Consider a three-phase generator rated 3 00 MVA , 23 kV , supplying a system load of 240 MA and 0.9 power factor lagging at 230 kV through a 33 0 MVA , 23 Δ / 23 0 Y-kV step-up transformer with a leakage reactance of 0.11 per unit. (a) Neglecting the exciting current and choosing base values at the load of 100 MVL and 230 kV. Find the phasor currents I A , I B , and I C supplied to the load in per unit. (b) By choosing the load terminal voltage I A as reference, specify the proper base for the generator circuit and determine the generator voltage V as well as the phasor currents I A , I B , and I C , from the generator. ( Note: Take into account the phase shift of the transformer.) (C) Find the generator terminal voltage in kV and the real power supplied by the generator in MW. (d) By omitting the transformer phase shift altogether, check to see whether you get the same magnitude of generator terminal voltage and real power delivered by the generator.
Consider a three-phase generator rated 3 00 MVA , 23 kV , supplying a system load of 240 MA and 0.9 power factor lagging at 230 kV through a 33 0 MVA , 23 Δ / 23 0 Y-kV step-up transformer with a leakage reactance of 0.11 per unit. (a) Neglecting the exciting current and choosing base values at the load of 100 MVL and 230 kV. Find the phasor currents I A , I B , and I C supplied to the load in per unit. (b) By choosing the load terminal voltage I A as reference, specify the proper base for the generator circuit and determine the generator voltage V as well as the phasor currents I A , I B , and I C , from the generator. ( Note: Take into account the phase shift of the transformer.) (C) Find the generator terminal voltage in kV and the real power supplied by the generator in MW. (d) By omitting the transformer phase shift altogether, check to see whether you get the same magnitude of generator terminal voltage and real power delivered by the generator.
Consider a three-phase generator rated
3
00
MVA
,
23 kV
, supplying a system load of 240 MA and 0.9 power factor lagging at 230 kV through a
33
0
MVA
,
23
Δ
/
23
0
Y-kV
step-up transformer with a leakage reactance of 0.11 per unit. (a) Neglecting the exciting current and choosing base values at the load of 100 MVL and 230 kV. Find the phasor currents
I
A
,
I
B
,
and
I
C
supplied to the load in per unit. (b) By choosing the load terminal voltage
I
A
as reference, specify the proper base for the generator circuit and determine the generator voltage V as well as the phasor currents
I
A
,
I
B
,
and
I
C
,
from the generator. (Note: Take into account the phase shift of the transformer.) (C) Find the generator terminal voltage in kV and the real power supplied by the generator in MW. (d) By omitting the transformer phase shift altogether, check to see whether you get the same magnitude of generator terminal voltage and real power delivered by the generator.
2. (35 points) Use you program to investigative properties of a four step linear pathway. Just
extend the model given in question 1 to include an additional two species x2 and x3. You can
assume simple irreversible mass-action kinetic on each reaction.
I recommend you use the following values for the rate constants: 1 = 0.6; k2 = 1.8; k3 =
0.5; k40.04. This will enable you to more easily answer the following questions.
You can also assume that the input is the source X and you can set its value to one.
You may find that the plot of the phase change at x3 is broken at -180 degrees because it wraps
around. To avoid this you can use the method:
phase = np.unwrap(phase)
to make sure the phase plot is continuous.
[10] i) Compute and show the Bode plots for x1, x2 and x3 with respect to the input Xo.
[5] ii) Do you see a pattern with the maximum phase shifts as you move from x₁ to x3?
[10] iii) Can you explain this pattern?
[5] iv) What would you predict would be the maximum phase shift for…
Please answer all
The zombies showed up while you were sleeping! The zombie alarm you built goes off as they open the door. You jolt awake to see an alpha-zombie charging through the door. The alphas are zombies that turned all of the zombies in its army. If you can take down this one zombie, all the others pouring into the room should fall as well. Luckily, your group was prepared for this eventuality. Another member of your team has constructed the zombie shocker circuit shown in Figure 5, using some batteries for the voltage source, some rusty metal for the resistors and a coil of wire for the inductor. The switch is just you pulling apart two wires to open the circuit (while holding them by their insulated sheaths).
1. Construct the circuit shown in Figure 15 in the Circuit JS simulator. 2. Start the simulation with switch SW1 in the closed position. You’ve been charging this circuit all night, so you’ll want to let the circuit run for a while (roughly 30 seconds at max…
Please answer all questions
1. Calculate the values of the following without using Circuit JS. Assume the circuit has reached steady state. Show these calculations: a) Voltage across and current through C1. b) Voltage across and current through L1. c) Voltage across and current through R5. 2. Construct the circuit in the Circuit JS simulator [1]. 3. Perform a simulation and determine the following values. Record them. Allow the circuit to reach steady state. a) Voltage across and current through C1. b) Voltage across and current through L1. c) Voltage across and current through R5. 4. Include a screen shot of the simulator window (including showing the values listed above). 5. Answer the following questions: a) In a DC circuit, what does a capacitor look like?
b) In a DC circuit, what does an inductor look like?
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
How does a Transformer work - Working Principle electrical engineering; Author: The Engineering Mindset;https://www.youtube.com/watch?v=UchitHGF4n8;License: Standard Youtube License