Zone 1 Zone 2 T1 T2 Line 1 100MVA Yz Y+ Yz Yz ww Vrated 20kV G Z+=30+j95 ohms X"X" 20.0% X"0 = 6.0% ZO 80+j225 ohms 125MVA 75 MVA 20kV/230kV %IX = 7.0 230kV/44kV %IX = 6.0 Zone 3 Line 2 ww Z+22+ j57 ohms ZO 66+j205 ohms

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
Question

Assume that for Line 1 and Line 2, Z- = Z+.

Assume that for T1 & T2, Z+ = Z- = Z0 = specified value.

Use an Sbase value of 100MVA. Use the transformer rated nameplate voltages as the base voltage in each zone.

Assume that the generator is operating at 19.0kV∠0.

 

Answer using digits only, e.g. 20,000, not 20kV. Do not include units. Do not include "j" for imaginary values.

 

 

  1. What is the adjusted per unit negative sequence impedance of T1 ?

     
    Integer, decimal, or E notation allowed

    Question 2

    What is the magnitude of the zero sequence per unit impedance of Line 1 ?

     
     
    Integer, decimal, or E notation allowed

    Question 3

    What is the adjusted positive sequence per unit impedance of T2 ?

     
    Integer, decimal, or E notation allowed

    Question 4

    What is the magnitude of the negative sequence per unit impedance of Line 2 ?

    Integer, decimal, or E notation allowed

    Question 5

    What is the magnitude of the power system fault current at the generator for a three phase fault at the end of Line 2 ?
     
    Integer, decimal, or E notation allowed

    Question 6

    What is the magnitude of the power system fault current at the point of the fault for a three phase fault at the end of Line 2 ?

    Integer, decimal, or E notation allowed

    Question 7

    What is the magnitude of the power system current at the point of the fault for a line to ground fault at the high voltage terminal of T2 ?
     
    Integer, decimal, or E notation allowed

    Question 8

    What is the magnitude of the power system B phase current at the point of the fault for a B phase to C phase fault at the HV terminal of T

 

 

Zone 1
Zone 2
T1
T2
Line 1
100MVA
Yz
Y+
Yz
Yz
ww
Vrated 20kV
G
Z+=30+j95 ohms
X"X" 20.0%
X"0 = 6.0%
ZO 80+j225 ohms
125MVA
75 MVA
20kV/230kV
%IX = 7.0
230kV/44kV
%IX = 6.0
Zone 3
Line 2
ww
Z+22+ j57 ohms
ZO 66+j205 ohms
Transcribed Image Text:Zone 1 Zone 2 T1 T2 Line 1 100MVA Yz Y+ Yz Yz ww Vrated 20kV G Z+=30+j95 ohms X"X" 20.0% X"0 = 6.0% ZO 80+j225 ohms 125MVA 75 MVA 20kV/230kV %IX = 7.0 230kV/44kV %IX = 6.0 Zone 3 Line 2 ww Z+22+ j57 ohms ZO 66+j205 ohms
Expert Solution
steps

Step by step

Solved in 2 steps with 6 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,