Q2) The single-line diagram of a three-phase power system is shown in the figure below. The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit using generator 3 ratings as base. Use a 1000-MVA, 765-kV base in the zone of line 1-2. Equipment ratings are given as follows: Synchronous generators: G1 1000 MVA 15 kV G2 1000 MVA 15 kV G3 500 MVA G4 750 MVA Transformers: 13.8 kV 13.8 kV T1 1000 MVA T2 1000 MVA T3 500 MVA T4 750 MVA Transmission lines: 1-2 765 kV 1-3 765 kV 2-3 765 kV 15 kV A/765 kV Y 15 kV A/765 kV Y 15 kV Y/765 kV Y 15 kV Y/765 kV Y X=X₂ = 0.18, Xo = 0.07 per unit X=X₂=0.20, Xo = 0.10 per unit X = X₂ = 0.15, Xo = 0.05 per unit X=0.30, X₂ = 0.40, Xo = 0.10 per unit X₁ = 50 2, Xo = 150 2 X₁ = 40 2, Xo = 100 2 X = 40 Ω, Χ = 100 Ω X = 0.10 per unit X = 0.10 per unit X = 0.12 per unit X = 0.11 per unit

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
icon
Concept explainers
Question
100%
Q2) The single-line diagram of a three-phase power system is shown in the figure
below. The inductor connected to Generator 3 neutral has a reactance of 0.05
per unit using generator 3 ratings as base. Use a 1000-MVA, 765-kV base in
the zone of line 1-2. Equipment ratings are given as follows:
Synchronous generators:
G1 1000 MVA
15 kV
G2 1000 MVA
15 kV
G3 500 MVA
13.8 kV
G4 750 MVA
13.8 kV
Transformers:
T1 1000 MVA
T2 1000 MVA
T3 500 MVA
T4 750 MVA
Transmission lines:
1-2 765 kV
1-3 765 kV
2-3 765 kV
15 kV A/765 kV Y
15 kV A/765 kV Y
15 kV Y/765 kV Y
15 kV Y/765 kV Y
X = X₂ = 0.18, Xo = 0.07 per unit
X=X₂=0.20, Xo = 0.10 per unit
X=X₂ = 0.15, Xo = 0.05 per unit
X=0.30, X₂ = 0.40, Xo = 0.10 per unit
X₁ = 50 2, Xo = 150 2
X₁ = 40 2, Xo = 100 2
X₁ = 40 2, Xo = 100 2
at
Line 1-3
Line 1-2
2
X = 0.10 per unit
X = 0.10 per unit
X = 0.12 per unit
X = 0.11 per unit
Line 2-3
3
youtly
Transcribed Image Text:Q2) The single-line diagram of a three-phase power system is shown in the figure below. The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit using generator 3 ratings as base. Use a 1000-MVA, 765-kV base in the zone of line 1-2. Equipment ratings are given as follows: Synchronous generators: G1 1000 MVA 15 kV G2 1000 MVA 15 kV G3 500 MVA 13.8 kV G4 750 MVA 13.8 kV Transformers: T1 1000 MVA T2 1000 MVA T3 500 MVA T4 750 MVA Transmission lines: 1-2 765 kV 1-3 765 kV 2-3 765 kV 15 kV A/765 kV Y 15 kV A/765 kV Y 15 kV Y/765 kV Y 15 kV Y/765 kV Y X = X₂ = 0.18, Xo = 0.07 per unit X=X₂=0.20, Xo = 0.10 per unit X=X₂ = 0.15, Xo = 0.05 per unit X=0.30, X₂ = 0.40, Xo = 0.10 per unit X₁ = 50 2, Xo = 150 2 X₁ = 40 2, Xo = 100 2 X₁ = 40 2, Xo = 100 2 at Line 1-3 Line 1-2 2 X = 0.10 per unit X = 0.10 per unit X = 0.12 per unit X = 0.11 per unit Line 2-3 3 youtly
a) Draw the zero, positive, and negative sequence reactance diagrams.
b) For a fault at bus 3, determine the thevenin equivalent of each sequence
network as viewed from the fault bus. Prefault voltage is 1 per unit. (use the
wye-delta transformation)
A
с
B
ZAB=
ZBC
ZCA =
ZCA
ZAZB+ Z₂Zc+ ZcZA
Zc
ZAZB+ ZBZc+ ZcZA
ZA
ZAZB+ ZBZc+ZCZA
ZB
B
Z₁ =
Z₁ =
Zc =
ZABZCA
ZAB + ZBC + ZCA
ZABZBC
ZAB + ZBC + ZCA
ZCAZBC
ZAB + ZBC + ZCA
c) Determine the subtransient fault current in per unit and in kA, as well as the
per unit line-to-ground voltages at the fault bus for a bolted single line-to-
ground fault at bus 3.
Transcribed Image Text:a) Draw the zero, positive, and negative sequence reactance diagrams. b) For a fault at bus 3, determine the thevenin equivalent of each sequence network as viewed from the fault bus. Prefault voltage is 1 per unit. (use the wye-delta transformation) A с B ZAB= ZBC ZCA = ZCA ZAZB+ Z₂Zc+ ZcZA Zc ZAZB+ ZBZc+ ZcZA ZA ZAZB+ ZBZc+ZCZA ZB B Z₁ = Z₁ = Zc = ZABZCA ZAB + ZBC + ZCA ZABZBC ZAB + ZBC + ZCA ZCAZBC ZAB + ZBC + ZCA c) Determine the subtransient fault current in per unit and in kA, as well as the per unit line-to-ground voltages at the fault bus for a bolted single line-to- ground fault at bus 3.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 5 steps with 6 images

Blurred answer
Knowledge Booster
Fault analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,