Q2) The single-line diagram of a three-phase power system is shown in the figure below. The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit using generator 3 ratings as base. Use a 1000-MVA, 765-kV base in the zone of line 1-2. Equipment ratings are given as follows: Synchronous generators: G1 1000 MVA 15 kV G2 1000 MVA 15 kV G3 500 MVA G4 750 MVA Transformers: 13.8 kV 13.8 kV T1 1000 MVA T2 1000 MVA T3 500 MVA T4 750 MVA Transmission lines: 1-2 765 kV 1-3 765 kV 2-3 765 kV 15 kV A/765 kV Y 15 kV A/765 kV Y 15 kV Y/765 kV Y 15 kV Y/765 kV Y X=X₂ = 0.18, Xo = 0.07 per unit X=X₂=0.20, Xo = 0.10 per unit X = X₂ = 0.15, Xo = 0.05 per unit X=0.30, X₂ = 0.40, Xo = 0.10 per unit X₁ = 50 2, Xo = 150 2 X₁ = 40 2, Xo = 100 2 X = 40 Ω, Χ = 100 Ω X = 0.10 per unit X = 0.10 per unit X = 0.12 per unit X = 0.11 per unit

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
icon
Concept explainers
Question
100%
Q2) The single-line diagram of a three-phase power system is shown in the figure
below. The inductor connected to Generator 3 neutral has a reactance of 0.05
per unit using generator 3 ratings as base. Use a 1000-MVA, 765-kV base in
the zone of line 1-2. Equipment ratings are given as follows:
Synchronous generators:
G1 1000 MVA
15 kV
G2 1000 MVA
15 kV
G3 500 MVA
13.8 kV
G4 750 MVA
13.8 kV
Transformers:
T1 1000 MVA
T2 1000 MVA
T3 500 MVA
T4 750 MVA
Transmission lines:
1-2 765 kV
1-3 765 kV
2-3 765 kV
15 kV A/765 kV Y
15 kV A/765 kV Y
15 kV Y/765 kV Y
15 kV Y/765 kV Y
X = X₂ = 0.18, Xo = 0.07 per unit
X=X₂=0.20, Xo = 0.10 per unit
X=X₂ = 0.15, Xo = 0.05 per unit
X=0.30, X₂ = 0.40, Xo = 0.10 per unit
X₁ = 50 2, Xo = 150 2
X₁ = 40 2, Xo = 100 2
X₁ = 40 2, Xo = 100 2
at
Line 1-3
Line 1-2
2
X = 0.10 per unit
X = 0.10 per unit
X = 0.12 per unit
X = 0.11 per unit
Line 2-3
3
youtly
Transcribed Image Text:Q2) The single-line diagram of a three-phase power system is shown in the figure below. The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit using generator 3 ratings as base. Use a 1000-MVA, 765-kV base in the zone of line 1-2. Equipment ratings are given as follows: Synchronous generators: G1 1000 MVA 15 kV G2 1000 MVA 15 kV G3 500 MVA 13.8 kV G4 750 MVA 13.8 kV Transformers: T1 1000 MVA T2 1000 MVA T3 500 MVA T4 750 MVA Transmission lines: 1-2 765 kV 1-3 765 kV 2-3 765 kV 15 kV A/765 kV Y 15 kV A/765 kV Y 15 kV Y/765 kV Y 15 kV Y/765 kV Y X = X₂ = 0.18, Xo = 0.07 per unit X=X₂=0.20, Xo = 0.10 per unit X=X₂ = 0.15, Xo = 0.05 per unit X=0.30, X₂ = 0.40, Xo = 0.10 per unit X₁ = 50 2, Xo = 150 2 X₁ = 40 2, Xo = 100 2 X₁ = 40 2, Xo = 100 2 at Line 1-3 Line 1-2 2 X = 0.10 per unit X = 0.10 per unit X = 0.12 per unit X = 0.11 per unit Line 2-3 3 youtly
a) Draw the zero, positive, and negative sequence reactance diagrams.
b) For a fault at bus 3, determine the thevenin equivalent of each sequence
network as viewed from the fault bus. Prefault voltage is 1 per unit. (use the
wye-delta transformation)
A
с
B
ZAB=
ZBC
ZCA =
ZCA
ZAZB+ Z₂Zc+ ZcZA
Zc
ZAZB+ ZBZc+ ZcZA
ZA
ZAZB+ ZBZc+ZCZA
ZB
B
Z₁ =
Z₁ =
Zc =
ZABZCA
ZAB + ZBC + ZCA
ZABZBC
ZAB + ZBC + ZCA
ZCAZBC
ZAB + ZBC + ZCA
c) Determine the subtransient fault current in per unit and in kA, as well as the
per unit line-to-ground voltages at the fault bus for a bolted single line-to-
ground fault at bus 3.
Transcribed Image Text:a) Draw the zero, positive, and negative sequence reactance diagrams. b) For a fault at bus 3, determine the thevenin equivalent of each sequence network as viewed from the fault bus. Prefault voltage is 1 per unit. (use the wye-delta transformation) A с B ZAB= ZBC ZCA = ZCA ZAZB+ Z₂Zc+ ZcZA Zc ZAZB+ ZBZc+ ZcZA ZA ZAZB+ ZBZc+ZCZA ZB B Z₁ = Z₁ = Zc = ZABZCA ZAB + ZBC + ZCA ZABZBC ZAB + ZBC + ZCA ZCAZBC ZAB + ZBC + ZCA c) Determine the subtransient fault current in per unit and in kA, as well as the per unit line-to-ground voltages at the fault bus for a bolted single line-to- ground fault at bus 3.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 5 steps with 6 images

Blurred answer
Knowledge Booster
Fault analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,