Consider a two-stage cascade refrigeration cycle with a flash chamber as shown in the figure with refrigerant-134a as the working fluid. The evaporator temperature is −10°C and the condenser pressure is 1600 kPa. The refrigerant leaves the condenser as a saturated liquid and is throttled to a flash chamber operating at 0.45 MPa. Part of the refrigerant evaporates during this flashing process, and this vapor is mixed with the refrigerant leaving the low-pressure compressor. The mixture is then compressed to the condenser pressure by the high-pressure compressor. The liquid in the flash chamber is throttled to the evaporator pressure and cools the refrigerated space as it vaporizes in the evaporator. The mass flow rate of the refrigerant through the low-pressure compressor is 0.11 kg/s. Assuming the refrigerant leaves the evaporator as a saturated vapor and the isentropic efficiency is 86 percent for both compressors, determine (a) the mass flow rate of the refrigerant through the high-pressure compressor, (b) the rate of refrigeration supplied by the system, and (c) the COP of this refrigerator. Also, determine (d) the rate of refrigeration and the COP if this refrigerator operated on a single-stage vapor-compression cycle between the same evaporating temperature and condenser pressure with the same compressor efficiency and the same flow rate as calculated in part a.
FIGURE P11–65
(a)
The mass flow rate of the refrigerant through the high-pressure compressor.
Answer to Problem 65P
The mass flow rate of the refrigerant through the high-pressure compressor is
Explanation of Solution
Show the T-s diagram as in Figure (1).
From Figure (1), write the specific enthalpy at state 6 is equal to state 5 due to throttling process.
Here, specific enthalpy at state 6 and 5 is
From Figure (1), write the specific enthalpy at state 8 is equal to state 7 due to throttling process.
Here, specific enthalpy at state 8 and 7 is
Express enthalpy at state 1.
Here, enthalpy saturation vapor at temperature of
Express entropy at state 1.
Here, entropy saturation vapor at temperature of
Express the specific enthalpy at state 2.
Here, specific enthalpy at state 2s is
Express enthalpy at state 3.
Here, enthalpy saturation vapor at pressure of
Express enthalpy at state 5.
Here, enthalpy saturation liquid at pressure of
Express enthalpy at state 7.
Here, enthalpy saturation liquid at pressure of
Express the quality at state 6.
Express the mass flow rate of the refrigerant.
Here, mass flow rate at state 7 is
Conclusion:
Refer Table A-11, “saturated refrigerant-134a-temperature table”, and write enthalpy saturation vapor at temperature of
Substitute
Refer Table A-11, “saturated refrigerant-134a-temperature table”, and write entropy saturation vapor at temperature of
Substitute
Perform the unit conversion of pressure at state 2 from
Refer Table A-13, “superheated refrigerant 134a”, and write the specific enthalpy at state 2s corresponding to pressure at state 2 of
Here, enthalpy at state 2s is
Substitute
Refer Table A-12, “saturated refrigerant-134a-pressure table”, and write the enthalpy saturation vapor at pressure of
Substitute
Refer Table A-12, “saturated refrigerant-134a-pressure table”, and write the enthalpy saturation liquid at pressure of
Substitute
Substitute
Refer Table A-12, “saturated refrigerant-134a-pressure table”, and write the enthalpy saturation liquid at pressure of
Substitute
Substitute
Substitute
Substitute
Hence, the mass flow rate of the refrigerant through the high-pressure compressor is
(b)
The rate of refrigeration supplied by the system.
Answer to Problem 65P
The rate of refrigeration supplied by the system is
Explanation of Solution
Express the mass flow rate at state 3.
Express the enthalpy at state 9.
Express the enthalpy at state 4.
Here, specific enthalpy at state 4s is
Express the rate of heat removal from the refrigerated space.
Conclusion:
Substitute
Substitute
Refer Table A-13, “superheated refrigerant 134a”, and write the specific enthalpy at state 9 corresponding to pressure at state 9 of
Here, entropy at state 9 is
Refer Table A-13, “superheated refrigerant 134a”, and write the specific enthalpy at state 4s corresponding to pressure at state 4 of
Write the formula of interpolation method of two variables.
Here, the variables denote by x and y is specific entropy at state 9 and specific enthalpy at state 4s respectively.
Show the specific enthalpy at state 4s corresponding to specific entropy as in Table (1).
Specific entropy at state 9 |
Specific enthalpy at state 4s |
0.9164 | 280.71 |
0.9399 | |
0.9536 | 293.27 |
Substitute
Thus, the specific enthalpy at state 4s is,
Substitute
Substitute
Hence, the rate of refrigeration supplied by the system is
(c)
The COP of the refrigerator.
Answer to Problem 65P
The COP of the refrigerator is
Explanation of Solution
Express the power input.
Express the coefficient of performance.
Conclusion:
Substitute
Substitute
Hence, the coefficient of performance of the refrigerator is
(d)
The rate of refrigeration and the COP of the refrigerator.
Answer to Problem 65P
The rate of refrigeration is
Explanation of Solution
Show the T-s diagram as in Figure (1).
From Figure (1), write the specific enthalpy at state 4 is equal to state 3 due to throttling process.
Here, specific enthalpy at state 4 and 3 is
Express the enthalpy at state 2.
Here, specific enthalpy at state 2s is
Express enthalpy at state 3.
Here, enthalpy saturation vapor at pressure of
Express the rate of refrigeration.
Express the rate of work input.
Express the coefficient of performance.
Conclusion:
Refer Table A-13, “superheated refrigerant 134a”, and write the specific enthalpy at state 2s corresponding to pressure at state 2 of
Show the specific enthalpy at state 2s corresponding to specific entropy as in Table (2).
Specific entropy at state 2 |
Specific enthalpy at state 2s |
0.9164 | 280.71 |
0.9378 | |
0.9536 | 293.27 |
Use excels and tabulates the values from Table (2) in Equation (XV) to get,
Thus, the specific enthalpy at state 2s is,
Substitute
Refer Table A-12, “saturated refrigerant-134a-pressure table”, and write the enthalpy saturation liquid at pressure of
Substitute
Substitute
Substitute
Hence, the rate of refrigeration is
Substitute
Substitute
Hence, the coefficient of performance of the refrigerator is
Want to see more full solutions like this?
Chapter 11 Solutions
Thermodynamics: An Engineering Approach ( 9th International Edition ) ISBN:9781260092684
- When a standard-efficiency air-cooled condenser is used, the condensing refrigerant will normally be higher in temperature than the entering air temperature.arrow_forwardCondensers in these refrigerators are all_______cooled.arrow_forwardWhat are the approximate temperature ranges tor low-, medium-, and high-temperature refrigeration applications?arrow_forward
- A two-stage compression refrigeration system with an adiabatic liquid-vapor separation unit like that in the figure uses refrigerant-134a as the working fluid. The system operates the evaporator at 100 psia the condenser at 300 psia, and the separator at 200 psia. The compressors use 29 kW of power. Determine the rate of cooling provided by the evaporator and the COP of this cycle. The refrigerant is a saturated liquid at the inlet of each expansion valve and a saturated vapor at the inlet of each compressor, and the compressors are isentropic. (Take the required values from saturated refrigerant-134a tables.) 2 Compressor Compressor (8) m6 Condenser Separator The rate of cooling provided by the evaporator is 5 ↓ Evaporator Btu/h, and the COP of the refrigerator isarrow_forwardA two-stage compression refrigeration system operates with refrigerant-134a between the pressure limits of 1.4 MPa and 0.10 MPa. The refrigerant leaves the condenser as a saturated liquid and is throttled to a flash chamber operating at 0.6 MPa. he flash chamber is maintained at the same pressure as the low pressure discharge which is 0.6 Mpa. The vapor in the flash chamber is then compressed to the condenser pressure by the high-pressure compressor, and the liquid is throttled to the evaporator pressure. Assume the refrigerant leaves the evaporator as saturated vapor and both compressors are isentropic. Consider a mass flow rate of 0.19 kg/s through the condenser. (Take the required values from saturated refrigerant-134a tables.) Determine the fraction of the refrigerant that evaporates as it is throttled to the flash chamber. (You must provide an answer before moving to the next part.) The fraction of the refrigerant that evaporates as it is throttled to the flash chamber is…arrow_forwardA two-stage compression refrigeration system operates with refrigerant-134a between the pressure limits of 1.4 MPa and 0.10 MPa. The refrigerant leaves the condenser as a saturated liquid and is throttled to a flash chamber operating at 0.6 MPa. he flash chamber is maintained at the same pressure as the low pressure discharge which is 0.6 Mpa. The vapor in the flash chamber is then compressed to the condenser pressure by the high-pressure compressor, and the liquid is throttled to the evaporator pressure. Assume the refrigerant leaves the evaporator as saturated vapor and both compressors are isentropic. Consider a mass flow rate of 0.19 kg/s through the condenser. (Take the required values from saturated refrigerant-134a tables.) Determine the coefficient of performance. The coefficient of performance is ______.arrow_forward
- Consider a two-stage compression refrigeration system operating between the pressure limits of 0.8 and 0.14 MPa(see Fig. Q 2). The working fluid is refrigerant -134a . The refrigerant leaves the condenser as a saturated liquid and is throttled to a flash chamber operating at 0.4 MPa. Part of the refrigerant evaporates during this flashing process, and this vapour is mixed with the refrigerant leaving the low-pressure compressor. The mixture is then compressed to the condenser pressure by the high-pressure compressor. The liquid in the flash chamber is throttled to the evaporator pressure,and it cools the refrigerated space as it vaporizes in the evaporator. Assuming the refrigerant leavesthe evaporator as saturated vapor and both compressors are isentropic, determine(a) the fraction of the refrigerant that evaporates as it is throttled to the flash chamber,(b) the amount of heat removed from the refrigerated space and the compressor work per unit massof refrigerant flowing through the…arrow_forwardA vapor compression cycle with R-134a is being used as its refrigerant. The refrigerant leaves the evaporator at -10 C and 120 kPa and it enters the condenser 1.0 MPa. Assuming there is a heat loss due to compression which is equal to 20 kJ/kg, and it has a cooling capacity of 75 tons of refrigeration, Determine the following: (a)heat rejected (b)cooling effect (c)work of compression (d) coefficient of performance (e)volume flow rate of refrigerant (f)compressor discharge temperaturearrow_forwardA vapor-compression refrigeration system uses R-134a. The evaporator pressure is 200.60 kPa and a condenser pressure of 770.20 kPa. The refrigerant enters the compressor as a saturated vapor and leaves the condenser as subcooled liquid at 20°C (there is subcooling from Tsatn to 20°C). Calculate the following: (a) The flowrate of R-134a in kg/s, if the refrigeration capacity is 35.5 kw (b) Work requirement in the compressor in kl/kg, if the compressor efficiency is 0.80 (c) COP of the refrigeration cycle. (d) Provide the P-H diagram of the cycle.arrow_forward
- Consider a two-stage compression refrigeration system operating between the pressure limits of 0.8 and 0.14 MPa. The working fluid is refrigerant-134a. The refrigerant leaves the condenser as a saturated liquid and is throttled to a flash chamber operating at 0.4 MPa. Part of the refrigerant evaporates during this flashing process, and this vapor is mixed with the refrigerant leaving the low-pressure compressor. The mixture is then compressed to the condenser pressure by the high-pressure compressor. The liquid in the flash chamber is throttled to the evaporator pressure, and it cools the refrigerated space as it vaporizes in the evaporator. Assuming the refrigerant leaves the evaporator as saturated vapor and both compressors are isentropic, determine (a)the fraction of the refrigerant that evaporates as it is throttled to the flash chamber, (b)the amount of heat removed from the refrigerated space and the compressor work per unit mass of refrigerant flowing through the condenser,…arrow_forwardA Carnot vapor refrigeration cycle uses R-134a as the working fluid. The refrigerarit enters the condenser as saturated vapor at 28°C and leaves as saturated liquid. The evaporator operates at a temperature of -10°C. For every kg of refrigerant flow, calculate the work of compression, kJarrow_forwardA steady-flow Carnot refrigeration cycle uses R-134a as the working fluid. The refrigerant changes from saturated vapor to saturated liquid at 36°C in the condenser as it rejects heat. The evaporator pressure is 200 kPa. For every kg of refrigerant, calculate the amount of heat removed from the refrigerated spacearrow_forward
- Refrigeration and Air Conditioning Technology (Mi...Mechanical EngineeringISBN:9781305578296Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill JohnsonPublisher:Cengage Learning