H.W. 1- The following figures were obtained from tests on a 30-kVA, 3000/110-V transformer: O.C. test: 3000 V 0.5 A 350 W; (a) full-load, 0.8 p.f. S.C. test; 150 V 10 A Calculate the efficiency of the transformer at (b) half-load, unity p.f. 500 W Also, calculate the kVA output at which the efficiency is maximum. (Ans. [96.56%; 97%; 25.1 kVA]) 2- The efficiency of a 400 kVA, 1-phase transformer is 98.77% when delivering full load at 0.8 power factor, and 99.13% at half load and unity power factor. Calculate (a) the iron loss, (b) the full load copper loss.(Ans. [(a) 1012 W (b) 2973 W])
H.W. 1- The following figures were obtained from tests on a 30-kVA, 3000/110-V transformer: O.C. test: 3000 V 0.5 A 350 W; (a) full-load, 0.8 p.f. S.C. test; 150 V 10 A Calculate the efficiency of the transformer at (b) half-load, unity p.f. 500 W Also, calculate the kVA output at which the efficiency is maximum. (Ans. [96.56%; 97%; 25.1 kVA]) 2- The efficiency of a 400 kVA, 1-phase transformer is 98.77% when delivering full load at 0.8 power factor, and 99.13% at half load and unity power factor. Calculate (a) the iron loss, (b) the full load copper loss.(Ans. [(a) 1012 W (b) 2973 W])
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.28MCQ
Related questions
Question
![H.W.
1- The following figures were obtained from tests on a 30-kVA, 3000/110-V transformer:
O.C. test: 3000 V
0.5 A 350 W;
(a) full-load, 0.8 p.f.
S.C. test; 150 V 10 A
Calculate the efficiency of the transformer at
(b) half-load, unity p.f.
500 W
Also, calculate the kVA output at which the efficiency is maximum. (Ans. [96.56%; 97%; 25.1 kVA])
2- The efficiency of a 400 kVA, 1-phase transformer is 98.77% when delivering full load at 0.8 power
factor, and 99.13% at half load and unity power factor. Calculate (a) the iron loss, (b) the full load
copper loss.(Ans. [(a) 1012 W (b) 2973 W])](/v2/_next/image?url=https%3A%2F%2Fcontent.bartleby.com%2Fqna-images%2Fquestion%2F749d077f-d410-4251-8515-bf01cf3812a1%2F792423b1-ff62-4706-9d77-4c2fd2470685%2Fw2gdr9d_processed.jpeg&w=3840&q=75)
Transcribed Image Text:H.W.
1- The following figures were obtained from tests on a 30-kVA, 3000/110-V transformer:
O.C. test: 3000 V
0.5 A 350 W;
(a) full-load, 0.8 p.f.
S.C. test; 150 V 10 A
Calculate the efficiency of the transformer at
(b) half-load, unity p.f.
500 W
Also, calculate the kVA output at which the efficiency is maximum. (Ans. [96.56%; 97%; 25.1 kVA])
2- The efficiency of a 400 kVA, 1-phase transformer is 98.77% when delivering full load at 0.8 power
factor, and 99.13% at half load and unity power factor. Calculate (a) the iron loss, (b) the full load
copper loss.(Ans. [(a) 1012 W (b) 2973 W])
Expert Solution

This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 2 steps with 3 images

Recommended textbooks for you

Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning

Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning