A 15-kVA, 2400/240-V transformer is to be tested to determine its excitation branch components, its series impedances and its voltage regulation. The following test data have been taken from the primary side of the transformer:

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
Subjcct Electrical machine
A 15-kVA, 2400/240-V transformer is to be
tested to determine its excitation branch
components, its series impedances and its
voltage regulation. The following test data
have been taken from the primary side of the
transformer:
Open- circuit test
Short- circuit test
Voc = 2400 V
Vsc = 48 V
loc = 0.25 A
Isc = 6.0 A
Poc = 50 W
Psc = 200 W
су
The data have been taken by using the
connections of open-circuit test and short-
circuit test:
a)Find the
transformer referred to the high-voltage side.
equivalent circuit
of
this
b)Find the
transformer referred to the low-voltage side
equivalent circuit
of
this
c)Calculate the full-load voltage regulation at
0.8 lagging power factor and 0.8 leading
power factor
What is the efficiency of the transformer at
full load with a power factor of 0.8 lagging?
Transcribed Image Text:A 15-kVA, 2400/240-V transformer is to be tested to determine its excitation branch components, its series impedances and its voltage regulation. The following test data have been taken from the primary side of the transformer: Open- circuit test Short- circuit test Voc = 2400 V Vsc = 48 V loc = 0.25 A Isc = 6.0 A Poc = 50 W Psc = 200 W су The data have been taken by using the connections of open-circuit test and short- circuit test: a)Find the transformer referred to the high-voltage side. equivalent circuit of this b)Find the transformer referred to the low-voltage side equivalent circuit of this c)Calculate the full-load voltage regulation at 0.8 lagging power factor and 0.8 leading power factor What is the efficiency of the transformer at full load with a power factor of 0.8 lagging?
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 6 steps with 2 images

Blurred answer
Knowledge Booster
Thermocouple
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,