Consider the plunger-type relay shown below. The pickup current is 5A and the drop out current is 3.57A. The pole face has a height of 1.5 cm, while the spring holds the plunger 1 cm out of the coil when the current is below the pickup value. The air gap 'g' is 0.2 cm, and 'gd/4a' = 0.05. Let the spring force Fs be a constant, with a value of 0.001 N, and let the mass of the plunger be 0.005 kg. Let the travel of the plunger be 3 mm before it hits a stop and closes its contacts. If I-2, then the operating time would be equal to: F Select one: a. None of these O b. 1.25s ○ c. 0.75s O d. 0.25s t = 100(x-x1) 1.48 In-1 Consider the system below where a fault F has taken place between breakers B1 and B2. If R1, B1, R5, B5, R6 and B6 operate, then the system response would be characterized by the following: Rs B R3 B3 R₁ B₁ R2 B2 R4 B4 R6 Be Select one: O a. Response incorrect and inappropriate b. All of these ○ c. R2 failed to operate: Incorrect and loss of security O d. R5, R6 initiate B5, B6 as remote back up protection Clear my choice
Consider the plunger-type relay shown below. The pickup current is 5A and the drop out current is 3.57A. The pole face has a height of 1.5 cm, while the spring holds the plunger 1 cm out of the coil when the current is below the pickup value. The air gap 'g' is 0.2 cm, and 'gd/4a' = 0.05. Let the spring force Fs be a constant, with a value of 0.001 N, and let the mass of the plunger be 0.005 kg. Let the travel of the plunger be 3 mm before it hits a stop and closes its contacts. If I-2, then the operating time would be equal to: F Select one: a. None of these O b. 1.25s ○ c. 0.75s O d. 0.25s t = 100(x-x1) 1.48 In-1 Consider the system below where a fault F has taken place between breakers B1 and B2. If R1, B1, R5, B5, R6 and B6 operate, then the system response would be characterized by the following: Rs B R3 B3 R₁ B₁ R2 B2 R4 B4 R6 Be Select one: O a. Response incorrect and inappropriate b. All of these ○ c. R2 failed to operate: Incorrect and loss of security O d. R5, R6 initiate B5, B6 as remote back up protection Clear my choice
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter12: Power System Controls
Section: Chapter Questions
Problem 12.4P
Related questions
Question
Please solve these two questions

Transcribed Image Text:Consider the plunger-type relay shown below. The pickup current is 5A and the drop out current is 3.57A. The pole face has a height of 1.5
cm, while the spring holds the plunger 1 cm out of the coil when the current is below the pickup value. The air gap 'g' is 0.2 cm, and 'gd/4a'
= 0.05. Let the spring force Fs be a constant, with a value of 0.001 N, and let the mass of the plunger be 0.005 kg. Let the travel of the
plunger be 3 mm before it hits a stop and closes its contacts. If I-2, then the operating time would be equal to:
F
Select one:
a.
None of these
O b. 1.25s
○ c. 0.75s
O d. 0.25s
t =
100(x-x1)
1.48 In-1

Transcribed Image Text:Consider the system below where a fault F has taken place between breakers B1 and B2. If R1, B1, R5, B5, R6 and B6 operate, then the system
response would be characterized by the following:
Rs B
R3 B3
R₁ B₁
R2 B2
R4 B4
R6 Be
Select one:
O a. Response incorrect and inappropriate
b. All of these
○ c.
R2 failed to operate: Incorrect and loss of security
O d. R5, R6 initiate B5, B6 as remote back up protection
Clear my choice
Expert Solution

This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 2 steps with 3 images

Recommended textbooks for you

Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning

Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning


Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning

Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning