9.7 A 4-pole, 50 Hz, 3-phase, star-connected Alternator has 60 slots with 2 conductors per slot. The winding is short-chorded by 2 slots. If the sinusoidally distributed flux per pole is 0.062 Wb, calculate the no-load terminal voltage. [Ans : Kp = 0.973: Ka = 0.956: E=257.54: E₁ = 446.07]

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter31: Three-phase Alternators
Section: Chapter Questions
Problem 1RQ: What conditions must be met before two alternators can be paralleled together?
icon
Related questions
Question
9.7 A 4-pole, 50 Hz, 3-phase, star-connected Alternator has 60 slots with 2
conductors per slot. The winding is short-chorded by 2 slots. If the sinusoidally
distributed flux per pole is 0.062 Wb, calculate the no-load terminal voltage.
[Ans : Kp = 0.973: Ka = 0.956: E=257.54: E₁ = 446.07]
Transcribed Image Text:9.7 A 4-pole, 50 Hz, 3-phase, star-connected Alternator has 60 slots with 2 conductors per slot. The winding is short-chorded by 2 slots. If the sinusoidally distributed flux per pole is 0.062 Wb, calculate the no-load terminal voltage. [Ans : Kp = 0.973: Ka = 0.956: E=257.54: E₁ = 446.07]