Q2) In the network in the figure below Y-Y connected transformers, each with grounded neutrals, are at the ends of each transmission line that is not terminating at bus 3. The transformers connecting the lines to bus 3 are Y-A, with the neutral of the Y solidly grounded and the A sides connected to bus 3. All the line reactances shown in the figure between busses include the reactances of the transformers. Zero sequence values for these lines including transformers are 2.0 times those shown in the figure. Both generators are Y-Connected. Zero-sequence reactances of the generators connected to bus 1 and bus 3 are 0.04 and 0.08 per unit, respectively. The neutral of the generator at bus 1 is connected to ground through a reactor of 0.02 per unit; the generator at bus 3 has a solidly ground neutral. (2) (0) Find the bus impedance matrices ZS, Z, Zus for the given network and bus bus then compute the Subtransient current in per unit for a single line-to-ground fault on bus 2 and the fault current contribution flowing in the transmission line connected busses 1 and 2. Assume no pre-fault current is flowing and all pre-fault voltages at all the buses is 1/0° per unit.

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
100%
Q2) In the network in the figure below Y-Y connected transformers, each with
grounded neutrals, are at the ends of each transmission line that is not
terminating at bus 3. The transformers connecting the lines to bus 3 are Y-A, with
the neutral of the Y solidly grounded and the A sides connected to bus 3. All the
line reactances shown in the figure between busses include the reactances of the
transformers. Zero sequence values for these lines including transformers are 2.0
times those shown in the figure.
Both generators are Y-Connected. Zero-sequence reactances of the
generators connected to bus 1 and bus 3 are 0.04 and 0.08 per unit, respectively.
The neutral of the generator at bus 1 is connected to ground through a reactor
of 0.02 per unit; the generator at bus 3 has a solidly ground neutral.
Find the bus impedance matrices (¹), (²), z for the given network and
'bus' 'bus' bus
then compute the Subtransient current in per unit for a single line-to-ground fault
on bus 2 and the fault current contribution flowing in the transmission line
connected busses 1 and 2.
Assume no pre-fault current is flowing and all pre-fault voltages at all the buses
is 1/0° per unit.
j0.5
j0.28
voo
#
X = 0.2
Gen. 1
j0.4
X = 0.25
Gen. 2
Transcribed Image Text:Q2) In the network in the figure below Y-Y connected transformers, each with grounded neutrals, are at the ends of each transmission line that is not terminating at bus 3. The transformers connecting the lines to bus 3 are Y-A, with the neutral of the Y solidly grounded and the A sides connected to bus 3. All the line reactances shown in the figure between busses include the reactances of the transformers. Zero sequence values for these lines including transformers are 2.0 times those shown in the figure. Both generators are Y-Connected. Zero-sequence reactances of the generators connected to bus 1 and bus 3 are 0.04 and 0.08 per unit, respectively. The neutral of the generator at bus 1 is connected to ground through a reactor of 0.02 per unit; the generator at bus 3 has a solidly ground neutral. Find the bus impedance matrices (¹), (²), z for the given network and 'bus' 'bus' bus then compute the Subtransient current in per unit for a single line-to-ground fault on bus 2 and the fault current contribution flowing in the transmission line connected busses 1 and 2. Assume no pre-fault current is flowing and all pre-fault voltages at all the buses is 1/0° per unit. j0.5 j0.28 voo # X = 0.2 Gen. 1 j0.4 X = 0.25 Gen. 2
Expert Solution
steps

Step by step

Solved in 4 steps with 5 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,