State the advantages to be gained by raising the power factor of industrial loads. A 400 V, 50 Hz, three-phase motor takes a line current of 15.0 A when operating at a lagging power factor of 0.65. When a capacitor bank is connected across the motor terminals, the line current is reduced to 11.5 A. Calculate the rating (in kVA) and the capa citance per phase of the capacitor bank for: (a) star connection; (b) delta connection. Find also the new overall power factor. ANS:  3.81 kvar, 70.5 µF, 23.5 µF, 0.848 lagging

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.16P: A single-phase, 120V(rms),60Hz source supplies power to a series R-L circuit consisting of R=10 and...
icon
Related questions
Question

State the advantages to be gained by raising the power

factor of industrial loads.

A 400 V, 50 Hz, three-phase motor takes a line

current of 15.0 A when operating at a lagging power

factor of 0.65. When a capacitor bank is connected

across the motor terminals, the line current is reduced

to 11.5 A. Calculate the rating (in kVA) and the capa

citance per phase of the capacitor bank for: (a) star

connection; (b) delta connection. Find also the new

overall power factor.

ANS: 

3.81 kvar, 70.5 µF, 23.5 µF, 0.848 lagging

Expert Solution
steps

Step by step

Solved in 2 steps with 3 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning