ENGINEERING CIRCUIT...(LL)>CUSTOM PKG.<
ENGINEERING CIRCUIT...(LL)>CUSTOM PKG.<
9th Edition
ISBN: 9781260540666
Author: Hayt
Publisher: MCG CUSTOM
Question
Book Icon
Chapter 11, Problem 35E

(a)

To determine

Find the average power delivered to each load, the apparent power supplied by the source, and the power factor of the combined loads for the circuit in Figure 11.43 in the textbook.

(a)

Expert Solution
Check Mark

Answer to Problem 35E

The average power delivered to Z1, Z2, the apparent power supplied by the source, and the power factor of the combined loads are 139.8W_, 259W_, 408.35VA_, and 0.977lagging_, respectively.

Explanation of Solution

Given data:

Refer to Figure 11.43 in the textbook for the given circuit.

Vff=1193°V,rmsZ1=1432°ΩZ2=22Ω

Formula used:

Write the expression for average power delivered to load as follows:

P=VeffIeffcos(θϕ)        (1)

Here,

Veff is the rms source voltage in the circuit,

Ieff is the rms current in the circuit,

θ is the phase angle of rms source voltage,

ϕ is the phase angle of the rms current, and

cos(θϕ) is the power factor.

Write the expression for rms current in the circuit as follows:

Ieff=VeffZ        (2)

Here,

Z is the is the total impedance in the given circuit.

Write the expression for total impedance in the given circuit as follows:

Z=Z1+Z2        (3)

Write the expression for rms voltage across load as follows:

Veff=IeffZ        (4)

Write the expression for complex power supplied by the source as follows:

S=Veff(Ieff)*        (5)

Write the expression for power factor of the combined loads as follows:

PF=cos(θϕ)        (6)

Calculation:

From Equation (3), substitute (Z1+Z2) for Z in Equation (2) as follows:

Ieff=VeffZ1+Z2        (7)

Substitute 1193°V for Vff, 1432°Ω for Z1, and 22Ω for Z2 to obtain the value of rms current in the circuit.

Ieff=1193°V1432°Ω+22Ω=1193°11.8726+j7.4188+22A=1193°33.8726+j7.4188A=1193°34.675512.35°A

Simplify the expression as follows:

Ieff=3.43159.35°A

Modify the expression in Equation (4) for the voltage across the load Z1 as follows:

(Veff)1=IeffZ1        (8)

Substitute 3.43159.35°A for Ieff and 1432°Ω for Z1 to obtain the voltage across the load Z1.

(Veff)1=(3.43159.35°A)(1432°Ω)=48.04122.65°V

Modify the expression in Equation (1) for the average power delivered to the load Z1 as follows:

P1=(Veff)1Ieffcos(θ1ϕ)        (9)

Substitute 48.041 V for (Veff)1, 3.4315 A for Ieff, 22.65° for θ1, and 9.35° for ϕ to obtain the average power delivered to the load Z1.

P1=(48.041V)(3.4315A)cos[22.65°(9.35°)]=139.8030W139.8W

Modify the expression in Equation (4) for the voltage across the load Z2 as follows:

(Veff)2=IeffZ2        (10)

Substitute 3.43159.35°A for Ieff and 22Ω for Z2 to obtain the voltage across the load Z2.

(Veff)2=(3.43159.35°A)(22Ω)=75.4939.35°V

Modify the expression in Equation (1) for the average power delivered to the load Z2 as follows:

P2=(Veff)2Ieffcos(θ2ϕ)        (11)

Substitute 75.493 V for (Veff)2, 3.4315 A for Ieff, 9.35° for θ2, and 9.35° for ϕ to obtain the average power delivered to the load Z2.

P2=(75.493V)(3.4315A)cos[9.35°(9.35°)]=259.0542W259W

Substitute 1193°V for Vff and 3.43159.35°A for Ieff in Equation (5) to obtain the complex power supplied by the source.

S=(1193°V)(3.43159.35°A)*=(1193°V)(3.43159.35°A)=408.348512.35°VA=(398.8990+j87.3387)VA

Find the apparent power supplied by the source from the complex power as follows:

|S|=|408.348512.35°VA|=408.3485VA408.35VA

Substitute 3° for θ and 9.35° for ϕ in Equation (6) to obtain the power factor of the combined loads.

PF=cos[3°(9.35°)]=0.97680.977

If the imaginary part of the complex power (reactive power) is positive value, then the load has lagging power factor. If the imaginary part is negative value, then the load has leading power factor.

As the imaginary part of the given complex power is positive value, the power factor is lagging power factor.

PF=0.977lagging

Conclusion:

Thus, the average power delivered to Z1, Z2, the apparent power supplied by the source, and the power factor of the combined loads are 139.8W_, 259W_, 408.35VA_, and 0.977lagging_, respectively.

(b)

To determine

Find the average power delivered to each load, the apparent power supplied by the source, and the power factor of the combined loads for the circuit in Figure 11.43 in the textbook.

(b)

Expert Solution
Check Mark

Answer to Problem 35E

The average power delivered to Z1, Z2, the apparent power supplied by the source, and the power factor of the combined loads are 435.72W_, 1307.2W_, 1756.45VA_, and 0.992leading_, respectively.

Explanation of Solution

Given data:

Z1=20°ΩZ2=(6j)Ω

Calculation:

Substitute 1193°V for Vff, 20°Ω for Z1, and (6j)Ω for Z2 in Equation (7) to obtain the value of rms current in the circuit.

Ieff=1193°V20°Ω+(6j)Ω=1193°8jA=1193°8.062257.13°A=14.760110.13°A

Substitute 14.760110.13°A for Ieff and 20°Ω for Z1 in Equation (8) to obtain the voltage across the load Z1.

(Veff)1=(14.760110.13°A)(20°Ω)=29.520210.13°V

Substitute 29.5202 V for (Veff)1, 14.7601 A for Ieff, 10.13° for θ1, and 10.13° for ϕ in Equation (9) to obtain the average power delivered to the load Z1.

P1=(29.5202V)(14.7601A)cos(10.13°10.13°)=435.7211W435.72W

Substitute 14.760110.13°A for Ieff and (6j)Ω for Z2 in Equation (10) to obtain the voltage across the load Z2.

(Veff)2=(14.760110.13°A)[(6j)Ω]=(14.760110.13°A)(6.08279.46°Ω)=89.78120.67°V

Substitute 89.7812 V for (Veff)2, 14.7601 A for Ieff, 0.67° for θ2, and 10.13° for ϕ in Equation (11) to obtain the average power delivered to the load Z2.

P2=(89.7812V)(14.7601A)cos(0.67°10.13°)=1307.1525W1307.2W

Substitute 1193°V for Vff and 14.760110.13°A for Ieff in Equation (5) to obtain the complex power supplied by the source.

S=(1193°V)(14.760110.13°A)*=(1193°V)(14.760110.13°A)=1756.45197.13°VA=(1742.7515j217.9756)VA

Find the apparent power supplied by the source from the complex power as follows:

|S|=|1756.45197.13°VA|=1756.4519VA1756.45VA

Substitute 3° for θ and 10.13° for ϕ in Equation (6) to obtain the power factor of the combined loads.

PF=cos(3°10.13°)=0.992

As the imaginary part of the given complex power is negative value, the power factor is leading power factor.

PF=0.992leading

Conclusion:

Thus, the average power delivered to Z1, Z2, the apparent power supplied by the source, and the power factor of the combined loads are 435.72W_, 1307.2W_, 1756.45VA_, and 0.992leading_, respectively.

(c)

To determine

Find the average power delivered to each load, the apparent power supplied by the source, and the power factor of the combined loads for the circuit in Figure 11.43 in the textbook.

(c)

Expert Solution
Check Mark

Answer to Problem 35E

The average power delivered to Z1, Z2, the apparent power supplied by the source, and the power factor of the combined loads are 16.3W_, 0W_, 82.11VA_, and 0.199lagging_, respectively.

Explanation of Solution

Given data:

Z1=10070°ΩZ2=7590°Ω

Calculation:

Substitute 1193°V for Vff, 10070°Ω for Z1, and 7590°Ω for Z2 in Equation (7) to obtain the value of rms current in the circuit.

Ieff=1193°V10070°Ω+7590°Ω=1193°(34.202+j93.969)+(0+j75)A=1193°172.395778.56°A=0.6975.56°A

Substitute 0.6975.56°A for Ieff and 10070°Ω for Z1 in Equation (8) to obtain the voltage across the load Z1.

(Veff)1=(0.6975.56°A)(10070°Ω)=695.56°V

Substitute 69 V for (Veff)1, 0.69 A for Ieff, 5.56° for θ1, and 75.56° for ϕ in Equation (9) to obtain the average power delivered to the load Z1.

P1=(69V)(0.69A)cos[5.56°(75.56°)]=16.2835W16.3W

Substitute 0.6975.56°A for Ieff and 7590°Ω for Z2 in Equation (10) to obtain the voltage across the load Z2.

(Veff)2=(0.6975.56°A)(7590°Ω)=51.7514.44°V

Substitute 51.75 V for (Veff)2, 0.69 A for Ieff, 14.44° for θ2, and 75.56° for ϕ in Equation (11) to obtain the average power delivered to the load Z2.

