GROUND FLOOR MAIN PANEL BOARD MAIN BREAKER 125 AT CB, 2 POLE 30 SQ MM 54 MM CU THHN PVC CONDUIT REFRIGERATOR CO. 15 AMP 15 AMP LIVING AREA 15 AMP TV CABLE SE 15 AMP FRONTYARD L CARPORT LO 15 AMP 10 AMP LIVING AREAL Q Q O Q SECOND FLOOR PANEL BOARD - 1 MAIN BREAKER 60 AT CB, 2 POLE 8 SQ MM CU THHN 25 MM PVC CONDUIT 2 CARPORT W.P LAUNDRY W.P KITCHEN W.P BEDROOM 1 (4 10 AMP 10 AMP ACU T&B 1W.P STAIRS LO. KITCHEN LO 14) T&B 1LO DINING AREA LO. SECOND FLOOR BEDROOM 2 6 10 AMP 10 AMP ACU MASTER BEDROOM 3 са BEDROOM CO C 10 AMP 10 AMP BALCONY 1 LO THIRD FLOOR 10 AMP AMP SPARE BEDROOM 1L017 10 AMP AMP ENTERTAINMENT ROOM 1 LC Q Q THIRD FLOOR PANEL BOARD - 2 MAIN BREAKER 60 AT CB, 2 POLE 8 SQ MM CU THHN 25 MM PVC CONDUIT W TOP S MASTER T&B 3 W.P 5 BEDROOM 4 9 ACU T&B 2 W.P O ENTERTAINMENT ROOM 1 TV CABLE SET BEDROOM 3 ACU E STAIRS LO. MASTER BR 3L.0. 16 MASTER T&B 3 LO. T&B 2 LO. WATERPROOF OUTLET CONVENIENCE OUTLET SPARE 13 10 AMP 10 AMP P 10 AMP 10 AMP оо ୦ 10 AMP 10 AMP BALCONY 2 LO BEDROOM 3 L. (19 BEDROOM 4L.O. 10 AMP 10 AMP Q о O 10 T&B 4W.P (12) TV CABLE SET O 18 STAIRS LO BR 3 LO. T&B 4 LO. WCS 20 OUTDOOR CELING LO. TOTAL AMPERES = 91.99 A IP = (91.99 x 100% ) + (25% x 8) = 93.99 A FEEDER CURRENT = 93.99 x 125% = 117.49 A FOR OVERCURRENT DEVICE HIGHEST CIRCUIT BREAKER RATING = 60 A HIGHEST MOTOR FL CURRENT = 8.00 A SUM OF REMAINING CURRENT 8.00 TOTAL AMPERES = 32.6 A IP = (32.6 x 100%) + (25% x 8) = 34.6 A FEEDER CURRENT = 34.6 x 125% = 43.25 A FOR OVERCURRENT DEVICE HIGHEST CIRCUIT BREAKER RATING = 20 A HIGHEST MOTOR FL CURRENT = 8.00 A = 91.99 - SUM OF REMAINING CURRENT = 32.6-8.00 = 24.6 A TOTAL AMPERES = 37.82 A IP = (37.82 x 100% ) + ( 25 % x 8) = 39.82 A FEEDER CURRENT = 39.82 x 125 % = 49.78 A FOR OVERCURRENT DEVICE HIGHEST CIRCUIT BREAKER RATING = 20 A HIGHEST MOTOR FL CURRENT SUM OF REMAINING CURRENT = 8.00 A = 37.82 - 8.00 = 29.82 A = 83.99 A APPLY DEMAND FACTOR = 24.6 x 125% APPLY DEMAND FACTOR = 83.99 = 30.75 A APPLY DEMAND FACTOR 125% = 29.82 x X 125% = 37.28 A = 104.99 A
GROUND FLOOR MAIN PANEL BOARD MAIN BREAKER 125 AT CB, 2 POLE 30 SQ MM 54 MM CU THHN PVC CONDUIT REFRIGERATOR CO. 15 AMP 15 AMP LIVING AREA 15 AMP TV CABLE SE 15 AMP FRONTYARD L CARPORT LO 15 AMP 10 AMP LIVING AREAL Q Q O Q SECOND FLOOR PANEL BOARD - 1 MAIN BREAKER 60 AT CB, 2 POLE 8 SQ MM CU THHN 25 MM PVC CONDUIT 2 CARPORT W.P LAUNDRY W.P KITCHEN W.P BEDROOM 1 (4 10 AMP 10 AMP ACU T&B 1W.P STAIRS LO. KITCHEN LO 14) T&B 1LO DINING AREA LO. SECOND FLOOR BEDROOM 2 6 10 AMP 10 AMP ACU MASTER BEDROOM 3 са BEDROOM CO C 10 AMP 10 AMP BALCONY 1 LO THIRD FLOOR 10 AMP AMP SPARE BEDROOM 1L017 10 AMP AMP ENTERTAINMENT ROOM 1 LC Q Q THIRD FLOOR PANEL BOARD - 2 MAIN BREAKER 60 AT CB, 2 POLE 8 SQ MM CU THHN 25 MM PVC CONDUIT W TOP S MASTER T&B 3 W.P 5 BEDROOM 4 9 ACU T&B 2 W.P O ENTERTAINMENT ROOM 1 TV CABLE SET BEDROOM 3 ACU E STAIRS LO. MASTER BR 3L.0. 16 MASTER T&B 3 LO. T&B 2 LO. WATERPROOF OUTLET CONVENIENCE OUTLET SPARE 13 10 AMP 10 AMP P 10 AMP 10 AMP оо ୦ 10 AMP 10 AMP BALCONY 2 LO BEDROOM 3 L. (19 BEDROOM 4L.O. 10 AMP 10 AMP Q о O 10 T&B 4W.P (12) TV CABLE SET O 18 STAIRS LO BR 3 LO. T&B 4 LO. WCS 20 OUTDOOR CELING LO. TOTAL AMPERES = 91.99 A IP = (91.99 x 100% ) + (25% x 8) = 93.99 A FEEDER CURRENT = 93.99 x 125% = 117.49 A FOR OVERCURRENT DEVICE HIGHEST CIRCUIT BREAKER RATING = 60 A HIGHEST MOTOR FL CURRENT = 8.00 A SUM OF REMAINING CURRENT 8.00 TOTAL AMPERES = 32.6 A IP = (32.6 x 100%) + (25% x 8) = 34.6 A FEEDER CURRENT = 34.6 x 125% = 43.25 A FOR OVERCURRENT DEVICE HIGHEST CIRCUIT BREAKER RATING = 20 A HIGHEST MOTOR FL CURRENT = 8.00 A = 91.99 - SUM OF REMAINING CURRENT = 32.6-8.00 = 24.6 A TOTAL AMPERES = 37.82 A IP = (37.82 x 100% ) + ( 25 % x 8) = 39.82 A FEEDER CURRENT = 39.82 x 125 % = 49.78 A FOR OVERCURRENT DEVICE HIGHEST CIRCUIT BREAKER RATING = 20 A HIGHEST MOTOR FL CURRENT SUM OF REMAINING CURRENT = 8.00 A = 37.82 - 8.00 = 29.82 A = 83.99 A APPLY DEMAND FACTOR = 24.6 x 125% APPLY DEMAND FACTOR = 83.99 = 30.75 A APPLY DEMAND FACTOR 125% = 29.82 x X 125% = 37.28 A = 104.99 A
Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter32: Three-phase Motors
Section: Chapter Questions
Problem 8RQ
Related questions
Question
can you compute the values inside the blue circles using the data from the plan above them? Please disregard the values (data/numbers) inside the circles.

Transcribed Image Text:GROUND FLOOR
MAIN PANEL
BOARD
MAIN BREAKER
125 AT CB, 2 POLE
30 SQ MM
54 MM
CU THHN
PVC CONDUIT
REFRIGERATOR
CO.
15 AMP 15 AMP
LIVING AREA
15 AMP
TV CABLE SE
15 AMP
FRONTYARD L
CARPORT LO
15 AMP 10 AMP
LIVING AREAL
Q Q
O
Q
SECOND FLOOR
PANEL BOARD - 1
MAIN BREAKER
60 AT CB, 2 POLE
8 SQ MM CU THHN
25 MM PVC CONDUIT
2 CARPORT W.P
LAUNDRY W.P
KITCHEN W.P
BEDROOM 1
(4
10 AMP 10 AMP
ACU
T&B 1W.P
STAIRS LO.
KITCHEN LO
14) T&B 1LO
DINING AREA LO.
SECOND FLOOR
BEDROOM 2 6
10 AMP 10 AMP
ACU
MASTER BEDROOM 3
са
BEDROOM CO
C
10 AMP
10 AMP
BALCONY 1 LO
THIRD FLOOR
10 AMP
AMP
SPARE
BEDROOM 1L017
10 AMP
AMP
ENTERTAINMENT ROOM 1 LC
Q
Q
THIRD FLOOR
PANEL BOARD - 2
MAIN BREAKER
60 AT CB, 2 POLE
8 SQ MM CU THHN
25 MM
PVC CONDUIT
W
TOP
S
MASTER T&B 3 W.P
5
BEDROOM 4
9
ACU
T&B 2 W.P
O
ENTERTAINMENT ROOM 1
TV CABLE SET
BEDROOM 3
ACU
E
STAIRS LO.
MASTER BR 3L.0.
16 MASTER T&B 3 LO.
T&B 2 LO.
WATERPROOF OUTLET
CONVENIENCE
OUTLET
SPARE
13
10 AMP 10 AMP
P
10 AMP 10 AMP
оо
୦
10 AMP 10 AMP
BALCONY 2 LO
BEDROOM 3 L. (19
BEDROOM 4L.O.
10 AMP 10 AMP
Q
о
O
10 T&B 4W.P
(12) TV CABLE SET
O
18
STAIRS LO
BR 3 LO.
T&B 4 LO.
WCS
20 OUTDOOR CELING
LO.
TOTAL AMPERES = 91.99 A
IP = (91.99 x 100% ) + (25% x 8) = 93.99 A
FEEDER CURRENT = 93.99 x 125% = 117.49 A
FOR OVERCURRENT DEVICE
HIGHEST CIRCUIT BREAKER RATING = 60 A
HIGHEST MOTOR FL CURRENT = 8.00 A
SUM OF REMAINING CURRENT
8.00
TOTAL AMPERES = 32.6 A
IP = (32.6 x 100%) + (25% x 8) = 34.6 A
FEEDER CURRENT = 34.6 x 125% = 43.25 A
FOR OVERCURRENT DEVICE
HIGHEST CIRCUIT BREAKER RATING = 20 A
HIGHEST MOTOR FL CURRENT
= 8.00 A
= 91.99 -
SUM OF REMAINING CURRENT
= 32.6-8.00
= 24.6 A
TOTAL AMPERES = 37.82 A
IP = (37.82 x 100% ) + ( 25 % x 8) = 39.82 A
FEEDER CURRENT = 39.82 x 125 % = 49.78 A
FOR OVERCURRENT DEVICE
HIGHEST CIRCUIT BREAKER RATING = 20 A
HIGHEST MOTOR FL CURRENT
SUM OF REMAINING CURRENT
= 8.00 A
= 37.82 - 8.00
= 29.82 A
= 83.99 A
APPLY DEMAND FACTOR
= 24.6 x 125%
APPLY DEMAND FACTOR
= 83.99
= 30.75 A
APPLY DEMAND FACTOR
125%
= 29.82 x
X 125%
= 37.28 A
= 104.99 A
Expert Solution

This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 2 steps with 7 images

Recommended textbooks for you

Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning

Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning

Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning

Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning