Repeat the example on symmetrical faults (page 27 in the class notes) if the fault occurs across the load terminals as shown below. 100 MVA, 11 kV Generator G + 0.05 pu. Reactance M 50 MVA, Motor 0.2 pu sub-transient On 100 MVA Base reactance 3 phase fault 0.25 pu sub-transient reactance The Motor is drawing 40 MW at 0.8 pf. Leading with terminal voltage of 10.95 kV. Calculate the total current in the generator and motor during 3 phase s.c. 27 27
Repeat the example on symmetrical faults (page 27 in the class notes) if the fault occurs across the load terminals as shown below. 100 MVA, 11 kV Generator G + 0.05 pu. Reactance M 50 MVA, Motor 0.2 pu sub-transient On 100 MVA Base reactance 3 phase fault 0.25 pu sub-transient reactance The Motor is drawing 40 MW at 0.8 pf. Leading with terminal voltage of 10.95 kV. Calculate the total current in the generator and motor during 3 phase s.c. 27 27
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter7: Symmetrical Faults
Section: Chapter Questions
Problem 7.3MCQ: The amplitude of the sinusoidal symmetrical ac component of the three-phase short-circuit current of...
Related questions
Question
Please show steps as i will study them

Transcribed Image Text:Repeat the example on symmetrical faults (page 27 in the class notes) if the fault occurs across
the load terminals as shown below.
100 MVA, 11 kV
Generator
G
+
0.05 pu. Reactance
M
50 MVA, Motor
0.2 pu
sub-transient
On 100 MVA Base
reactance
3 phase
fault
0.25 pu
sub-transient
reactance
The Motor is drawing 40 MW at 0.8 pf. Leading with terminal
voltage of 10.95 kV.
Calculate the total current in the generator and motor during
3 phase s.c.
27
27
Expert Solution

This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 2 steps with 1 images

Recommended textbooks for you

Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning


Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning