Atmospheric air at 1 atm, 32°C, and 95 percent relative humidity is cooled to 24°C and 60 percent relative humidity. A simple ideal vapor-compression refrigeration system using refrigerant-134a as the working fluid is used to provide the cooling required. It operates its evaporator at 4°C and its condenser at a saturation temperature of 39.4°C. The condenser rejects its heat to the atmospheric air. Calculate the exergy destruction, in kJ, in the total system per 1000 m3 of dry air processed.
The exergy destruction in the total system per
Answer to Problem 88P
The exergy destruction in the total system per
Explanation of Solution
Show the T-s diagram for the simple ideal vapour-compression refrigeration system.
Express the mass of air.
Here, volume at state 1 is
Express the water mass balance and energy balance equations to the combined cooling and dehumidification section.
For water mass balance:
For energy balance:
Write the energy balance equation using steady-flow equation.
Here, the rate of total energy entering the system is
Substitute
Here, the specific enthalpy at the state 1 and 2 are
Write the formula for mass flow rate of refrigerant-134a.
Write the formula for amount of heat rejected from the condenser.
Calculate the exergy destruction in the components of the refrigeration cycle.
For the process 1-2,
Here, the process 1-2 is an isentropic.
For the process 2-3,
For the process 3-4,
Write the entropy change of water vapour in the air stream.
Write the entropy of water leaving the cooling section.
Determine the partial pressure of water vapour at state 1 for air steam.
Determine the partial pressure of dry air at state 1 for air steam.
Here, the pressure at the state 1 is
Determine the partial pressure of water vapour at state 2 for air steam.
Determine the partial pressure of dry air at state 2 for air steam.
Here, the pressure at the state 2 is
Write the formula for entropy change of dry air.
Write the formula for entropy change R-134a in the evaporator.
Write the formula for an entropy balance on the evaporator.
Write the formula for an exergy destruction in the evaporator.
Write the formula for the total exergy destruction.
Conclusion:
Refer Figure A-31, “psychometric chart at
Refer Table A-4, “saturated water-temperature table”, and write the specific enthalpy of condensate water at temperature of
Here, entropy of saturation liquid at temperature of
Write the formula of interpolation method of two variables.
Here, the variables denote by x and y is temperature and specific enthalpy of condensate water at state 2 respectively.
Show the specific enthalpy of condensate water at corresponding to temperature as in Table (1).
Temperature |
Specific enthalpy of condensate water |
25 | 104.83 |
28 | |
30 | 125.74 |
Substitute
Substitute
Substitute
Substitute 1105 kg for
Substitute 1105 kg for
From the Table A-11 “Saturated Refrigerant-134a-Pressure Table”, obtain the value of the specific enthalpy and entropy at state 1 of
Refer Table A-13 “Saturated Refrigerant-134a-Pressure Table”, and write the specific enthalpy at state 2 in 1 MPa of pressure and entropy of
From the Table A-12 “Saturated Refrigerant-134a-Pressure Table”, obtain the value of the specific enthalpy and entropy at state 3 of
Here, the specific enthalpy at the state 4 and 3 are equal in the throttling.
Calculate the value of
From the Table A-11 “Saturated Refrigerant-134a-Pressure Table”, obtain the value of the specific enthalpy and entropy of saturated liquid and change upon vaporization at state 4 of
Substitute
Calculate the value of specific entropy of the state 4.
Substitute
Substitute
Substitute
Substitute
Substitute
Refer Table A-4 “Saturated water-temperature Table”, and write the specific entropy at state 1 at
Refer Table A-4 “Saturated water-temperature Table”, and write the specific entropy at state 1 at
Substitute
Substitute
Substitute
Substitute
Substitute
Substitute
Substitute
Substitute
Substitute
Substitute
Substitute 0 for
Thus, the exergy destruction in the total system per
Want to see more full solutions like this?
Chapter 14 Solutions
EBK THERMODYNAMICS: AN ENGINEERING APPR
- Consider the vapor-compression refrigeration cycle shown below with tetrafluoroethane as the refrigerant. If the evaporation temperature is -12°C, determine the coefficients of performance for condensation temperatures of 16°C, 28°C, and 40°C. Use the table containing the properties of saturated 1,1,1,2- tetrafluoroethane (R134A) and the PH diagram for tetrafluoroethane (HFC-134a). T S Vapor-compression refrigeration cycle. 4 Throttle valve Condenser Compressor Evaporator Assume isentropic compression of the vapor. The coefficient of performance for a condensation temperature of 16°C is The coefficient of performance for a condensation temperature of 28°C is 3 The coefficient of performance for a condensation temperature of 40°C is 2arrow_forward1. A refrigeration system using R-22 has a capacity of 320 kW of refrigeration. The evaporating temperature is -10°C and the condensing temperature is 40°C. Calculate the fraction of vapor in the mixture before the evaporator. Properties of R-22: At -10°C; hg = 401.60 kJ/kg, hf = 188.43 kJ/kg At 40°C; hf 249.69 kJ/kgarrow_forwardAdditional Instructions: Define each enthalpy obtained from tables and chart and draw the p-h diagram labeling the respective evaporating and condensing pressures and temperatures in each problem. (2) A standard vapor compression system produces 20 tons of refrigeration using R-12 as a refrigerant while operating between a condenser temperature of 41.6 C and an evaporator temperature of -25°C. Determine (a) the refrigerating effect in kJ/kg, (b) the circulating rate in kg/s, (c) the power supplied, (d) the COP, (e) the heat rejected in kW, and (f the volume flow rate in L/s. Ans. (a) 100.26 kJ/kg, (b) 0.7022 kg/s, (c) 25.69 kW, (d) 2.74, (e) 96.09 kW, (f) 92.18 L/sarrow_forward
- Can you also show the plot on the chart provided? The mass flow rate of the refrigerant in a Single Stage Vapor Compression (SSVC) refrigeration system is 0.015 kg/s and the evaporating and condensing temperatures shall be -20°C and 50°C, respectively. Determine the following: (1) cooling capacity in tons, (2) work of compressor in kW, (3) COP of the system, (4) EER of the system, and (5) refrigerating efficiency. Can you also show the plot on the chart provided?arrow_forwardاريد حل كتابة يدarrow_forwardA refrigeration system using refrigerant 12 is to have a refrigerating capacity of 80 kW. The cycle is a standard vapor-compression cycle in which the evaporating temperature is -15°C and the condensing temperature 30°C. At the entrance to the evaporator, what is the fraction of vapor in the mixture expressed on a mass basis? 0.97 0.29 0.92 0.27arrow_forward
- Air enters a humidifier at 34.25°C and 30% RH. If the air leaves the humidifier at 70% RH. Determine: The exit dry-bulb temperature of the air in °C.The saturation effectiveness in %.arrow_forwardIn the C-D duct, with the help of a refrigeration cycle which uses R-134A as a working fluid, atmospheric air is cooled at a rate of 34 m3/min, which is entering at a temperature of 36°C and a relative humidity of fifty%. The enthalpy produced in thisprocess is 29.46 kJ/kg of mass of dry air and it is possible to cool the air to 19°C.During this process the Plant Engineers need to know the flow of water that is extracted from the incoming air and the KW needed for the cooling process if the water leaves at 19.2°C.arrow_forwardA two-stage ammonia food-freezing plant – with a desired capacity of 528,000 kJ/h at -40℃ evaporating temperature and 35C condensing temperature – has a flash intercooling system with a liquid sub cooler. The vapour leaving the evaporator is at -30℃ and entering the first stage compressor is at -15℃. The vapour leaving the flash chamber is superheated by 10℃ in the suction line to the second stage compressor. Water intercooling is done to cool the vapour to 45℃. Adiabatic efficiencies of both compressors are 0.65 and 0.77 respectively. Find the piston displacements, discharge temperatures and power requirements of the two compressors.arrow_forward
- HUMIDIFIER: MASS BALANCE On a hot summer day, the air is at 30.6 ° C and 80% relative humidity. The air conditioning in a building supplies 30 m3 / min of air at 13 ° C to keep the air inside the building at an average temperature of 24 ° C and 40% relative humidity. If the ventilation switch of the air conditioner is “open”, the air from outside enters the unit as shown in the drawing (I): The air conditioner cools the air to a temperature low enough to condense the required amount of water and reheat it to 13 ° C (unsaturated current), at which point it has the same absolute humidity as the air in the building. Calculate: a. the speed at which condenses water (kg / min) b. the temperature at which the air must be cooled to condense water at this rate. Do the calculations without using the psychrometric chart (although 1 atm of current pressure can be assumed). If the ventilation switch is closed, as normal, the air from inside the building would be recirculated in the air…arrow_forwardالسؤال الثالث The thermodynamic properties of refrigerant R22 mixture of liquid and vapor leaving the expansion device and entering the evaporator are: pressure of 498 KPa, temperature of 0 °C, fraction dryness (x) of 0.238, saturated liquid enthalpy of 200 kJ/kg, and saturated vapour enthalpy of 405 kJ/kg. The pressure of this refrigerant at the entrance of the condenser is measured to be 19.3 bar After the subcooling process, the enthalpy in (kJ/kg) and the pressure in (MPa) of this refrigerant have been measured and were found to be 199 47 kJ/kg and 2.3 MPa. 239. 68 kJ/kg and 1.96 MPAO 248.79 kU/kg and 1.93 MPa 110 52 kJ/kg and 3.1 MPa 1:29 PM 91°F Sunny 5/14/2022arrow_forwardاريد حل كتابة يدarrow_forward
- Refrigeration and Air Conditioning Technology (Mi...Mechanical EngineeringISBN:9781305578296Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill JohnsonPublisher:Cengage Learning