G उह T₁ Line 3 M T₂
The ff. figure shows the single-line diagram consisting of a synchronous generator feeding a synchronous motor through two transformers and a transmission line. The generator is rated 100 MVA, 13.8 kV with Xd” = 0.15 pu. The synchronous motor is rated 100 MVA, 13.8 kV with Xd” = 0.20 pu. Both three-phase transformers are rated 100 MVA, 13.8/138 kV with leakage reactance of 0.10 pu. The series reactance of the line is 20 ohms. The synchronous generator is operating at rated MVA, 0.95 pf lagging and at 5% above rated voltage when a bolted three-phase fault occurs at the generator terminals. Calculate the pu values of (a) subtransient fault current and (b) subtransient generator and motor currents during this fault.