Explain the advantage of connecting the low-voltage winding of distribution transformers in star. A factory has the following load with power factor of 0.9 lagging in each phase. Red phase 40 A, yellow phase 50 A and blue phase 60 A. If the supply is 400 V, three phase, four-wire, calculate the current in the neutral and the total active power. Draw a phasor diagram for phase and line quantities. Assume that, relative to the current in the red phase, the current in the yellow phase lags by 120° and that in the blue phase leads by 120°. ANS:  17.3 A, 31.2 kW

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.28MCQ
icon
Related questions
Question

Explain the advantage of connecting the low-voltage

winding of distribution transformers in star.

A factory has the following load with power factor of

0.9 lagging in each phase. Red phase 40 A, yellow phase

50 A and blue phase 60 A. If the supply is 400 V, three

phase, four-wire, calculate the current in the neutral

and the total active power. Draw a phasor diagram for

phase and line quantities. Assume that, relative to the

current in the red phase, the current in the yellow phase

lags by 120° and that in the blue phase leads by 120°.

ANS: 

17.3 A, 31.2 kW

Expert Solution
steps

Step by step

Solved in 2 steps with 3 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning