Air enters a cooling section at 97 kPa, 35°C, and 30 percent relative humidity at a rate of 6 m3/min, where it is cooled until the moisture in the air starts condensing. Determine (a) the temperature of the air at the exit and (b) the rate of heat transfer in the cooling section.
(a)
The temperature of the air at the exit.
Answer to Problem 130RP
The temperature of the air at the exit is
Explanation of Solution
As the process is a steady flow and thus the mass flow rate of dry air remains constant during the entire process.
Here, the mass flow rate of air at inlet is
The amount of moisture in the air remains constant as it flows through the heating section as process involves no dehumidification or humidification.
Here, specific humidity at state 1 and 2 is
Express initial partial pressure.
Here, relative humidity at state 1 is
Express initial humidity ratio.
Here, pressure at state 1 is
Express initial enthalpy.
Here, specific heat at constant pressure is
Express specific volume at state 1.
Here, gas constant of air is
As the air at the final state is saturated and the vapor pressure during the process will remain constant, thus the dew point temperature is the exit temperature.
Here, exit temperature is
Conclusion:
Refer Table A-4, “saturated water-temperature table”, and write the saturation pressure and initial specific enthalpy saturated vapor at temperature of
Substitute
Substitute
Substitute
Refer Table A-2, “ideal-gas specific heats of various common gases”, and write the properties of air.
Substitute
Substitute
Substitute
Refer Table A-5, “saturated water-pressure table”, and write the saturation temperature or exit temperature at pressure of
Write the formula of interpolation method of two variables.
Here, the variables denote by x and y is pressure and exit or saturation temperature respectively.
Show the specific enthalpy at state 2 corresponding to specific entropy as in Table (1).
Pressure |
Saturation or exit temperature |
1.5 | 13.02 |
1.69 | |
2 | 17.50 |
Substitute
Substitute
Hence, the temperature of the air at the exit is
(b)
The rate of heat transfer in the cooling section.
Answer to Problem 130RP
The rate of heat transfer in the cooling section is
Explanation of Solution
Express the enthalpy of air at exit.
Here, temperature at exit is
Express mass flow rate of air.
Here, volume flow rate at inlet is
Express the rate of heat transfer in the cooling section.
Conclusion:
Refer Table A-4, “saturated water-temperature table”, and write the final specific enthalpy saturated vapor at temperature of
Show the final specific enthalpy saturated vapor corresponding to exit temperature as in Table (2).
Exit temperature |
Final specific enthalpy saturated vapor |
10 | 2519.2 |
14.8 | |
15 | 2528.3 |
Use excels and tabulates the values from Table (2) in Equation (VIII) to get,
Substitute
Substitute
Substitute
Substitute
Hence, the rate of heat transfer in the cooling section is
Want to see more full solutions like this?
Chapter 14 Solutions
EBK THERMODYNAMICS: AN ENGINEERING APPR
- The desired final conditions of the air in the room are 22 °C and 65% relative humidity. To achieve these conditions, outdoor air at 10 °C and 40% relative humidity is firstly heated to 18 °C and then humidified by steam injection. For an airflow rate of 50 m3/min, determine the rate of heat supplied and the mass flow rate of steam required for humidification. Make use of psychrometric charts.arrow_forward250 kg/h of air saturated at 2°C is mixed with 50 kg/h of air at 35°C and 80% relative humidity. Determine the final state of airarrow_forwardIn an industrial plant where tires are made, there is a wet cooling tower which fulfills a very important part of the process, it must cool 15 kg/s of watercooling temperature from 45 to 27°C, in a location where the atmospheric pressure is 95 kPa.Atmospheric air enters the tower at 22 °C and 60% relative humidity, and leaves 0.87 saturated at a temperature of 37 °C.Neglecting the power input to the fan, determine the following:1. The volumetric flow of air at the inlet of the cooling tower.2. The mass flow of make-up water required.arrow_forward
- Cooling water leaves the condenser of a power plant and enters a wet cooling tower at 35°C at a rate of 100 kg/s. Water is cooled to 22°C in the cooling tower by air that enters the tower at 1 atm, 20°C, and 60 percent relative humidity and leaves saturated at 30°C. Neglecting the power input to the fan, determine (a) the volume flow rate of air into the cooling tower and (b) the mass flow rate of the required makeup water.arrow_forwardAmbient air with a dew point of 1°C and a relative humidity of 60% is conveyed at a rate of 1.5 m3/s through an electric heater. The air is heated to a dry bulb temperature of 50°C. The heated air is then allowed to pass through a tray drier that contains 200 kg of apple slices with an initial moisture content of 80% wet basis. The air exits the dryer with a dew-point temperature of 21.2°C. If the electrical energy costs 5¢/(kW h), calculate the electrical costs for heating the air per hour of operation. {Hint: unit of electrical energy is kW.h, ie. amount of power consumed for 1 hour. To estimate the electrical energy, you calculate the power required in kW and multiply it by the number of hours of operation. Do not do unit conversion of hours into seconds} Calculate the amount of water removed by air from apple slices per hour of operation. If the dryer is operated for 2 h, what will be the final moisture content of the apple slices (wet basis)?arrow_forwardThe air in a room (24.0°C and 30% humidity) with a volume of 96.6 m3 must be replaced every 5 minutes. Outside air at 38.0°C and 70% humidity is chilled to remove some of its water content and then dehumidified to the required temperature. What is the volumetric flow rate (in m3/min) of the humid air entering the chiller?arrow_forward
- A cooling tower receives 6 kg/s of water of 60oC. Air enters the tower at 32oC DB and 27oC WB temperatures and leaves at 50oC and 90 per cent relative humidity. The cooling efficiency is 60.6 per cent. Determine: (a) the mass flow rate of air entering, and (b) the quantity of make-up water required.arrow_forward20h AD Air enters a 30 cm diameter cooling section at 1 atm, 35 C°, and 60 % relative humidity at 120 m/min. The air is cooled by passing it over a cooling coil through which cold water. flow. The water experiences a temperature rise of 8 C° The air leaves the cooling section saturated at 20 CO Determine:. tuly: a- The rate of heat transfer. b- The mass flow rate of the water c- The exit velocity of the air stream. Assume specific heat capacity of water is 4.18 kJ/kg. Cº cuétems?arrow_forwardProper indoor ventilation is important to lower the risk of infection from the SARS-CoV-2 virus. The air in a room (28.0°C and 30% humidity) with a volume of 96.6 m3 must be replaced every 5 minutes. Outside air at 38.0°C and 70% humidity is chilled to remove some of its water content and then dehumidified to the required temperature. What is the volumetric flow rate (in m3/min) of the humid air entering the chiller? How many kg of water per kg of dry air is removed from the dehumidification process? To what temperature (in °C) should the outside air be chilled?arrow_forward
- 8. Moist air undergoes a heating and humidification process at a pressure of 101.325 kPa from an initial state of 15°C db and 90% relative humidity to a final state at 22°C and 70% relative humidity. If the mass flow rate of the air at the initial state is 24.5 kg da/s, what is the increase in the water content of the air? Express your answer in kg/s. In your written solution, draw the process in the psychrometric chart, show the initial and final state and the values obtained from the chart.arrow_forwardIn an air-conditioning unit 3.5 m3/s air at 27°C dry-bulb temperature, 21°C wet-bulb temperature, and 95 kPa atmospheric pressure enters the unit. The leaving condition of the air is 13°C dry-bulb temperature and 90 percent relative humidity. Calculate the rate of water removal from the air in kg/s.arrow_forwardAn air-conditioning system is to take in outdoor air at 10 C and 30 percent relative humidity at a steady rate of 45 m3/min and to condition it to 25 C and 60 percent relative humidity. The outdoor air is first heated to 22 C in the heating section and then humidified by the injection of hot steam in the humidifying section. Assuming the entire process takes place at a pressure of 100 kPa, determine a. the rate of heat supply in the heating section and b. the mass flow rate of the steam required in the humidifying section.arrow_forward
- Elements Of ElectromagneticsMechanical EngineeringISBN:9780190698614Author:Sadiku, Matthew N. O.Publisher:Oxford University PressMechanics of Materials (10th Edition)Mechanical EngineeringISBN:9780134319650Author:Russell C. HibbelerPublisher:PEARSONThermodynamics: An Engineering ApproachMechanical EngineeringISBN:9781259822674Author:Yunus A. Cengel Dr., Michael A. BolesPublisher:McGraw-Hill Education
- Control Systems EngineeringMechanical EngineeringISBN:9781118170519Author:Norman S. NisePublisher:WILEYMechanics of Materials (MindTap Course List)Mechanical EngineeringISBN:9781337093347Author:Barry J. Goodno, James M. GerePublisher:Cengage LearningEngineering Mechanics: StaticsMechanical EngineeringISBN:9781118807330Author:James L. Meriam, L. G. Kraige, J. N. BoltonPublisher:WILEY