Two parallel three-phase loads are supplied from 415.7 V rms, 60 Hz three-phase supply. The loads are as follows: Load 1: Y-connected with an impedance of (80 -j 60) Q/ phase Load 2: Delta-connected with an impedance of (48 + j 36) 0/ phase Taking Van as phase reference, determine the power factor of the combined load and the line current in phase a. Select one: O a. Pf= 0.89 (lagging); la 12.87 <-26.5° A b. Pf= 0.982 (lèading); la = 5.209 <+10.418° A O c. Pf= 0.89 (leading); la = 12.87 <+26.5° A O d. Pf= 0.89 (leading); la = 7.415 <+26.5° A Oe. Pf= 0.982 (lagging); la = 5.209 <-10.418° A O f. Pf3 0.982 (leading); la = 3.007 <+10.418° A g. None of these

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
Two parallel three-phase loads are supplied from 415.7 V rms, 60 Hz three-phase supply. The loads are as follows:
Load 1: Y-connected with an impedance of (80 -j 60) Q/ phase
Load 2: Delta-connected with an impedance of (48 +j 36) 0/ phase
Taking Van as phase reference, determine the power factor of the combined load and the line current in phase a.
Select one:
O a. Pf= 0.89 (lagging); la = 12.87 <-26.5° A
O b. Pf= 0.982 (leading); la = 5.209 <+10.418° A
C. Pf= 0.89 (leading); la = 12.87 <+26.5° A
O d. Pf= 0.89 (leading); la =7.415 <+26.5° A
O e. Pf= 0.982 (lagging); la = 5.209 <-10.418° A
Of. Pf= 0.982 (leading); la = 3.007 <+10.418° A
g. None of these
Transcribed Image Text:Two parallel three-phase loads are supplied from 415.7 V rms, 60 Hz three-phase supply. The loads are as follows: Load 1: Y-connected with an impedance of (80 -j 60) Q/ phase Load 2: Delta-connected with an impedance of (48 +j 36) 0/ phase Taking Van as phase reference, determine the power factor of the combined load and the line current in phase a. Select one: O a. Pf= 0.89 (lagging); la = 12.87 <-26.5° A O b. Pf= 0.982 (leading); la = 5.209 <+10.418° A C. Pf= 0.89 (leading); la = 12.87 <+26.5° A O d. Pf= 0.89 (leading); la =7.415 <+26.5° A O e. Pf= 0.982 (lagging); la = 5.209 <-10.418° A Of. Pf= 0.982 (leading); la = 3.007 <+10.418° A g. None of these
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Analysis of Single Phase and Three Phase System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,