Steel Design (Activate Learning with these NEW titles from Engineering!)
6th Edition
ISBN: 9781337094740
Author: Segui, William T.
Publisher: Cengage Learning
expand_more
expand_more
format_list_bulleted
Concept explainers
Question
Chapter 9, Problem 9.3.2P
To determine
(a)
To check:
If, the beam satisfies the provisions of AISC or not.
To determine
(b)
To check:
Whether the beam satisfies the provisions of AISC or not.
Expert Solution & Answer
Want to see the full answer?
Check out a sample textbook solutionStudents have asked these similar questions
A composite floor system uses formed steel deck of the type shown in Figure . The beams are W18 x 50, and the slab has a total thickness of 41⁄2 inches from top of slab to bottom of deck. The effective slab width is 90 inches, and the span length is 30 feet. The structural steel is A992, and the concrete strength is f,c= 4 ksi. Compute the nominal flexural strength with two 3⁄4-inch 3 31⁄2-inch studs per rib.
A fully composite section that is comprised of an A992 W16x31 with a 5-inch, (f'c= 4 ksi) slab on top of it. The beam span is 30' and the spacing of the beams is 5-foot. All the shear studs to make the composite beam were completely forgotten to be installed by the contractor. Assume that the friction between the slab and the steel beam is enough to provide continuous lateral support to the compression flange of the steel beam but provides no composite action between the concrete and the steel. What is the LRFD moment capacity (4bMn) of this badly built attempt at a 'composite' beam, Hint; The flexural strength of the unreinforced concrete slab is 7.5*(f'c)^0.5 Also, the fundamental flexural equation is MC/I. Show all work.
3. A floor structure with a live load of 7 kPa has been designed to be a Canam P3615 composite slab 0.76
thick deck with a slab thickness of 115mm. The span of the deck slab is 2325mm. The floor finish is 50
mm terrazzo. The floor also supports a tiled ceiling & suspension system as well as an allowance for
ducts/pipes/ and wiring and sprayed on fire protection. Check if the composite slab meets Ultimate Limit
State and Serviceability Limit State. The deflection limitation is L/300.
16
Chapter 9 Solutions
Steel Design (Activate Learning with these NEW titles from Engineering!)
Ch. 9 - Prob. 9.1.1PCh. 9 - Prob. 9.1.2PCh. 9 - Prob. 9.1.3PCh. 9 - Prob. 9.1.4PCh. 9 - Prob. 9.1.5PCh. 9 - Prob. 9.1.6PCh. 9 - A W1422 acts compositely with a 4-inch-thick floor...Ch. 9 - Prob. 9.2.2PCh. 9 - Prob. 9.3.1PCh. 9 - Prob. 9.3.2P
Ch. 9 - Prob. 9.4.1PCh. 9 - Prob. 9.4.2PCh. 9 - Prob. 9.4.3PCh. 9 - Prob. 9.4.4PCh. 9 - Prob. 9.4.5PCh. 9 - Prob. 9.5.1PCh. 9 - Prob. 9.5.2PCh. 9 - Prob. 9.5.3PCh. 9 - Note For Problems 9.6-1 through 9.6-5, use the...Ch. 9 - Note For Problems 9.6-1 through 9.6-5, use the...Ch. 9 - Note For Problems 9.6-1 through 9.6-5, use the...Ch. 9 - Note For Problems 9.6-1 through 9.6-5, use the...Ch. 9 - Note For Problems 9.6-1 through 9.6-5, use the...Ch. 9 - Prob. 9.7.1PCh. 9 - Prob. 9.7.2PCh. 9 - Prob. 9.7.3PCh. 9 - Prob. 9.7.4PCh. 9 - Prob. 9.8.1PCh. 9 - Prob. 9.8.2PCh. 9 - A beam must be designed to the following...Ch. 9 - Prob. 9.8.4PCh. 9 - Prob. 9.8.5PCh. 9 - Prob. 9.8.6PCh. 9 - Prob. 9.8.7PCh. 9 - Prob. 9.8.8PCh. 9 - Use the composite beam tables and select a W-shape...Ch. 9 - Prob. 9.8.10PCh. 9 - Prob. 9.10.1PCh. 9 - Prob. 9.10.2P
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, civil-engineering and related others by exploring similar questions and additional content below.Similar questions
- 2. Determine if the composite beam pictured below is adequate for this application (this includes bending, shear, deflection and shear stud limit states). The dead load for this beam is 10 psf plus the weight of the deck, which is made from normal weight concrete. I 5" 5" Normal weight slab fc=4000 psi W24x94 Span length = 30' Service Live Load = 100 psf 3/4" Diameter Shear Connectors 8' o.c. typical Fu=60 ksi (shear connectors)arrow_forwardB) For reinforced concrete lining, the transverse reinforcement is two times the longitudinal reinforcement.O FalseO Truearrow_forwardAs a design engineer you are asked to peer review the design done by another engineer at your organization. A typical reinforced concrete floor slab plan is given. Assume all members to be simply supported. The specified compressive strength of concrete is 5000 psi and Grade-60 steel is used. Unit weight of concrete can be assumed as 150 lb/ft³. B 30'-0"- B2 -EQ.- EQ. -EQ. SEC 1 -40'-0" IS B1 B3 B3 B1 2 The only dead load acting on the slab is the self-weight of the members. The live load on the slab is 100 psf. Initial cross-section and reinforcement details of beam B1 is shown. Area of steel is 4.8in². EQ. 40'-0" B EQ. Northarrow_forward
- Determine the LRFD moment capacity (φbMn) of a composite section that is comprised of a W30x99 with a 5-inch, (f’c = 4 ksi) slab on top of it. The beam span is 30-ft and the spacing of the beams is 8-ft. Show all work. Determine how many 3/4-inch shear studs would be required to ensure that this section is fully composite. Refer the figure below for the general cross-section.arrow_forward= 1. The beam shown is interior exposure and is reinforced with 4-#8 Grade 60 bars. 11" cover over #3 stirrup, also fy = 60 ksi in the region of the beam where the #8 bars are developed, these stirrups are at 6" centers. f = 4.5 ksi, lightweight concrete, no fct splitting tensile strength is given. #8 bars are epoxy coated. (1) Find the value for Ktr using ACI 318-22 Equation (25.4.2.4b) (2) Find la using ACI 318-22 Equation (25.4.2.4a) 4-#8 GR 60 16 in. #3 stirrup at 6" on center 24 inarrow_forwardA W1422 acts compositely with a 4-inch-thick floor slab whose effective width b is 90 inches. The beams are spaced at 7 feet 6 inches, and the span length is 30 feet. The superimposed loads are as follows: construction load = 20 psf, partition load = 10 psf, weight of ceiling and light fixtures = 5 psf, and live load = 60 psf, A992 steel is used, and fc=4 ksi. Determine whether the flexural strength is adequate. a. Use LRFD. b. Use ASD.arrow_forward
- Note For Problems 9.6-1 through 9.6-5, use the lower-bound moment of inertia for deflection of the composite section. Compute this as illustrated in Example 9.7. 9.6-5 For the beam of Problem 9.4-2. a. Compute the deflections that occur before and after the concrete has cured. b. It the live toad deflection exceeds L360 , select another steel shape using either LRFD or ASD.arrow_forwardGiven the section and plan view of the structural elements (Foundation and Column), estimate the concrete material quantities to be used in construction. There are sixteen (16) - C3F2 in the entire structure. Consider only from the foundation base up to the Natural Ground Level (NGL). The concrete is to have a minimum compressive strength of 3500 psi (24 Mpa).arrow_forwardThe 5-story building design project will have its beams and slab poured monolithically and formed a T- section as shown. Determine the design strength oMn in accordance with the ACI/NSCP Code. The tension steel is 9- 36 mm diameter bars (As of 36 mm = 1006 mm2) with three bars in each of three layers. Assume 12 mm stirrups are used, and there is 25 mm between layers. Use fc' = 28 MPa and fy = 413.70 MPa. 750 mm T175 mm 1000 mm 9-36 mm dibmeter bars 350 mm doooarrow_forward
- 4. An interior reinforced concrete slab has to be designed to support a live load and a dead load in addition to its own weight based on the following specifications: The slab is one-way and simply supported with a span of 12 ft. The live load on the slab is 200 psf. The dead load on the slab is 100 psf. Your design will use concrete compressive strength fe= 3000 psi and steel yield strength of fy = 40,000 psiarrow_forwardGiven: A fully composite slab is connected to a W24x68 made with the manufacturer preferred material. Concrete is specified to be 3.5 ksi concreteand the slab is 4 inches thick. The effective width of this portion of the slab is 84 inches. Find: The nominal and design strength of the section for the fully plastic condition.arrow_forwardQ2: Design a typical interior flat slab panel 18x15ft as shown in the figure rested on squared columns of 21x21 in. The slab total thickness is 14in. to support dead load of 32 psf in addition to the self-weight of the slab and live load of 110 psf. The concrete has a unit weight of 132 pcf and a specified compressive strength of 4ksi, and yield strength for steel is 60ksi. Use steel No.5 as reinforcement. 21x21in. column 15ft Interior Panel/flat slab 18ft *arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Steel Design (Activate Learning with these NEW ti...Civil EngineeringISBN:9781337094740Author:Segui, William T.Publisher:Cengage Learning
Steel Design (Activate Learning with these NEW ti...
Civil Engineering
ISBN:9781337094740
Author:Segui, William T.
Publisher:Cengage Learning