P2=(51.75V)(0.69A)cos[14.44°(75.56°)]=0W

Substitute 1193°V for Vff and 0.6975.56°A for Ieff in Equation (5) to obtain the complex power supplied by the source.

S=(1193°V)(0.6975.56°A)*=(1193°V)(0.6975.56°A)=82.1178.56°VA=(16.2858+j80.4787)VA

Find the apparent power supplied by the source from the complex power as follows:

|S|=|82.1178.56°VA|=82.11VA

Substitute 3° for θ and 75.56° for ϕ in Equation (6) to obtain the power factor of the combined loads.

PF=cos[3°(75.56°)]0.199

As the imaginary part of the given complex power is positive value, the power factor is lagging power factor.

PF=0.199lagging

Conclusion:

Thus, the average power delivered to Z1, Z2, the apparent power supplied by the source, and the power factor of the combined loads are 16.3W_, 0W_, 82.11VA_, and 0.199lagging_, respectively.

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
For the control system Plot root Locus and find the Jain of stability? RIST. K Kp (S+3) S+5 (s+1) s (S+2) (5765+18) 5-1 5²+35+4 * Mathematically, not by Matlab.
Not use ai please
find the signal genrator for the first circuit

Chapter 11 Solutions

ENGINEERING CIRCUIT...(LL)>CUSTOM PKG.<

Ch. 11 - Determine the power absorbed at t = 1.5 ms by each...Ch. 11 - Calculate the power absorbed at t = 0, t = 0+, and...Ch. 11 - Three elements are connected in parallel: a 1 k...Ch. 11 - Let is = 4u(t) A in the circuit of Fig. 11.28. (a)...Ch. 11 - Prob. 6ECh. 11 - Assuming no transients are present, calculate the...Ch. 11 - Prob. 8ECh. 11 - Prob. 9ECh. 11 - Prob. 10ECh. 11 - The phasor current I=915mA (corresponding to a...Ch. 11 - A phasor voltage V=10045V (the sinusoid operates...Ch. 11 - Prob. 13ECh. 11 - Prob. 14ECh. 11 - Find the average power for each element in the...Ch. 11 - (a) Calculate the average power absorbed by each...Ch. 11 - Prob. 17ECh. 11 - Prob. 18ECh. 11 - Prob. 19ECh. 11 - The circuit in Fig. 11.36 has a series resistance...Ch. 11 - Prob. 21ECh. 11 - Prob. 22ECh. 11 - Prob. 23ECh. 11 - Prob. 24ECh. 11 - Prob. 25ECh. 11 - Prob. 26ECh. 11 - Prob. 27ECh. 11 - Prob. 28ECh. 11 - Prob. 29ECh. 11 - Prob. 30ECh. 11 - Prob. 31ECh. 11 - Prob. 32ECh. 11 - Prob. 33ECh. 11 - (a) Calculate both the average and rms values of...Ch. 11 - Prob. 35ECh. 11 - FIGURE 11.43 Calculate the power factor of the...Ch. 11 - Prob. 37ECh. 11 - Prob. 38ECh. 11 - Prob. 40ECh. 11 - Prob. 41ECh. 11 - Prob. 42ECh. 11 - Prob. 43ECh. 11 - Compute the complex power S (in polar form) drawn...Ch. 11 - Calculate the apparent power, power factor, and...Ch. 11 - Prob. 46ECh. 11 - Prob. 48ECh. 11 - Prob. 49ECh. 11 - Prob. 50ECh. 11 - Prob. 51ECh. 11 - Prob. 52ECh. 11 - FIGURE 11.49 Instead of including a capacitor as...Ch. 11 - Prob. 54ECh. 11 - A load is drawing 10 A rms when connected to a...Ch. 11 - For the circuit of Fig. 11.50, assume the source...Ch. 11 - Prob. 57ECh. 11 - A source 45 sin 32t V is connected in series with...Ch. 11 - Prob. 60ECh. 11 - FIGURE 11.51 The circuit in Fig. 11.51 uses a Pi...Ch. 11 - Prob. 62ECh. 11 - Prob. 63ECh. 11 - You would like to maximize power transfer to a 50 ...
Knowledge Booster
Background pattern image
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:PEARSON
Text book image
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Cengage Learning
Text book image
Programmable Logic Controllers
Electrical Engineering
ISBN:9780073373843
Author:Frank D. Petruzella
Publisher:McGraw-Hill Education
Text book image
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:9780078028229
Author:Charles K Alexander, Matthew Sadiku
Publisher:McGraw-Hill Education
Text book image
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:9780134746968
Author:James W. Nilsson, Susan Riedel
Publisher:PEARSON
Text book image
Engineering Electromagnetics
Electrical Engineering
ISBN:9780078028151
Author:Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:Mcgraw-hill Education,