2 A 1000 kVA 11 kV/400 V ONAF cooled transformer works on a cycle of 3 hours heavy load and 21 hours light load. The peak load is 140 % which can only be maintained for 0.5 hours per hour of time constant. The average cooling air temperature is 25 °C and the oil temperature at the start of the peak load is 65 °C. Prepare a 24-hour loading schedule to include the maximum time the peak load can be maintained and the permissible loads that can be maintained for the remaining periods. Information: The thermal time constant for an ONAF transformer up to 12.5 kV is 3 and the relevant loading factors are given in the source document.

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
2
A 1000 kVA 11 kV/400 V ONAF cooled transformer works on a cycle of 3 hours heavy
load and 21 hours light load. The peak load is 140 % which can only be maintained for
0.5 hours per hour of time constant. The average cooling air temperature is 25 °C
and the oil temperature at the start of the peak load is 65 °C.
Prepare a 24-hour loading schedule to include the maximum time the peak load can be
maintained and the permissible loads that can be maintained for the remaining periods.
Information:
The thermal time constant for an ONAF transformer up to 12.5 kV is 3 and the relevant
loading factors are given in the source document.
Transcribed Image Text:2 A 1000 kVA 11 kV/400 V ONAF cooled transformer works on a cycle of 3 hours heavy load and 21 hours light load. The peak load is 140 % which can only be maintained for 0.5 hours per hour of time constant. The average cooling air temperature is 25 °C and the oil temperature at the start of the peak load is 65 °C. Prepare a 24-hour loading schedule to include the maximum time the peak load can be maintained and the permissible loads that can be maintained for the remaining periods. Information: The thermal time constant for an ONAF transformer up to 12.5 kV is 3 and the relevant loading factors are given in the source document.
AI-Generated Solution
AI-generated content may present inaccurate or offensive content that does not represent bartleby’s views.
steps

Unlock instant AI solutions

Tap the button
to generate a solution

Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,