A generating station is to supply four regions of load [15MW,10 MW,20MW,3MW]. The diversity factor at the station is 1-6. Calculate: (i) The maximum demand on the station. (ii) Suggest the installed capacity and the number of units. NOT: Taking installed capacity to be 20% more than the maximum demand.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.31P: Consider two interconnected voltage sources connected by a line of impedance Z=jX, as shown in...
Question
A generating station is to supply four regions of load [15MW,10 MW,20MW,3MW].
The diversity factor at the station is 1-6. Calculate:
(i) The maximum demand on the station.
(ii) Suggest the installed capacity and the number of units.
NOT: Taking installed capacity to be 20% more than the maximum demand.
Transcribed Image Text:A generating station is to supply four regions of load [15MW,10 MW,20MW,3MW]. The diversity factor at the station is 1-6. Calculate: (i) The maximum demand on the station. (ii) Suggest the installed capacity and the number of units. NOT: Taking installed capacity to be 20% more than the maximum demand.
Expert Solution
steps

Step by step

Solved in 2 steps with 3 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning