A generator supplies a motor through a Y-A transformer. The generator is connected to Y side of the transformer. A fault occurs between the motor terminals and the transformer. The symmetrical components of the subtransient current in the motor flowing toward the fault are: I =-0.8-j2.6pu I =-j 2.0pu I =-j3pu From the transformer toward the Fault: I' = 0.8- j0.4pu I =-j1.0pu 1 = 0pu Assume X =X, =X, for both the motor and the generator. (a) Describe the fault type and find the prefault current, if any, in line a. (b) Determine the subtransient fault current in per unit. (c) Calculate the subtransient current in each phase of the generator in per unit taking into consideration the phase shift of the Y-A transformer.

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
A generator supplies a motor through a Y-A transformer. The generator is connected to Y side of
the transformer. A fault occurs between the motor terminals and the transformer. The
symmetrical components of the subtransient current in the motor flowing toward the fault are:
I =-0.8- j2.6pu
I =-j2.0pu
I =-j3pu
From the transformer toward the Fault:
I = 0.8– j0.4pu
I? =-j1.0pu
1 = Opu
Assume X =X,=X, for both the motor and the generator.
(a) Describe the fault type and find the prefault current, if any, in line a.
(b) Determine the subtransient fault current in per unit.
(c) Calculate the subtransient current in each phase of the generator in per unit taking into
consideration the phase shift of the Y-A transformer.
Transcribed Image Text:A generator supplies a motor through a Y-A transformer. The generator is connected to Y side of the transformer. A fault occurs between the motor terminals and the transformer. The symmetrical components of the subtransient current in the motor flowing toward the fault are: I =-0.8- j2.6pu I =-j2.0pu I =-j3pu From the transformer toward the Fault: I = 0.8– j0.4pu I? =-j1.0pu 1 = Opu Assume X =X,=X, for both the motor and the generator. (a) Describe the fault type and find the prefault current, if any, in line a. (b) Determine the subtransient fault current in per unit. (c) Calculate the subtransient current in each phase of the generator in per unit taking into consideration the phase shift of the Y-A transformer.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,