
Electric machinery fundamentals
5th Edition
ISBN: 9780073529547
Author: Chapman, Stephen J.
Publisher: MCGRAW-HILL HIGHER EDUCATION
expand_more
expand_more
format_list_bulleted
Concept explainers
Textbook Question
Chapter 2, Problem 2.1Q
Is the turns ratio of a transformer the same as the ratio of voltages across the transformer? Why or why not?
Expert Solution & Answer

To determine
Whether a transformer’s turns ratio is same as a transformer’s voltage ratio or not along with reason.
Explanation of Solution
Diagram of ideal transformer is:
Mutual flux of transformer is
Primary voltage of transformer is
Secondary voltage of transformer is −
Ratio of primary and secondary voltage is
It is observed that ratio of voltages of transformer are same as ratio of their turns because flux linking both the coils is same. So, voltage will be directly proportional to number of turns.
Want to see more full solutions like this?
Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
A single phase a.c. distributor AB has:
The distance from A to B is 500 m. The distance from A to C is 800 m.
The impedance of each section is (6+j 8) /km.
A
B
C
The voltage at the far end is maintained at 250 volt.
Find: sending voltage, sending current, supply power factor and
80 A
60 A
total voltage drop.
0.8 lag. P.f
0.6 lead. p.f
A 3-phase, 4-wire distributor supplies a balanced voltage of 400/230 V to a load consisting of 8 A at p.f. 0-7
lagging for R-phase, 10 A at p.f. 0-8 leading for Y phase and 12 A at unity p.f. for B phase. The resistance
of each line conductor is 0.4 2. The reactance of neutral is 0.2 2. Calculate the neutral current, the supply
voltage for R phase and draw the phasor diagram. The phase sequence is RYB.
The three line leads of a 400/230 V, 3-phase, 4-wire supply are designated as R, Y and B respectively.
The fourth wire or neutral wire is designated as N. The phase sequence is RYB. Compute the currents
in the four wire when the following loads are connected to this supply:
From R to N: 25 kW, unity power factor.
From Y to N: 20 kVA, 0-7 lag.
From B to N: 30 kVA, 0-6 lead.
Chapter 2 Solutions
Electric machinery fundamentals
Ch. 2 - Is the turns ratio of a transformer the same as...Ch. 2 - Why does the magnetization current impose an upper...Ch. 2 - What components compose the excitation current of...Ch. 2 - What is the leakage flux in a transformer? Why is...Ch. 2 - List and describe the types of losses that occur...Ch. 2 - Why does the power factor of a load affect the...Ch. 2 - Why does the short-circuit test essentially show...Ch. 2 - Why does the open-circuit test essentially show...Ch. 2 - How does the per-unit system of measurement...Ch. 2 - Why can autotransformers handle more power than...
Ch. 2 - What are transformer taps? Why are they used?Ch. 2 - What are the problems associated with the Y—Y...Ch. 2 - What is a TCUL transformer?Ch. 2 - How can three-phase transformation be accomplished...Ch. 2 - Prob. 2.15QCh. 2 - Can a 60-Hz transformer be operated on a 50-Hz...Ch. 2 - What happens to a transformer when it is first...Ch. 2 - What is a potential transform? How is it used?Ch. 2 - What is a current transformer? How is it used?Ch. 2 - A distribution transformer is rated at 18 kVA,...Ch. 2 - Why does one hear a hum when standing near a large...Ch. 2 - A 100-kVA, 8000/277-V distribution transformer has...Ch. 2 - A single-phase power system is shown in Figure...Ch. 2 - Consider a simple power system consisting of an...Ch. 2 - The secondary winding of a real transformer has a...Ch. 2 - When travelers from the USA and Canada visit...Ch. 2 - A 1000-VA, 230/115-V transformer has been tested...Ch. 2 - A 30-kVA, 8000/230-V distribution transformer has...Ch. 2 - A 150-MVA, 15/200-kV, single-phase power...Ch. 2 - A 5000-kVA, 230/13.8-kV, single-phase power...Ch. 2 - A three-phase transformer bank is to handle 500...Ch. 2 - A 100-MVA, 230/115-kV, Y three-phase power...Ch. 2 - Three 20-kVA, 24,000/277-V distribution...Ch. 2 - A 14,000/480-V, three-phase, Y-connected...Ch. 2 - A 13.8-kV, single-phase generator supplies power...Ch. 2 - An autotransformer is used to connect a 12.6-kV...Ch. 2 - Prove the following statement: If a transformer...Ch. 2 - A 10-kVA, 480/120-V conventional transformer is to...Ch. 2 - A 10-kVA, 480/120-V conventional transformer is to...Ch. 2 - Two phases of a 14.4-kV, three-phase distribution...Ch. 2 - A 50-kVA, 20,000/480-V, 60-Hz, single-phase...Ch. 2 - Prove that the three-phase system of voltages on...Ch. 2 - Prove that the three-phase system of voltages on...Ch. 2 - A single-phase, 10-kVA, 480/120-V transformer is...Ch. 2 - Figure P2-4 shows a one-line diagram of a power...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- A 3-phase, 50 Hz, 132 kV overhead line transpose system of bundle conductors .a radius of conductor is 0.5 cm. Calculate the total inductance of the line. 4m bi 4m C1 C1 im am biarrow_forwardInth big below:- A 500m B Zoom с 180011 I=50A I-60A I-804 06 ·0.7 0.8 lag. unit) Teading Pf P.F Pl A I sing phase distributor of 3/cm = The distance from point A To B is 500m distance from point A To C is /200m The distance from point A To D is 3000m The impedance of each part is. ZAB-0.51j0.8 -2/km ZBC= 0.7+71.2 12/1cm ZCD = 1.3772.5 -2/1cm The voltage of end for is VD= 220 Volt Find : 1- sending Voltage senting power 2- 5arrow_forwardConsider the circuit diagram below, where the load is indicated by the dashed box. Compute the apparent power and power factor of the load. Use power factor correction to correct the power factor of the load to 0.8 lagging. Your solution should include a circuit diagram of your modified circuit.arrow_forward
- Consider the circuit diagram below. What is the power factor of the circuit? Is it leading or lagging? Draw the power factor triangle of the circuit without calculating the individual power consumption of each component.arrow_forwardExplain what is wrong with each diagram in Fig. 6.41 if the two op amps are known to be perfectly ideal.arrow_forwardAmplitudes are given in peak values. Use node analysis to determine the voltage at nodes a and b. Express the voltages as sinusoids in the time domain with phase angles measured in radians. You may solve the system of equations using MATLAB or a similar software, but you must include the code you ran as part of your solution.arrow_forward
- Q3a [3 points] Simplify the following Boolean function using K-map: f= (0,2,8,9,10,12) & don't care X= (1,7,14) Put each cell number in the cell left upper corner. Put 1, O or X inside each cell. Circle your groups Write the simplified function f in terms of x, y, z and w ESM MZ f= Q3b [2 point] Design the above simplified Boolean function f after k-map using iCircuit then post your design screenshot here:arrow_forwardQ1a [2 points] Convert the binary into octal and hexadecimal? (10101111101)2 = ( )2 = ( )8 (10101111101) = ( )2 = ( )16 Q1b [2 points] Convert the decimal number 91.125 into binary? 91/2 = 91.25=( )2 0.125x2 = Q1c [1 point] Convert (101110), into decimal?arrow_forwardQ2 [5 points] Given the following Truth Table: f m X M 0 0 0 0 1 1 0 0 1 1 2 0 1 0 1 3 0 1 1 0 4 1 0 0 1 5 1 10 1 0 6 1 1 0 1 7 1 1 1 1 [1 point] Find the Boolean Function f in Minterms form: f=m( [1 point] Find the Boolean Function f in terms of x, y and z: f= [3 point] Simplify the above Boolean Function f in the sum form using k-map: Put each cell number in the cell left upper corner. Put 1's or 0's in each cell Circle any group of 4 ones, if not, circle any group of 2 ones Write the simplified function f in terms of x, y and z Narrow_forward
- Q4) A: Derive with the aid of diagrams the critical clearing angle for synchronous generator connected to infinite bus bar through parallel transmission line when fault occurs at the sending end of the lines.arrow_forwardQ3) A:A 60 Hz, 4 pole turbo-generator rated 10 MVA., 20 KV has stored energy in the rotor at synchronous speed of 90 MJ. (a) Find. M the anguler momentum. (b)If the generator supply 10 MW load at synchronous speed, find rotor acceleration in degrees/sec.² and in rpm/sec if the rotor drop to 5MW. (c) If the rotor acceleration calculated in part (b) is maintained for 12 cycles, find the change in torque angle and rotor speed in rpm at the end of this period.arrow_forwardChat gpt responses and ai responses are reported immediately reported please solve this question step by step handwritten solution thanksarrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- Electricity for Refrigeration, Heating, and Air C...Mechanical EngineeringISBN:9781337399128Author:Russell E. SmithPublisher:Cengage LearningPower System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning

Electricity for Refrigeration, Heating, and Air C...
Mechanical Engineering
ISBN:9781337399128
Author:Russell E. Smith
Publisher:Cengage Learning

Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
TRANSFORMERS - What They Are, How They Work, How Electricians Size Them; Author: Electrician U;https://www.youtube.com/watch?v=tXPy4OE7ApE;License: Standard Youtube License