Required information Problem 05.087 - Heat exchanger The evaporator of a refrigeration cycle is basically a heat exchanger in which a refrigerant is evaporated by absorbing heat from a fluid. Refrigerant-22 enters an evaporator at 200 kPa with a quality of 22 percent and a flow rate of 2. 65 m³/h. R-22 leaves the evaporator at the same pressure superheated by 5°C. The refrigerant is evaporated by absorbing heat from air whose flow rate is 0.745 kg/s. The properties of R-22 at the inlet and exit of the condenser are h₁ = 220.2 kJ/kg, v₁ = 0.0253 m³/kg, and h₂ = 398.0 kJ/kg. The specific heat of air is taken as 1.005 kJ/kg-°C. Problem 05.087.b - Heat exchanger Determine the temperature change of air. (Round the final answer to three decimal places.) °C. The temperature change of air is Required information Problem 05.087- Heat exchanger The evaporator of a refrigeration cycle is basically a heat exchanger in which a refrigerant is evaporated by absorbing heat from a fluid. Refrigerant-22 enters an evaporator at 200 kPa with a quality of 22 percent and a flow rate of 2.65 m³/h. R-22 leaves the evaporator at the same pressure superheated by 5°C. The refrigerant is evaporated by absorbing heat from air whose flow rate is 0.745 kg/s. The properties of R-22 at the inlet and exit of the condenser are h₁ 220.2 kJ/kg, V₁ = 1.005 kJ/kg °C. 0.0253 m³/kg, and h₂ 398.0 kJ/kg. The specific heat of air is taken as Problem 05.087.a - Heat exchanger Determine the rate of heat absorbed from the air. The rate of heat absorbed from the air is KW

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter44: Geothermal Heat Pumps
Section: Chapter Questions
Problem 12RQ: The function of the pressure tank in an open-loop, geo-thermal heat pump well system is to prevent...
icon
Related questions
Question
Required information
Problem 05.087 - Heat exchanger
The evaporator of a refrigeration cycle is basically a heat exchanger in which a refrigerant is evaporated
by absorbing heat from a fluid. Refrigerant-22 enters an evaporator at 200 kPa with a quality of 22
percent and a flow rate of 2. 65 m³/h. R-22 leaves the evaporator at the same pressure superheated by
5°C. The refrigerant is evaporated by absorbing heat from air whose flow rate is 0.745 kg/s. The
properties of R-22 at the inlet and exit of the condenser are
h₁ = 220.2 kJ/kg, v₁ = 0.0253 m³/kg, and h₂ = 398.0 kJ/kg. The specific heat of air is taken as
1.005 kJ/kg-°C.
Problem 05.087.b - Heat exchanger
Determine the temperature change of air. (Round the final answer to three decimal places.)
°C.
The temperature change of air is
Transcribed Image Text:Required information Problem 05.087 - Heat exchanger The evaporator of a refrigeration cycle is basically a heat exchanger in which a refrigerant is evaporated by absorbing heat from a fluid. Refrigerant-22 enters an evaporator at 200 kPa with a quality of 22 percent and a flow rate of 2. 65 m³/h. R-22 leaves the evaporator at the same pressure superheated by 5°C. The refrigerant is evaporated by absorbing heat from air whose flow rate is 0.745 kg/s. The properties of R-22 at the inlet and exit of the condenser are h₁ = 220.2 kJ/kg, v₁ = 0.0253 m³/kg, and h₂ = 398.0 kJ/kg. The specific heat of air is taken as 1.005 kJ/kg-°C. Problem 05.087.b - Heat exchanger Determine the temperature change of air. (Round the final answer to three decimal places.) °C. The temperature change of air is
Required information
Problem 05.087- Heat exchanger
The evaporator of a refrigeration cycle is basically a heat exchanger in which a refrigerant is evaporated
by absorbing heat from a fluid. Refrigerant-22 enters an evaporator at 200 kPa with a quality of 22
percent and a flow rate of 2.65 m³/h. R-22 leaves the evaporator at the same pressure superheated by
5°C. The refrigerant is evaporated by absorbing heat from air whose flow rate is 0.745 kg/s. The
properties of R-22 at the inlet and exit of the condenser are
h₁ 220.2 kJ/kg, V₁ =
1.005 kJ/kg °C.
0.0253 m³/kg, and h₂
398.0 kJ/kg. The specific heat of air is taken as
Problem 05.087.a - Heat exchanger
Determine the rate of heat absorbed from the air.
The rate of heat absorbed from the air is
KW
Transcribed Image Text:Required information Problem 05.087- Heat exchanger The evaporator of a refrigeration cycle is basically a heat exchanger in which a refrigerant is evaporated by absorbing heat from a fluid. Refrigerant-22 enters an evaporator at 200 kPa with a quality of 22 percent and a flow rate of 2.65 m³/h. R-22 leaves the evaporator at the same pressure superheated by 5°C. The refrigerant is evaporated by absorbing heat from air whose flow rate is 0.745 kg/s. The properties of R-22 at the inlet and exit of the condenser are h₁ 220.2 kJ/kg, V₁ = 1.005 kJ/kg °C. 0.0253 m³/kg, and h₂ 398.0 kJ/kg. The specific heat of air is taken as Problem 05.087.a - Heat exchanger Determine the rate of heat absorbed from the air. The rate of heat absorbed from the air is KW
Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning