Determine the regulation at 0.8 lagging power factor of a 10 KVA transformer the characteristics of which are given below. 

 

240/120 volts ri = 0.13 ohm r2= 0.03 ohm xi = 0.20 ohm x2 = 0.05 ohm Core Loss = 85 watts In = 1.0 ampere 

The terminal voltage at full load is 110 volts.

Expert Solution
steps

Step by step

Solved in 3 steps

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning