Chapter 5, Problem 5.10P

The 500-kV, 60-Hz, three-phase line in Problems 4.20 and 4.41 has a 180-km length and delivers 1600 M W at 475 kv and at 0.95 power factor leading to the receiving end at full load. Using the nominal π circuit, calculate the (a) ABCD parameters, (b) sending-end voltage and current, (c) sending-end power and power factor, (d) full-load line losses and efficiency, and (e) percent voltage regulation. Assume a 50 ° C . conductor temperature to determine the resistance of this line.