Q10 The full-load copper loss on the H.V. side of 100KVA, 11000/317 V, single-phase transformer is 0.62 kw and on the L.V. side is 0.48 kW. i) Calculate R1, R2 in ohms ii) Find X1,X2,if the percentage equivalent reactance is 4%, and reactance is divided in same proportion as resistance. Ans, 27.30, 0.175), 0.00482 . (7.5)

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.28MCQ
icon
Related questions
Question
Q10 The full-load copper loss on the H.V. side of 100KVA, 11000/317 V, single-phase transformer is
0.62 kw and on the L.V. side is 0.48 kW. i) Calculate R1, R2 in ohms ii) Find X1,X2,if the percentage
equivalent reactance is 4%, and reactance is divided in same proportion as resistance. Ans, 27.30,
0.175), 0.00482 . (7.5)
Transcribed Image Text:Q10 The full-load copper loss on the H.V. side of 100KVA, 11000/317 V, single-phase transformer is 0.62 kw and on the L.V. side is 0.48 kW. i) Calculate R1, R2 in ohms ii) Find X1,X2,if the percentage equivalent reactance is 4%, and reactance is divided in same proportion as resistance. Ans, 27.30, 0.175), 0.00482 . (7.5)
Expert Solution
steps

Step by step

Solved in 2 steps with 9 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning