'
η
'
as the reference Account for the phase shift, and assume positive-sequence operation.
(b) Find the phase shift between the primary and secondary voltages.
Consider a fixed and updated instrumentation amplifier (where two resistors are lumped into one
resistor), analyze the circuit if a common voltage source (VICM) is connected to two inputs.
A₁
R₂
+
R₁
R₂,
RA
www
www
R₁
R₁
www
A3
X
R₁
R₂
www
www
R₁₂
+
Vo
RA
A2
V2 O-
+
R₂
12
R₁
Show that the input impedance of a lossy transmission line of length L connected to a load
impedance of Z is given by
Z₁Cosh(yL) + ZoSinh(yL)
Zin = Zo ZoCosh(YL) + Z₁Sihh(YL)
ex
Where Cosh(x) =
and Sinh(x) =
are the hyperbolic cosine and sine, respectively.
2
2
A sinusoidal source of V = 10 and Z = 50 - j40 is connected to a 60 lossless
transmission line of length 100 m with ẞ = 0.25. What is the Thevenin's equivalent of this
system seen looking into the load end of the transmission line?
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.