Solve the following problems with complete solutions and units using two(2) decimal digits. 3. A 100-kVA, 6600/330-V., 50 Hz, 1-phase transformer took 10 A. and 436 W. at 100 V. in a short-circuit test, referring to the high voltage side. Calculate the voltage to be applied to the high voltage side on full-load at power factor of 0.8 lagging when the secondary terminal voltage is 330 V.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.15P: Rework Problem 3.14 if the transformer is delivering rated load at rated secondary voltage and at...
icon
Related questions
Question

Solve the following problems with complete solutions and units using
two(2) decimal digits.

3. A 100-kVA, 6600/330-V., 50 Hz, 1-phase transformer took 10 A. and
436 W. at 100 V. in a short-circuit test, referring to the high voltage
side. Calculate the voltage to be applied to the high voltage side on
full-load at power factor of 0.8 lagging when the secondary terminal
voltage is 330 V.

Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning