The parallel admittance of a 300 mile transmission line isYc=0+j6.87*10^-6 S/mileDetermine the ABCD constants of a shunt reactance that compensates for 60% of the total shunt admittance!

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter4: Transmission Line Parameters
Section: Chapter Questions
Problem 4.35MCQ: The affect of the earth plane is to slightly increase the capacitance, and as the line height...
icon
Related questions
Question

The parallel admittance of a 300 mile transmission line is
Yc=0+j6.87*10^-6 S/mile
Determine the ABCD constants of a shunt reactance that compensates for 60% of the total shunt admittance!

Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer